SIMATIC S7-200 Smart – Digital Output Expansion Modules – Siemens Modules

USD $ 68.25

SKU: N/A

The new S7-200 SMART has two different types of CPU modules, i.e. standard type and compact type.
Standard type CPU is expandable with I/O expansion modules and signal boards. Compact type CPUs are non expandable with I/O expansion modules and signal boards.

Product Specifications :

Model EM DR08 EM DT08
Order No.: (MLFB) 6ES7 288-2DR08-0AA0 6ES7 288-2DT08-0AA0
Standard
Dimension W x H x D (mm) 45 x 100 x 81
Weight 166.3 g 147 g
Power consumption 4.5 W 1.5 W
Current consumption (SM bus) 120 mA
Current consumption (24 V DC) Each relay coil used is 11 mA
 –
Digital output
Number of outputs 8
Type Relay, dry contact Solid state-MOSFET (source-type)
Voltage range 5 ~ 30 V DC or 5 ~ 250 V AC 20.4 ~ 28.8 V DC
Logic 1 signal when the current is max. 20 V
Logic 0 signal when the load is KG 0.1 V
Rated current at each point (max) 2.0 A 0.75 A
Lamp load 30 W DC/200 W AC 5 W DC
Resistance of the contact in the ON state New equipment is 0.2 Ω maximally 0.6 Ω
Leakage current at each point 10 μ A
Surge current It is 7A when the contact is closed 8 A, max. lasting 100 ms
Overload protection none
Isolation (field side and logic side) 1500 V AC, lasting 1 min (coil and contact) none, (coil and logic side) 500 V AC, lasting 1 min
Isolation resistance New equipment is 100 MΩ minimally
Disconnect the insulation between the contacts 750 V AC, lasting 1 min
Isolated group 2 2
Current of each public end (max) 8:00 AM 3:00 AM
Inductive voltage clamp – 48 V DC
Switching delay Max. 10 ms From the disconnection to connection max.50 μs from the connection to disconnection is 200 μs max.
Mechanical life (no load) 10,000,000 break/close cycles
Contact life under the rated load 100,000 break/close cycles
Output state under the STOP mode Last value or replicable value (The default value is 0)
Number of output that are connected at the same time 8
Cable length Shielded: 500 m; non shielded: 300 m
Weight N/A