Contact Us:
sales@inosaki.com

SIMATIC S7-400 – SM 432 Analog Output Modules – Siemens

$ 990.38

SKU 6ES7432-1HF00-0AB0 Category

Analog output modules can be used to output analog signals from the control to the process.

Siemens Analog Output Modules SIMATIC S7-400 Product Specifications:

Article number 6ES7432-1HF00-0AB0
SM 432, 8AO, U/I, 13BIT
Supply voltage
Load voltage L+
● Rated value (DC) 24 V
● Reverse polarity protection Yes
Input current
from supply and load voltage L+ (without load), max. 200 mA; at rated load: max. 400 mA
from backplane bus 5 V DC, max. 150 mA
Power loss
Power loss, typ. 9 W
Analog outputs
Number of analog outputs 8
Voltage output, short-circuit protection Yes
Voltage output, short-circuit current, max. 30 mA
Current output, no-load voltage, max. 19 V
Output ranges, voltage
● 0 to 10 V Yes
● 1 V to 5 V Yes
● -10 V to +10 V Yes
Output ranges, current
● 0 to 20 mA Yes
● -20 mA to +20 mA Yes
● 4 mA to 20 mA Yes
Load impedance (in rated range of output)
● with voltage outputs, min. 1 kΩ
● with voltage outputs, capacitive load, max. 1 µF
● with current outputs, max. 500 Ω; 600 ohms if common-mode-voltage reduced to <1 V
Cable length
● shielded, max. 200 m
Analog value generation for the outputs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 13 bit
● Conversion time (per channel) 420 µs; 420 µs in the ranges 1 to 5 V and 4 to 20 mA; 300 µs in all ranges
Settling time
● for resistive load 0.1 ms
● for capacitive load 3.5 ms
● for inductive load 0.5 ms
Errors/accuracies
Operational error limit in overall temperature range
● Voltage, relative to output range, (+/-) 0.5 %; ±10 V, 0 to 10 V, 1 to 5 V
● Current, relative to output range, (+/-) 1 %; ±20 mA, 4 to 20 mV
Basic error limit (operational limit at 25 °C)
● Voltage, relative to output range, (+/-) 0.5 %; ±10 V, 0 to 10 V, 1 to 5 V
● Current, relative to output range, (+/-) 0.5 %; ±20 mA, 0 to 20 mA
Interrupts/diagnostics/status information
Diagnostics function No
Potential separation
Potential separation analog outputs
● between the channels No
● between the channels and backplane bus Yes
Isolation
Isolation tested with 2 120 V DC between bus and L+/M; 2 120 V DC between bus and analog section; 500 V DC between bus and local ground; 500 V DC between analog section and L+/M; 2 120 V DC between analog section and local ground; 2 120 V DC between L+/M and local ground
Dimensions
Width 25 mm
Height 290 mm
Depth 210 mm
Weights
Weight, approx. 650 g

Additional information

Weight 0.782 kg
Dimensions 23.3 × 29.9 × 4.1 cm