Inosaki is one of the largest Phoenix Contact Distributors to provide terminal block, interface module, power supply and relay. And our best offer for terminal block types are Feed-through, Fuse Modular, Spring Cage, Double Level, and Multi-level, hence the series model references to PT Series, ST Series, TB Series, UT Series, UK Series. In additional for power supply are QUINT Power, STEP Power, Trio Power, and UNO Power. Please email us for catalog: sales@inosaki.my
Dimensions
Width |
59 mm |
Height |
130 mm |
Depth |
129 mm |
|
125 mm (Device depth (DIN rail mounting)) |
Installation distance right/left (active, passive) |
0 mm / 0 mm (POut ≥50% ) |
Installation distance top/bottom (active, passive) |
30 mm / 30 mm (POut ≥50% ) |
Ambient conditions
Ambient temperature (operation) |
-25 °C … 70 °C (> 55 °C Derating: 2.5 %/K) |
Ambient temperature (start-up type tested) |
-40 °C |
Ambient temperature (storage/transport) |
-40 °C … 85 °C |
Max. permissible relative humidity (operation) |
≤ 95 % (at 25 °C, non-condensing) |
Maximum altitude |
≤ 3000 m (> 2000 m, Derating: 10 %/1000 m) |
Degree of pollution |
2 |
Climatic class |
3K3 (in acc. with EN 60721) |
Input data
Nominal input voltage range |
100 V AC … 240 V AC |
Input voltage range |
100 V AC … 240 V AC -15 % … +10 % |
Derating |
< 90 V AC (1 %/V) |
Frequency range (fN) |
50 Hz … 60 Hz 10 % |
Typical national grid voltage |
120 V AC |
|
230 V AC |
Voltage type of supply voltage |
AC |
Current consumption |
5.4 A (100 V AC) |
|
4.4 A (120 V AC) |
|
2.3 A (230 V AC) |
|
2.2 A (240 V AC) |
Discharge current to PE |
< 3.5 mA |
Mains buffering time |
typ. 17 ms (120 V AC) |
|
typ. 18 ms (230 V AC) |
Switch-on time |
typ. 1 s |
Inrush current |
typ. 15 A (at 25 °C) |
Inrush current integral (I2t) |
< 1 A2s |
Type of protection |
Transient protection |
Protective circuit/component |
Varistor, gas-filled surge arrester |
Device mains fuse |
8 A internal (device protection), fast-blow |
Recommended breaker for input protection |
10 A … 16 A (Characteristic B, C, D, K or comparable) |
Output data
Nominal output voltage |
24 V DC |
Setting range of the output voltage (USet) |
24 V DC … 28 V DC (> 24 V DC, constant capacity restricted) |
Nominal output current (IN) |
20 A |
Control deviation |
< 1 % (change in load, static 10 % … 90 %) |
|
< 3 % (change in load, dynamic 10 % … 90 %) |
|
< 0.1 % (change in input voltage ±10 %) |
Short-circuit-proof |
yes |
No-load proof |
yes |
Residual ripple |
typ. 70 mVPP (with nominal values) |
Connection in parallel |
yes, for redundancy |
Connection in series |
yes, for increased output voltage |
Feedback voltage resistance |
≤ 35 V DC |
Protection against overvoltage at the output (OVP) |
≤ 35 V DC |
Rise time |
< 1 s (UOut = 10 % … 90 %) |
Derating |
55 °C … 70 °C |
Crest factor |
typ. 1,667 (120 V AC) |
|
typ. 1,75 (230 V AC) |
Minimum no-load power dissipation |
< 2.9 W (120 V AC) |
Maximum power dissipation in no-load condition |
< 3 W (230 V AC) |
Minimum nominal load power dissipation |
< 37 W (120 V AC) |
Power loss nominal load max. |
< 28 W (230 V AC) |
General
Article Number |
2910105 |
Net weight |
1 kg |
Environmental protection directive |
RoHS Directive 2011/65/EU |
|
WEEE |
|
Reach |
Efficiency |
typ. 93 % (120 V AC) |
|
typ. 94.6 % (230 V AC) |
MTBF (IEC 61709, SN 29500) |
> 900000 h (25 °C) |
|
> 530000 h (40 °C) |
|
> 280000 h (55 °C) |
Insulation voltage input/output |
4 kV AC (type test) |
|
3 kV AC (routine test) |
Insulation voltage input / PE |
3.5 kV AC (type test) |
|
2.4 kV AC (routine test) |
Degree of protection |
IP20 |
Protection class |
I |
Housing material |
Aluminum (AlMg3) / sheet steel, zinc-plated |
Foot latch material |
Sheet steel, zinc-plated |
Mounting position |
horizontal DIN rail NS 35, EN 60715 |
Assembly instructions |
alignable: 0 mm horizontally, 30 mm vertically |
Input connection data
Connection method |
Screw connection |
Stripping length |
8 mm |
Conductor cross section solid |
0.2 mm² … 6 mm² |
Conductor cross section flexible |
0.2 mm² … 4 mm² |
Flexible conductor cross section (ferrule with plastic sleeve) |
0.25 mm² … 4 mm² |
Flexible conductor cross section flexible (ferrule, w/o plastic sleeve) |
0.25 mm² … 4 mm² |
Conductor cross section AWG |
24 … 10 (Cu) |
Torque |
0.5 Nm … 0.6 Nm |
Output connection data
Connection method |
Screw connection |
Stripping length |
8 mm |
Conductor cross section solid |
0.2 mm² … 6 mm² |
Conductor cross section flexible |
0.2 mm² … 4 mm² |
Flexible conductor cross section (ferrule with plastic sleeve) |
0.25 mm² … 4 mm² |
Flexible conductor cross section flexible (ferrule, w/o plastic sleeve) |
0.25 mm² … 4 mm² |
Conductor cross section AWG |
24 … 10 (Cu) |
Torque |
0.5 Nm … 0.6 Nm |
Signal connection data
Connection method |
Screw connection |
Stripping length |
8 mm |
Conductor cross section solid |
0.2 mm² … 6 mm² |
Conductor cross section flexible |
0.2 mm² … 4 mm² |
Flexible conductor cross section (ferrule with plastic sleeve) |
0.25 mm² … 4 mm² |
Flexible conductor cross section flexible (ferrule, w/o plastic sleeve) |
0.25 mm² … 4 mm² |
Conductor cross section AWG |
24 … 10 (Cu) |
Torque |
0.5 Nm … 0.6 Nm |
LED signaling
Types of signaling |
LED DC OK – signal state operation (UN = 24 V DC, IOut = IN) |
Signal contacts – signal output relay 13/14 (configurable)
Maximum contact load |
30 V AC/DC |
|
100 mA |
Connection level |
3.x |
Connection labeling |
3.1 (13), 3.2 (14) |
Function |
Operating state forwarding |
Switch contact |
OptoMOS |
Switching voltage |
max. 30 V AC |
|
max. 60 V DC |
Current carrying capacity |
max. 50 mA |
State condition |
UOUT > 0,9 x UN (Contact closed) |
|
UOUT < 0,9 x UN (Contact open) |
Standards
EMC requirements for noise immunity |
EN 61000-6-2 |
Standard designation |
Safety of power supply units up to 1100 V (insulation distances) |
Standards/regulations |
DIN EN 61558-2-16 |
Standard designation |
Electrical safety |
Standards/regulations |
IEC 61010-2-201 (SELV) |
Standard designation |
Equipping high voltage installations with electronic equipment |
Standards/regulations |
EN 50178/VDE 0160 (PELV) |
Standard designation |
Safety for equipment for measurement, control, and laboratory use |
Standards/regulations |
IEC 61010-1 |
Standard designation |
Protective extra-low voltage |
Standards/regulations |
IEC 61010-1 (SELV) |
|
IEC 61010-2-201 (PELV) |
Standard designation |
Safe isolation |
Standards/regulations |
IEC 61558-2-16 |
|
IEC 61010-2-201 |
Standard designation |
Limitation of harmonic line currents |
Standards/regulations |
EN 61000-3-2 |
Standard designation |
Requirement of the semiconductor industry with regard to mains voltage dips |
Standards/regulations |
SEMI F47 – 0706 (185 V AC) |
Overvoltage category EN 61010-1 |
II (≤ 3000 m) |
Overvoltage category EN 62477-1 |
III (≤3000 m) |
Conformance/approvals
Designation |
UL |
Identification |
UL/C-UL Listed UL 61010-1 |
Designation |
UL |
Identification |
UL/C-UL Listed UL 61010-2-201 |
Designation |
UL |
Identification |
UL/C-UL Listed ANSI/UL 121201 Class I, Division 2, Groups A, B, C, D (Hazardous Location) |
Designation |
SIQ |
Identification |
CB scheme (IEC 61010-1, IEC 61010-2-201) |
EMC data
Electromagnetic compatibility |
Conformance with EMC Directive 2014/30/EU |
Low Voltage Directive |
Conformance with Low Voltage Directive 2014/35/EC |
Conducted noise emission |
EN 55016 |
|
EN 61000-6-3 (Class B) |
Noise emission |
EN 55016 |
|
EN 61000-6-3 (Class B) |
Harmonic currents |
EN 61000-3-2 |
|
EN 61000-3-2 (Class A) |
Electrostatic discharge |
EN 61000-4-2 |
Contact discharge |
6 kV (Test Level 3) |
Discharge in air |
8 kV (Test Level 3) |
Electromagnetic HF field |
EN 61000-4-3 |
Frequency range |
80 MHz … 1 GHz |
Test field strength |
10 V/m (Test Level 3) |
Frequency range |
1 GHz … 6 GHz |
Test field strength |
10 V/m (Test Level 3) |
Comments |
Criterion A |
Fast transients (burst) |
EN 61000-4-4 |
Input |
4 kV (Test Level 4 – asymmetrical) |
Output |
2 kV (Test Level 3 – asymmetrical) |
Comments |
Criterion A |
Surge voltage load (surge) |
EN 61000-4-5 |
Input |
2 kV (Test Level 3 – symmetrical) |
|
4 kV (Test Level 4 – asymmetrical) |
Output |
1 kV (Test Level 2 – symmetrical) |
|
2 kV (Test Level 3 – asymmetrical) |
Comments |
Criterion A |
Conducted interference |
EN 61000-4-6 |
Frequency range |
0.15 MHz … 80 MHz |
Voltage |
10 V (Test Level 3) |
Comments |
Criterion A |
Voltage dips |
EN 61000-4-11 |
Voltage |
230 V AC |
Frequency |
50 Hz |
Voltage dip |
70 % |
Number of periods |
25 / 30 periods |
Comments |
Criterion A |
Voltage dip |
40 % |
Number of periods |
12 periods |
Additional text |
Test Level 2 |
Comments |
Criterion A |
Voltage dip |
0 % |
Number of periods |
1 period |
Additional text |
Test Level 2 |
Comments |
Criterion B |
Criterion A |
Normal operating behavior within the specified limits. |
Criterion B |
Temporary impairment to operational behavior that is corrected by the device itself. |
Environmental Product Compliance
REACh SVHC |
Lead 7439-92-1 |
China RoHS |
Environmentally Friendly Use Period = 25; |
|
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer’s declaration” |