SIMATIC S7-1200 – SB 1231 RTD – Siemens Signal/ Communication Boards

$ 132.50

SKU 6ES7231-5PA30-0XB0 Category

Product Description

The SB 1231 RTD signal board permits temperature recording with high precision using resistance temperature detectors. The SB 1231 RTD signal board can be used with SIMATIC S7-1200 CPUs. The SB 1231 RTD signal board can be plugged directly into all SIMATIC S7-1200 CPUs.

Siemens Signal Boards S7-1200 Product Specifications:

Article number 6ES7231-5PA30-0XB0
Signal Board SB 1231 RTD
General information
Product type designation SB 1231, AI 1×16 bit RTD
Supply voltage
Rated value (DC) 24 V
Input current
Current consumption, typ. 5 mA
from backplane bus 5 V DC, typ. 20 mA
Power loss
Power loss, typ. 0.5 W
Analog inputs
Number of analog inputs 1; Resistance thermometer
permissible input voltage for current input (destruction limit), max. ±35 V
Technical unit for temperature measurement adjustable Degrees Celsius/degrees Fahrenheit
Input ranges
● Voltage Yes
● Current No
● Thermocouple No
● Resistance thermometer Yes; Platinum (Pt)
● Resistance Yes; 150 Ω, 300 Ω, 600 Ω
Input ranges (rated values), voltages
● -80 mV to +80 mV
— Input resistance (-80 mV to +80 mV) >= 10 MOhm
Input ranges (rated values), resistance thermometer
● Pt 100 Yes
— Input resistance (Pt 100) 100 Ω
● Pt 1000 Yes
— Input resistance (Pt 1000) 1 000 Ω
● Pt 200 Yes
— Input resistance (Pt 200) 200 Ω
● Pt 500 Yes
— Input resistance (Pt 500) 500 Ω
Input ranges (rated values), resistors
● 0 to 150 ohms Yes
● 0 to 300 ohms Yes
● 0 to 600 ohms Yes
Thermocouple (TC)
Temperature compensation
— parameterizable No
Analog outputs
Number of analog outputs 0
Cable length
● shielded, max. 100 m; shielded, twisted pair
Analog value generation for the inputs
Measurement principle integrating
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 15 bit; + sign
● Integration time, parameterizable No
● Interference voltage suppression for interference frequency f1 in Hz 85 dB at 10 / 50 / 60 / 400 Hz
Errors/accuracies
Temperature error (relative to input range), (+/-) 25 °C ±0.1%, to 55 °C ±0.2% total measurement range
Repeat accuracy in steady state at 25 °C (relative to output range), (+/-) 0.05 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Common mode interference, min. 120 dB
Interrupts/diagnostics/status information
Alarms Yes
Diagnostics function Yes; Can be read out
Alarms
● Diagnostic alarm Yes
Diagnoses
● Wire-break Yes
Diagnostics indication LED
● for status of the inputs Yes
● for maintenance Yes
Standards, approvals, certificates
CE mark Yes
CSA approval Yes
UL approval Yes
cULus Yes
FM approval Yes
RCM (formerly C-TICK) Yes
KC approval Yes
Marine approval Yes
Ambient conditions
Free fall
● Fall height, max. 0.3 m; five times, in product package
Ambient temperature during operation
● min. -20 °C
● max. 60 °C
● horizontal installation, min. -20 °C
● horizontal installation, max. 60 °C
● vertical installation, min. -20 °C
● vertical installation, max. 50 °C
Ambient temperature during storage/transportation
● min. -40 °C
● max. 70 °C
Air pressure acc. to IEC 60068-2-13
● Operation, min. 795 hPa
● Operation, max. 1 080 hPa
● Storage/transport, min. 660 hPa
● Storage/transport, max. 1 080 hPa
Relative humidity
● Operation at 25 ℃ without condensation, max. 95 %
Pollutant concentrations
● SO2 at RH < 60% without condensation S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free
connection method / header
required front connector Yes
Mechanics/material
Enclosure material (front)
● Plastic Yes
Dimensions
Width 38 mm
Height 62 mm
Depth 21 mm
Weights
Weight, approx. 35 g
Select your currency