Contact Us:
sales@inosaki.com

SIMATIC S7- SM 1223 – Digital Hybrid Signal Modules – Siemens

$ 204.82$ 350.02

SKU N/A Category

The SM 1223 digital input/output signal modules convert:

  • the level of the external digital signals from the process into the internal signal level of the S7-1200 controller and
  • the internal signal level of the SIMATIC S7-1200 Controller into the external signal level required for the process.

Product Specifications :

Article number 6ES7223-1BH32-0XB0 6ES7223-1BL32-0XB0 6ES7223-1BL32-1XB0 6ES7223-1PH32-0XB0 6ES7223-1PL32-0XB0 6ES7223-1QH32-0XB0
Digital I/O SM 1223, 8 DI / 8 DO Digital I/O SM 1223, 16DI/16DO Digital I/O SM 1223, 16DI/16DO sink Digital I/O SM 1223, 8DI/8DO Digital I/O SM 1223, 16DI/16DO Digital I/O SM 1223, 8DI AC/ 8DO Rly
General information
Product type designation SM 1223, DI 8×24 V DC, DQ 8×24 V DC SM 1223, DI 16×24 V DC, DQ 16×24 V DC SM 1223, DI 16×24 V DC, DO 16x 24 V DC Sink SM 1223, DI 8×24 V DC, DQ 8x relay SM 1223, DI 16×24 V DC, DQ 16x relay SM 1223, DI 8×120/230 V AC, DQ 8x relay
Supply voltage
Rated value (DC) 24 V 24 V 24 V 24 V 24 V 24 V
permissible range, lower limit (DC) 20.4 V 20.4 V 20.4 V 20.4 V 20.4 V 20.4 V
permissible range, upper limit (DC) 28.8 V 28.8 V 28.8 V 28.8 V 28.8 V 28.8 V
Input current
from backplane bus 5 V DC, max. 145 mA 185 mA 185 mA 145 mA 180 mA 120 mA
Digital inputs
● from load voltage L+ (without load), max. 4 mA; per channel 4 mA; per channel 4 mA; per channel 4 mA/input 11 mA/relay 4 mA/input 11 mA/relay
output voltage / header
supply voltage of the transmitters / header
● product function / supply voltage for transmitters Yes Yes Yes Yes Yes Yes
Power loss
Power loss, typ. 2.5 W 4.5 W 4.5 W 5.5 W 10 W 7.5 W
Digital inputs
Number of digital inputs 8 16 16 8 16 8
● in groups of 2 2 2 2 2 4
Input characteristic curve in accordance with IEC 61131, type 1 Yes Yes Yes Yes Yes Yes
Number of simultaneously controllable inputs
all mounting positions
— up to 40 °C, max. 8 16 16 8 16 8
horizontal installation
— up to 40 °C, max. 8 16 16 8 16 8
— up to 50 °C, max. 8 16 16 8 16 8
vertical installation
— up to 40 °C, max. 8 16 16 8 16 8
Input voltage
● Type of input voltage DC DC DC DC DC AC
● Rated value (DC) 24 V 24 V 24 V 24 V 24 V
● Rated value (AC) 120/230 V AC
● for signal “0” 5 V DC at 1 mA 5 V DC at 1 mA 5 V DC at 1 mA 5 V DC at 1 mA 5 V DC at 1 mA 20 V AC at 1 mA
● for signal “1” 15 V DC at 2.5 mA 15 V DC at 2.5 mA 15 V DC at 2.5 mA 15 V DC at 2.5 mA 15 V DC at 2.5 mA 79 V AC at 2.5 mA
Input current
● for signal “0”, max. (permissible quiescent current) 1 mA 1 mA 1 mA 1 mA 1 mA 1 mA
● for signal “1”, min. 2.5 mA 2.5 mA 2.5 mA 2.5 mA 2.5 mA 2.5 mA
● for signal “1”, typ. 4 mA 4 mA 4 mA 4 mA 4 mA 9 mA
Input delay (for rated value of input voltage)
for standard inputs
— parameterizable Yes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four Yes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four Yes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four Yes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four Yes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four Yes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four
for interrupt inputs
— parameterizable Yes Yes Yes Yes Yes Yes
Cable length
● shielded, max. 500 m 500 m 500 m 500 m 500 m 500 m
● unshielded, max. 300 m 300 m 300 m 300 m 300 m 300 m
Digital outputs
Number of digital outputs 8 16 16; Transistor current sinking 8 16 8
● in groups of 1 1 1 2 4 4
Short-circuit protection No; to be provided externally No; to be provided externally Yes; 1 to 3.5 A No; to be provided externally No; to be provided externally No; to be provided externally
Limitation of inductive shutdown voltage to L+ (-48 V) L+ (-48 V) Typ 45 V
Switching capacity of the outputs
● with resistive load, max. 0.5 A 0.5 A 0.5 A 2 A 2 A 2 A
● on lamp load, max. 5 W 5 W 5 W 30 W with DC, 200 W with AC 30 W with DC, 200 W with AC 30 W with DC, 200 W with AC
Output voltage
● Rated value (DC) 24 V 24 V 24 V 5 V DC to 30 V DC 5 V DC to 30 V DC 5 V DC to 30 V DC
● Rated value (AC) 5 V AC to 250 V AC 5 V AC to 250 V AC 5 V AC to 250 V AC
● for signal “0”, max. 0.1 V; with 10 kOhm load 0.1 V; with 10 kOhm load L+ minus 0.75 V DC with 10k Load
● for signal “1”, min. 20 V DC 20 V DC 0,5 V
Output current
● for signal “1” rated value 0.5 A 0.5 A 0.5 A 2 A 2 A 2 A
● for signal “1” permissible range, max. 0.5 A 0.5 A 0.5 A 2 A 2 A 2 A
● for signal “0” residual current, max. 10 µA 10 µA 75 µA
Output delay with resistive load
● “0” to “1”, max. 50 µs 50 µs 20 µs 10 ms 10 ms 10 ms
● “1” to “0”, max. 200 µs 200 µs 350 µs 10 ms 10 ms 10 ms
Total current of the outputs (per group)
horizontal installation
— up to 50 °C, max. 4 A; Current per mass 8 A; Current per mass 8 A; Current per mass 10 A; Current per mass 8 A; Current per mass 8 A; Current per mass
Relay outputs
● Number of relay outputs 8 16 8
● Rated supply voltage of relay coil L+ (DC) 24 V 24 V 24 V
● Number of operating cycles, max. mechanically 10 million, at rated load voltage 100 000 mechanically 10 million, at rated load voltage 100 000 mechanically 10 million, at rated load voltage 100 000
Switching capacity of contacts
— with inductive load, max. 0.5 A 0.5 A 2 A 2 A 2 A
— on lamp load, max. 5 W 5 W 30 W with DC, 200 W with AC 30 W with DC, 200 W with AC 30 W with DC, 200 W with AC
— with resistive load, max. 0.5 A 0.5 A 2 A 2 A 2 A
Cable length
● shielded, max. 500 m 500 m 500 m 500 m 500 m 500 m
● unshielded, max. 150 m 150 m 150 m 150 m 150 m 150 m
Interrupts/diagnostics/status information
Alarms
● Diagnostic alarm Yes Yes Yes Yes Yes Yes
Diagnostics indication LED
● for status of the inputs Yes Yes Yes Yes Yes Yes
● for status of the outputs Yes Yes Yes Yes Yes Yes
Potential separation
Potential separation digital inputs
● between the channels, in groups of 2 2 2 2 2 2
Potential separation digital outputs
● between the channels Relays Relays Relays
● between the channels, in groups of 1 1 1 2 4 2
● between the channels and backplane bus 500 V AC 500 V AC 500 V AC 1 500 V AC for 1 minute 1 500 V AC for 1 minute 1 500 V AC for 1 minute
Permissible potential difference
between different circuits 750 V AC for 1 minute 750 V AC for 1 minute 750 V AC for 1 minute
Degree and class of protection
IP degree of protection IP20 IP20 IP20 IP20 IP20 IP20
Standards, approvals, certificates
CE mark Yes Yes Yes Yes Yes Yes
CSA approval Yes Yes Yes Yes Yes Yes
UL approval Yes Yes Yes Yes Yes Yes
cULus Yes Yes Yes Yes Yes Yes
FM approval Yes Yes Yes Yes Yes Yes
RCM (formerly C-TICK) Yes Yes Yes Yes Yes Yes
KC approval Yes Yes Yes Yes Yes Yes
Marine approval Yes Yes Yes Yes Yes Yes
Ambient conditions
Free fall
● Fall height, max. 0.3 m; five times, in product package 0.3 m; five times, in product package 0.3 m; five times, in product package 0.3 m; five times, in product package 0.3 m; five times, in product package 0.3 m; five times, in product package
Ambient temperature during operation
● min. -20 °C -20 °C -20 °C -20 °C -20 °C -20 °C
● max. 60 °C 60 °C 60 °C 60 °C 60 °C; Number of simultaneously activated outputs: 8 (no adjacent points) at 60 °C horizontal or 50 °C vertical, 16 at 55 °C horizontal or 45 °C vertical 60 °C; Number of simultaneously activated outputs: 4 (no adjacent points) at 60 °C horizontal or 50 °C vertical, 8 at 55 °C horizontal or 45 °C vertical
● horizontal installation, min. -20 °C -20 °C -20 °C -20 °C -20 °C -20 °C
● horizontal installation, max. 60 °C 60 °C 60 °C 60 °C 60 °C 60 °C
● vertical installation, min. -20 °C -20 °C -20 °C -20 °C -20 °C -20 °C
● vertical installation, max. 50 °C 50 °C 50 °C 50 °C 50 °C 50 °C
● permissible temperature change 5°C to 55°C, 3°C / minute 5°C to 55°C, 3°C / minute 5°C to 55°C, 3°C / minute 5°C to 55°C, 3°C / minute 5°C to 55°C, 3°C / minute 5°C to 55°C, 3°C / minute
Ambient temperature during storage/transportation
● min. -40 °C -40 °C -40 °C -40 °C -40 °C -40 °C
● max. 70 °C 70 °C 70 °C 70 °C 70 °C 70 °C
Air pressure acc. to IEC 60068-2-13
● Storage/transport, min. 660 hPa 660 hPa 660 hPa 660 hPa 660 hPa 660 hPa
● Storage/transport, max. 1 080 hPa 1 080 hPa 1 080 hPa 1 080 hPa 1 080 hPa 1 080 hPa
Relative humidity
● Operation at 25 ℃ without condensation, max. 95 % 95 % 95 % 95 % 95 % 95 %
connection method / header
required front connector Yes Yes Yes Yes Yes Yes
Mechanics/material
Enclosure material (front)
● Plastic Yes Yes Yes Yes Yes Yes
Dimensions
Width 45 mm 70 mm 70 mm 45 mm 70 mm 45 mm
Height 100 mm 100 mm 100 mm 100 mm 100 mm 100 mm
Depth 75 mm 75 mm 75 mm 75 mm 75 mm 75 mm
Weights
Weight, approx. 210 g 310 g 310 g 230 g 350 g 230 g

Additional information

Weight N/A
Dimensions N/A

Related Products

Panasonic_RF-210
PEPPERLFUCHS_Inductive Sensors_NBN5-F7-E0
MOXA_Ethernet-to-Fiber Media Converters_MOXA_IMC-101-S-SC-T
Festo_Mounting Attachments For Actuators_MUC-25_531753
BTF15-BDTL-P
SIMATIC BusAdapters with RJ45 interface
Select your currency