| input | |
| type of the power supply network | 1-phase and 2-phase AC | 
| supply voltage at AC | Set by means of selector switch on the device | 
| supply voltage 1 at AC | 120 … 230 V | 
| supply voltage 2 at AC | 230 … 500 V | 
| input voltage 1 at AC | 85 … 264 V | 
| input voltage 2 at AC | 176 … 550 V | 
| wide range input | Yes | 
| overvoltage overload capability | 1300 Vpeak, 1.3 ms | 
| buffering time for rated value of the output current in the event of power failure minimum | 25 ms | 
| operating condition of the mains buffering | at Vin = 120/230 V, typ. 150 ms at Vin = 400 V | 
| line frequency | 50/60 Hz | 
| line frequency | 47 … 63 Hz | 
| input current | |
| ● at rated input voltage 120 V | 4.4 A | 
| ● at rated input voltage 230 V | 2.4 A | 
| ● at rated input voltage 500 V | 1.1 A | 
| current limitation of inrush current at 25 °C maximum | 35 A | 
| I2t value maximum | 4 A²·s | 
| fuse protection type | T 6.3 A (not accessible) | 
| fuse protection type in the feeder | Recommended miniature circuit breaker at 1-phase operation: from 6 A (10 A) characteristic C (B); required at 2-phase operation: circuit breaker 2-pole connected or circuit breaker 3RV2011-1EA10 (setting 3.8 A) or 3RV2711- 1ED10 (UL 489) at 230 V; 3RV2011-1DA10 (setting 3 A) or 3RV2711-1DD10 (UL 489) at 400/500 V | 
| output | |
| voltage curve at output | Controlled, isolated DC voltage | 
| output voltage at DC rated value | 24 V | 
| output voltage | |
| ● at output 1 at DC rated value | 24 V | 
| output voltage adjustable | Yes; via potentiometer | 
| adjustable output voltage | 24 … 28.8 V | 
| relative overall tolerance of the voltage | 3 % | 
| relative control precision of the output voltage | |
| ● on slow fluctuation of input voltage | 0.1 % | 
| ● on slow fluctuation of ohm loading | 0.1 % | 
| residual ripple | |
| ● maximum | 50 mV | 
| voltage peak | |
| ● maximum | 200 mV | 
| display version for normal operation | Green LED for 24 V OK | 
| type of signal at output | relay contact (normally open, contact rating (SELV (ES1) must be observed): 30 V DC/0.1 A | 
| behavior of the output voltage when switching on | Overshoot of Vout approx. 3 % | 
| response delay maximum | 1 s | 
| voltage increase time of the output voltage | |
| ● typical | 50 ms | 
| output current | |
| ● rated value | 10 A | 
| ● rated range | 0 … 10 A; +60 … +70 °C: Derating 2%/K (at 120 V, 230 V) or 3.5%/K (at 400 V) | 
| supplied active power typical | 240 W | 
| short-term overload current | |
| ● at short-circuit during operation typical | 30 A | 
| duration of overloading capability for excess current | |
| ● at short-circuit during operation | 25 ms | 
| constant overload current | |
| ● on short-circuiting during the start-up typical | 12 A | 
| bridging of equipment | Yes; switchable characteristic | 
| number of parallel-switched equipment resources for increasing the power | 2 | 
| efficiency | |
| efficiency in percent | 91 % | 
| power loss [W] | |
| ● at rated output voltage for rated value of the output current typical | 24 W | 
| ● during no-load operation maximum | 6 W | 
| closed-loop control | |
| relative control precision of the output voltage with rapid fluctuation of the input voltage by +/- 15% typical | 0.1 % | 
| relative control precision of the output voltage load step of resistive load 50/100/50 % typical | 3 % | 
| setting time | |
| ● load step 50 to 100% typical | 2 ms | 
| ● load step 100 to 50% typical | 2 ms | 
| setting time | |
| ● maximum | 5 ms | 
| protection and monitoring | |
| design of the overvoltage protection | < 35 V | 
| property of the output short-circuit proof | Yes | 
| design of short-circuit protection | Alternatively, constant current characteristic approx. 12 A or latching shutdown | 
| ● typical | 12 A | 
| enduring short circuit current RMS value | |
| ● typical | 12 A | 
| display version for overload and short circuit | LED yellow for “overload”, LED red for “latching shutdown” | 
| safety | |
| galvanic isolation between input and output | Yes | 
| galvanic isolation | Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 | 
| operating resource protection class | Class I | 
| leakage current | |
| ● maximum | 3.5 mA | 
| ● typical | 0.32 mA | 
| protection class IP | IP20 | 
| EMC | |
| standard | |
| ● for emitted interference | EN 55022 Class B | 
| ● for mains harmonics limitation | EN 61000-3-2 | 
| ● for interference immunity | EN 61000-6-2 | 
| standards, specifications, approvals | |
| certificate of suitability | |
| ● CE marking | Yes | 
| ● UL approval | Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1) | 
| ● CSA approval | Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1) | 
| ● UKCA marking | Yes | 
| ● EAC approval | Yes | 
| ● Regulatory Compliance Mark (RCM) | Yes | 
| ● NEC Class 2 | No | 
| ● SEMI F47 | Yes | 
| type of certification | |
| ● CB-certificate | Yes | 
| MTBF at 40 °C | 1 055 408 h | 
| standards, specifications, approvals hazardous environments | |
| certificate of suitability | |
| ● IECEx | No | 
| ● ATEX | No | 
| ● ULhazloc approval | No | 
| ● cCSAus, Class 1, Division 2 | No | 
| ● FM registration | No | 
| standards, specifications, approvals marine classification | |
| shipbuilding approval | Yes | 
| Marine classification association | |
| ● American Bureau of Shipping Europe Ltd. (ABS) | Yes | 
| ● French marine classification society (BV) | No | 
| ● Det Norske Veritas (DNV) | Yes | 
| ● Lloyds Register of Shipping (LRS) | No | 
| standards, specifications, approvals Environmental Product Declaration | |
| Environmental Product Declaration | Yes | 
| global warming potential [CO2 eq] | |
| ● total | 763.9 kg | 
| ● during manufacturing | 12.6 kg | 
| ● during operation | 751 kg | 
| ● after end of life | 0.18 kg | 
| ambient conditions | |
| ambient temperature | |
| ● during operation | -25 … +70; With natural convection; startup tested starting from -40 °C nominal voltage | 
| ● during transport | -40 … +85 | 
| ● during storage | -40 … +85 | 
| environmental category according to IEC 60721 | Climate class 3K3, 5 … 95% no condensation | 
| connection method | |
| type of electrical connection | screw terminal | 
| ● at input | L, N, PE: 1 screw terminal each for 0.2 … 2.5 mm² single-core/finely stranded | 
| ● at output | +, -: 2 screw terminals each for 0.2 … 2.5 mm² | 
| ● for auxiliary contacts | 13, 14 (alarm signal): 1 screw terminal each for 0.14 … 1.5 mm² | 
| mechanical data | |
| width × height × depth of the enclosure | 70 × 125 × 121 mm | 
| installation width × mounting height | 70 mm × 225 mm | 
| required spacing | |
| ● top | 50 mm | 
| ● bottom | 50 mm | 
| ● left | 0 mm | 
| ● right | 0 mm | 
| fastening method | Snaps onto DIN rail EN 60715 35×7.5/15 | 
| ● DIN-rail mounting | Yes | 
| ● S7 rail mounting | No | 
| ● wall mounting | No | 
| housing can be lined up | Yes | 
| net weight | 0.8 kg | 
| accessories | |
| electrical accessories | Buffer module |