SINAMICS V20 Basic Converter – 1AC 200 V, FSAA, 0.25 kW – Siemens Standard Performance Frequency Converters

USD $ 114.45USD $ 180.60

SKU: N/A
SINAMICS V20 – The cost-effective, reliable and easy-to-use converter for basic applications

Today, in an increasing number of applications in plant and machinery construction, individual automation and drive solutions are demanded that automate simple motion sequences with low associated requirements.

The compact SINAMICS V20, the basic performance converter, offers a simple and cost-effective drive solution for these types of applications. SINAMICS V20 sets itself apart with its quick commissioning times, ease of operation, robustness and cost-efficiency.

With nine frame sizes, it covers a power range extending from 0.12 kW to 30 kW (0.16 hp to 40 hp).

Minimizing costs

SINAMICS V20 keeps engineering and commissioning costs as well as those in operation as low as possible. To increase energy efficiency, the converter is equipped with a control technique to achieve optimum energy efficiency through automatic flux reduction. Not only this, it displays the actual energy consumption and has additional, integrated energy-saving functions. This allows energy consumption to be slashed drastically.

Siemens Converters V20 Product Specifications:

SINAMICS V20
Article Number 6SL3210-5BB11-2BV1

6SL3210-5BB11-2UV1

6SL3210-5BB12-5BV1

6SL3210-5BB12-5UV1

6SL3210-5BB13-7BV1

6SL3210-5BB13-7UV1

6SL3210-5BB15-5BV1

6SL3210-5BB15-5UV1

6SL3210-5BB17-5BV1

6SL3210-5BB17-5UV1

Power range 230 V 1 AC: 0.12 … 3 kW (0.16 … 4 hp)
400 V 3 AC:  0.37 … 30 kW (0.5 … 40 hp)
Offset factor cos φ ≥0.95
Power factor λ 0.72
Line voltage 230 V 1 AC: 200 … 240 V 1 AC (-15 … +10 %) 1)
400 V 3 AC: 380 … 480 V 3 AC (-15 … +10 %)
Maximum output voltage 100 % of input voltage
Line frequency 50 Hz/60 Hz
Line system configuration TN, TT, TT grounded line supply
IT for
230 V 1 AC unfiltered devices, frame sizes FSAA, FSAB, FSAC, and FSAD
400 V 3 AC unfiltered devices
Overload capability
Up to 15 kW High overload (HO):
150 % IH for 60 s within a cycle time of 300 s.
From 18.5 kW Low overload (LO):
110 % IL for 60 s within a cycle time of 300 s.
High overload (HO):
150 % IH for 60 s within a cycle time of 300 s.
Output frequency 0 … 550 Hz, resolution: 0.01 Hz
Pulse frequency 2 … 16 kHz
Efficiency 95 … 98 %
According to IEC 61800-9-2
Efficiency class IE2
According to IEC 61800-9-2
Programmable fixed frequency setpoints 16
Analog inputs AI1: bipolar current/voltage mode
AI2: unipolar current/voltage mode
can be used as digital inputs
Resolution 12 bit
Analog output AO1 current output
0 … 20 mA
Digital inputs DI1 … DI4: isolated; for 400 V converters with optional SINAMICS V20 I/O Extension Module two additional digital inputs DI5 and DI6
PNP/NPN selectable via terminal
Input current, max. 15 mA
Digital outputs DO1: transistor output
DO2: relay output; for 400 V converters with optional SINAMICS V20 I/O Extension Module two additional digital outputs (relay outputs) DO3 and DO4
250 V AC 0.5 A with resistive load
30 V DC 0.5 A with resistive load
Integrated interface
Type RS485
Protocols USS, Modbus RTU
Extension interface SINAMICS V20 BOP Interface, SINAMICS V20 Smart Access, SINAMICS V20 Parameter Loader, SINAMICS V20 I/O Extension Module (cannot be operated simultaneously with SINAMICS V20 Parameter Loader)
Control methods
V/f linear/square/multi-point
V/f with flux current control (FCC)
Functions
Easy to use
Automatic restart
Parameter cloning
Drive data sets (DDS) ✓ (3)
Command data sets (CDS) ✓ (3)
JOG
Pre-configured connection macros and application macros
Simple parameter-based menu on internal or external SINAMICS V20 BOP
Simple text menu for setup
USS
Modbus RTU
Motor frequency display scaling
Customization of parameter defaults
Energy consumption monitoring
List of modified parameters
Converter status in case of a fault
Application
Keep Running Mode
Flying restart
PID controller
Kinetic buffering (Vdc_min controller)
Skippable frequency bandwidth 4
Braking functions
DC braking
Compound braking
Dynamic braking
2-wire/3-wire control
Mechanical holding brake control
Super torque mode
Hammer start mode
Blockage clearing mode
Hibernation mode
Motor staging
Multi-pump control 2)
(for 400 V converters with optional SINAMICS V20 I/O Extension Module)
Dual ramp parameterizable
Wobble function
BICO function
Slip compensation
Protection
DC link voltage control
Load torque monitoring
Phase loss detection
Cavitation protection
Condensation protection
Frost protection
Control
ECO mode
Vdc_max controller
Imax controller
Programmable V/f coordinates
Flexible voltage boost
50/60 Hz adaptation
1) Single-phase devices can also be connected to two phases of a 3-phase 230 V power supply system. You can find more information here:

 

General technical specifications
Degree of protection IP20
Mounting Wall mounting, side-by-side mounting, push-through mounting for FSB, FSC, FSD, and FSE
Ambient temperature
Operation -10 … +40 °C (14 … 104 °F) without derating
40 … 60 °C (104 … 140 °F) with derating
Storage -40 … +70 °C (-40 … +158 °F)
Relative humidity 95 % (non-condensing)
Cooling
FSAA, FSAB, FSA up to 0.75 kW Convection cooling
FSAC, FSAD, FSA, FSB, FSC, FSD, FSE Power electronics cooled using heat sinks with external fan
Installation altitude Up to 4000 m (13124 ft) above sea level
1000 … 4000 m: (3281 … 13124 ft): output current derating
2000 … 4000 m (6562 … 13124 ft): input voltage derating
Motor cable length
Unshielded
FSAA to FSD 50 m (164 ft)
FSE 100 m (328 ft)
Shielded
FSAA to FSD 25 m (82 ft)
FSE 50 m (164 ft)
Longer motor cables with an additional output reactor
230 V 1 AC 200 m (656 ft) (shielded and unshielded)
400 V 3 AC 150 m (492 ft) (shielded and unshielded) for frame sizes FSA to FSD
200/300 m (656 ft/984 ft) (shielded/unshielded) for frame size FSE
Vibration load
Transport 5 … 9 Hz: Deflection, 3.5 mm
9 … 200 Hz: Vibration 1 × g
Vibration class: 2M3
Operation Area of application IIa
10 … 58 Hz: Deflection, 0.075 mm (0.003 in)
58 … 200 Hz: Vibration 1 × g
Shock load
Operation Area of application II
Peak acceleration: 5 × g
Duration of shock: 30 ms
FSAA FSAB FSAC FSAD FSA FSA FSB FSC FSD FSE
without fan without fan with 1 fan with 1 fan without fan with 1 fan with 1 fan with 1 fan with 2 fans with 2 fans
Dimensions
Width in mm (in) 68 (2.68) 68 (2.68) 90.8 (3.57) 136.6 (5.38) 90 (3.54) 90 (3.54) 140 (5.51) 184 (7.24) 240 (9.45) 245 (9.65)
Height in mm (in) 142 (5.59) 142 (5.59) 160.9 (6.33) 176.5 (6.95) 150 (5.91) 166 (6.54) 160 (6.3) 182 (7.17) 206.5 (8.13) 264.5 (10.41)
Depth in mm (in) 107.8 (4.24) 127.8 (5.03) 147 (5.79) 158.8 (6.25) 145.5 (5.73) 145.5 (5.73) 164.5 (6.48) 169 (6.65) 172.5 (6.79) 209 (8.23)
Weight, approx.
230 V 1 AC
Without integrated line filter 0.6 kg (1.32 lb) 0.8 kg (1.76 lb) 1.2 kg (2.65 lb) 1.9 kg (4.19 lb)
With integrated line filter Category C1 0.7 kg (1.54 lb) 0.9 kg (1.98 lb) 1.4 kg (3.09 lb) 2.2 kg (4.85 lb)
400 V 3 AC
Without integrated line filter 0.9 kg (1.98 lb) 1 kg (2.21 lb) 1.6 kg (3.53 lb) 2.4 kg (5.29 lb) 3.9 kg (8.60 lb) 6.4 kg (14.1 lb)
With integrated line filter Category C3 1 kg (2.21 lb) 1.1 kg (2.43 lb) 1.8 kg (3.97 lb) 2.6 kg (5.73 lb) 4.3 kg (9.48 lb) 7 kg (15.4 lb)
Mounting clearance, min.
Top 100 mm (3.94 in)
Bottom 100 mm (3.94 in)
85 mm (3.35 in) for fan-cooled FSA
Side 0 mm
Certificates of suitability cULus, CE, UKCA, RCM, KC
Environmental classes Pollution class: 3S2
Gas class: 3C2 (SO2, H2S)
Climate class: 3K3
CE marking, according to European Low-Voltage Directive (EN 61800‑5‑1/EN 60204-1), ecodesign requirements of the EU Directive 2019/1781 and European EMC Directive (EN 61800‑3)
UL marking, according to UL508C
EMC standards, radiated emissions and disturbance voltage (conducted emissions)
EN 61800‑3 Category C1, 1st environment (residential, commercial) 230 V 1 AC with integrated line filter or unfiltered with external line filter, shielded cables
FSAA, FSAB, and FSAD: ≤5 m (16.4 ft)
FSAC: ≤10 m (32.8 ft)
EN 61800‑3 Category C2, 1st environment (residential, commercial) 400 V 3 AC without integrated line filter, with external line filter, shielded cables
FSA 1) to FSE ≤25 m (82 ft)
EN 61800‑3 Category C3, 2nd environment (industrial) 400 V 3 AC with integrated line filter, shielded cables
FSA: ≤10 m (32.8 ft)
FSB to FSD: ≤25 m (82 ft)
FSE: ≤50 m (164 ft)
Note The EMC product standard EN 61800‑3 does not apply directly to a frequency converter but to a PDS (Power Drive System), which covers the complete circuitry, motor and cables in addition to the converter. The converters themselves are in general not subject to marking in accordance with the EMC directive.
Weight N/A
Dimensions N/A
Model

, , , , , , , , ,