Siemens PLC model SIMATIC S7-1200 controller is at the core of our offering for simple but highly precise automation tasks. The SIMATIC S7-1200 controller is modular and compact, versatile, a secure investment, and is perfectly suited to a whole range of applications.
Siemens PLC S7-1200 CPUs with Safety Integrated handle both standard and safety-related tasks. A compact design with integrated IO, communication interfaces that meet the highest industry requirements and a range of powerful integrated technological functions make this controller an integral part of a comprehensive automation solution. Siemens plc software are available for win cc find out more.
| Article number | 6ES7212-1AE40-0XB0 | 6ES7212-1BE40-0XB0 | 6ES7212-1HE40-0XB0 |
| CPU 1212C ,DC/DC/DC, 8DI/6DO/2AI | CPU 1212C, AC/DC/Relay, 8DI/6DO/2AI | CPU 1212C, DC/DC/Relay, 8DI/6DO/2AI | |
| General information | |||
| Product type designation | CPU 1212C DC/DC/DC | CPU 1212C AC/DC/relay | CPU 1212C DC/DC/relay |
| Firmware version | V4.5 | V4.5 | V4.5 |
| Engineering with | |||
| ● Programming package | STEP 7 V17 or higher | STEP 7 V17 or higher | STEP 7 V17 or higher |
| Supply voltage | |||
| Rated value (DC) | |||
| ● 24 V DC | Yes | Yes | |
| permissible range, lower limit (DC) | 20.4 V | 20.4 V | |
| permissible range, upper limit (DC) | 28.8 V | 28.8 V | |
| Rated value (AC) | |||
| ● 120 V AC | Yes | ||
| ● 230 V AC | Yes | ||
| permissible range, lower limit (AC) | 85 V | ||
| permissible range, upper limit (AC) | 264 V | ||
| Reverse polarity protection | Yes | Yes | |
| Line frequency | |||
| ● permissible range, lower limit | 47 Hz | ||
| ● permissible range, upper limit | 63 Hz | ||
| Load voltage L+ | |||
| ● Rated value (DC) | 24 V | 24 V | |
| ● permissible range, lower limit (DC) | 20.4 V | 20.4 V | |
| ● permissible range, upper limit (DC) | 28.8 V | 28.8 V | |
| Input current | |||
| Current consumption (rated value) | 400 mA; CPU only | 80 mA at 120 V AC; 40 mA at 240 V AC | 400 mA; CPU only |
| Current consumption, max. | 1 200 mA; CPU with all expansion modules | 240 mA at 120 V AC; 120 mA at 240 V AC | 1 200 mA; CPU with all expansion modules |
| Inrush current, max. | 12 A; at 28.8 V DC | 20 A; at 264 V | 12 A; at 28.8 V |
| I²t | 0.5 A²·s | 0.8 A²·s | 0.8 A²·s |
| Output current | |||
| for backplane bus (5 V DC), max. | 1 000 mA; Max. 5 V DC for SM and CM | 1 000 mA; Max. 5 V DC for SM and CM | 1 000 mA; Max. 5 V DC for SM and CM |
| Encoder supply | |||
| 24 V encoder supply | |||
| ● 24 V | L+ minus 4 V DC min. | 20.4 to 28.8V | L+ minus 4 V DC min. |
| Power loss | |||
| Power loss, typ. | 9 W | 11 W | 9 W |
| Memory | |||
| Work memory | |||
| ● integrated | 75 kbyte | 75 kbyte | 75 kbyte |
| ● expandable | No | No | No |
| Load memory | |||
| ● integrated | 2 Mbyte | 2 Mbyte | 2 Mbyte |
| ● Plug-in (SIMATIC Memory Card), max. | with SIMATIC memory card | with SIMATIC memory card | with SIMATIC memory card |
| Backup | |||
| ● present | Yes | Yes | Yes |
| ● maintenance-free | Yes | Yes | Yes |
| ● without battery | Yes | Yes | Yes |
| CPU processing times | |||
| for bit operations, typ. | 0.08 µs; / instruction | 0.08 µs; / instruction | 0.08 µs; / instruction |
| for word operations, typ. | 1.7 µs; / instruction | 1.7 µs; / instruction | 1.7 µs; / instruction |
| for floating point arithmetic, typ. | 2.3 µs; / instruction | 2.3 µs; / instruction | 2.3 µs; / instruction |
| CPU-blocks | |||
| Number of blocks (total) | DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used | DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used | DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used |
| OB | |||
| ● Number, max. | Limited only by RAM for code | Limited only by RAM for code | Limited only by RAM for code |
| Data areas and their retentivity | |||
| Retentive data area (incl. timers, counters, flags), max. | 14 kbyte | 14 kbyte | 14 kbyte |
| Flag | |||
| ● Size, max. | 4 kbyte; Size of bit memory address area | 4 kbyte; Size of bit memory address area | 4 kbyte; Size of bit memory address area |
| Local data | |||
| ● per priority class, max. | 16 kbyte; Priority class 1 (program cycle): 16 KB, priority class 2 to 26: 6 KB | 16 kbyte; Priority class 1 (program cycle): 16 KB, priority class 2 to 26: 6 KB | 16 kbyte; Priority class 1 (program cycle): 16 KB, priority class 2 to 26: 6 KB |
| Address area | |||
| Process image | |||
| ● Inputs, adjustable | 1 kbyte | 1 kbyte | 1 kbyte |
| ● Outputs, adjustable | 1 kbyte | 1 kbyte | 1 kbyte |
| Hardware configuration | |||
| Number of modules per system, max. | 3 comm. modules, 1 signal board, 2 signal modules | 3 comm. modules, 1 signal board, 2 signal modules | 3 comm. modules, 1 signal board, 2 signal modules |
| Time of day | |||
| Clock | |||
| ● Hardware clock (real-time) | Yes | Yes | Yes |
| ● Backup time | 480 h; Typical | 480 h; Typical | 480 h; Typical |
| ● Deviation per day, max. | ±60 s/month at 25 °C | ±60 s/month at 25 °C | ±60 s/month at 25 °C |
| Digital inputs | |||
| Number of digital inputs | 8; Integrated | 8; Integrated | 8; Integrated |
| ● of which inputs usable for technological functions | 6; HSC (High Speed Counting) | 6; HSC (High Speed Counting) | 6; HSC (High Speed Counting) |
| Source/sink input | Yes | Yes | Yes |
| Number of simultaneously controllable inputs | |||
| all mounting positions | |||
| — up to 40 °C, max. | 8 | 8 | 8 |
| Input voltage | |||
| ● Rated value (DC) | 24 V | 24 V | 24 V |
| ● for signal “0” | 5 V DC at 1 mA | 5 V DC at 1 mA | 5 V DC at 1 mA |
| ● for signal “1” | 15 V DC at 2.5 mA | 15 V DC at 2.5 mA | 15 V DC at 2.5 mA |
| Input delay (for rated value of input voltage) | |||
| for standard inputs | |||
| — parameterizable | 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four | 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four | 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four |
| — at “0” to “1”, min. | 0.2 ms | 0.2 ms | 0.2 ms |
| — at “0” to “1”, max. | 12.8 ms | 12.8 ms | 12.8 ms |
| for interrupt inputs | |||
| — parameterizable | Yes | Yes | Yes |
| for technological functions | |||
| — parameterizable | Single phase: 3 @ 100 kHz & 3 @ 30 kHz, differential: 3 @ 80 kHz & 3 @ 30 kHz | Single phase: 3 @ 100 kHz & 3 @ 30 kHz, differential: 3 @ 80 kHz & 3 @ 30 kHz | Single phase: 3 @ 100 kHz & 3 @ 30 kHz, differential: 3 @ 80 kHz & 3 @ 30 kHz |
| Cable length | |||
| ● shielded, max. | 500 m; 50 m for technological functions | 500 m; 50 m for technological functions | 500 m; 50 m for technological functions |
| ● unshielded, max. | 300 m; for technological functions: No | 300 m; for technological functions: No | 300 m; for technological functions: No |
| Digital outputs | |||
| Number of digital outputs | 6 | 6; Relays | 6; Relays |
| ● of which high-speed outputs | 4; 100 kHz Pulse Train Output | ||
| Limitation of inductive shutdown voltage to | L+ (-48 V) | ||
| Switching capacity of the outputs | |||
| ● with resistive load, max. | 0.5 A | 2 A | 2 A |
| ● on lamp load, max. | 5 W | 30 W with DC, 200 W with AC | 30 W with DC, 200 W with AC |
| Output voltage | |||
| ● for signal “0”, max. | 0.1 V; with 10 kOhm load | ||
| ● for signal “1”, min. | 20 V | ||
| Output current | |||
| ● for signal “1” rated value | 0.5 A | ||
| ● for signal “0” residual current, max. | 0.1 mA | ||
| Output delay with resistive load | |||
| ● “0” to “1”, max. | 1 µs | 10 ms; max. | 10 ms; max. |
| ● “1” to “0”, max. | 5 µs | 10 ms; max. | 10 ms; max. |
| Switching frequency | |||
| ● of the pulse outputs, with resistive load, max. | 100 kHz | ||
| Relay outputs | |||
| ● Number of relay outputs | 0 | 6 | 6 |
| ● Number of operating cycles, max. | mechanically 10 million, at rated load voltage 100 000 | mechanically 10 million, at rated load voltage 100 000 | |
| Cable length | |||
| ● shielded, max. | 500 m | 500 m | 500 m |
| ● unshielded, max. | 150 m | 150 m | 150 m |
| Analog inputs | |||
| Number of analog inputs | 2 | 2 | 2 |
| Input ranges | |||
| ● Voltage | Yes | Yes | Yes |
| Input ranges (rated values), voltages | |||
| ● 0 to +10 V | Yes | Yes | Yes |
| — Input resistance (0 to 10 V) | ≥100k ohms | ≥100k ohms | ≥100k ohms |
| Cable length | |||
| ● shielded, max. | 100 m; twisted and shielded | 100 m; twisted and shielded | 100 m; twisted and shielded |
| Analog outputs | |||
| Number of analog outputs | 0 | 0 | 0 |
| Analog value generation for the inputs | |||
| Integration and conversion time/resolution per channel | |||
| ● Resolution with overrange (bit including sign), max. | 10 bit | 10 bit | 10 bit |
| ● Integration time, parameterizable | Yes | Yes | Yes |
| ● Conversion time (per channel) | 625 µs | 625 µs | 625 µs |
| Encoder | |||
| Connectable encoders | |||
| ● 2-wire sensor | Yes | Yes | Yes |
| 1. Interface | |||
| Interface type | PROFINET | PROFINET | PROFINET |
| Isolated | Yes | Yes | Yes |
| automatic detection of transmission rate | Yes | Yes | Yes |
| Autonegotiation | Yes | Yes | Yes |
| Autocrossing | Yes | Yes | Yes |
| Interface types | |||
| ● RJ 45 (Ethernet) | Yes | Yes | Yes |
| ● Number of ports | 1 | 1 | 1 |
| ● integrated switch | No | No | No |
| Protocols | |||
| ● PROFINET IO Controller | Yes | Yes | Yes |
| ● PROFINET IO Device | Yes | Yes | Yes |
| ● SIMATIC communication | Yes | Yes | Yes |
| ● Open IE communication | Yes; Optionally also encrypted | Yes; Optionally also encrypted | Yes; Optionally also encrypted |
| ● Web server | Yes | Yes | Yes |
| ● Media redundancy | No | No | No |
| PROFINET IO Controller | |||
| ● Transmission rate, max. | 100 Mbit/s | 100 Mbit/s | 100 Mbit/s |
| Services | |||
| — PG/OP communication | Yes; encryption with TLS V1.3 pre-selected | Yes; encryption with TLS V1.3 pre-selected | Yes; encryption with TLS V1.3 pre-selected |
| — Isochronous mode | No | No | No |
| — IRT | No | No | No |
| — PROFIenergy | No | No | No |
| — Prioritized startup | Yes | Yes | Yes |
| — Number of IO devices with prioritized startup, max. | 16 | 16 | 16 |
| — Number of connectable IO Devices, max. | 16 | 16 | 16 |
| — Number of connectable IO Devices for RT, max. | 16 | 16 | 16 |
| — of which in line, max. | 16 | 16 | 16 |
| — Activation/deactivation of IO Devices | Yes | Yes | Yes |
| — Number of IO Devices that can be simultaneously activated/deactivated, max. | 8 | 8 | 8 |
| — Updating time | The minimum value of the update time also depends on the communication component set for PROFINET IO, on the number of IO devices and the quantity of configured user data. | The minimum value of the update time also depends on the communication component set for PROFINET IO, on the number of IO devices and the quantity of configured user data. | The minimum value of the update time also depends on the communication component set for PROFINET IO, on the number of IO devices and the quantity of configured user data. |
| PROFINET IO Device | |||
| Services | |||
| — PG/OP communication | Yes; encryption with TLS V1.3 pre-selected | Yes; encryption with TLS V1.3 pre-selected | Yes; encryption with TLS V1.3 pre-selected |
| — Isochronous mode | No | No | No |
| — IRT | No | No | No |
| — PROFIenergy | Yes | Yes | Yes |
| — Shared device | Yes | Yes | Yes |
| — Number of IO Controllers with shared device, max. | 2 | 2 | 2 |
| Protocols | |||
| Supports protocol for PROFINET IO | Yes | Yes | Yes |
| PROFIsafe | No | No | No |
| PROFIBUS | Yes; CM 1243-5 (master) or CM 1242-5 (slave) required | Yes; CM 1243-5 (master) or CM 1242-5 (slave) required | Yes; CM 1243-5 (master) or CM 1242-5 (slave) required |
| OPC UA | Yes; OPC UA Server | Yes; OPC UA Server | Yes; OPC UA Server |
| AS-Interface | Yes; CM 1243-2 required | Yes; CM 1243-2 required | Yes; CM 1243-2 required |
| Protocols (Ethernet) | |||
| ● TCP/IP | Yes | Yes | Yes |
| ● DHCP | No | No | No |
| ● SNMP | Yes | Yes | Yes |
| ● DCP | Yes | Yes | Yes |
| ● LLDP | Yes | Yes | Yes |
| Redundancy mode | |||
| Media redundancy | |||
| — MRP | No | No | No |
| — MRPD | No | No | No |
| SIMATIC communication | |||
| ● S7 routing | Yes | Yes | Yes |
| Open IE communication | |||
| ● TCP/IP | Yes | Yes | Yes |
| — Data length, max. | 8 kbyte | 8 kbyte | 8 kbyte |
| — several passive connections per port, supported | Yes | ||
| ● ISO-on-TCP (RFC1006) | Yes | Yes | Yes |
| — Data length, max. | 8 kbyte | 8 kbyte | 8 kbyte |
| ● UDP | Yes | Yes | Yes |
| — Data length, max. | 1 472 byte | 1 472 byte | 1 472 byte |
| Web server | |||
| ● supported | Yes | Yes | Yes |
| ● User-defined websites | Yes | Yes | Yes |
| OPC UA | |||
| ● Runtime license required | Yes; “Basic” license required | Yes; “Basic” license required | Yes; “Basic” license required |
| ● OPC UA Server | Yes; data access (read, write, subscribe), method call, runtime license required | Yes; data access (read, write, subscribe), method call, runtime license required | Yes; data access (read, write, subscribe), method call, runtime license required |
| — Application authentication | Available security policies: None, Basic128Rsa15, Basic256Rsa15, Basic256Sha256 | Available security policies: None, Basic128Rsa15, Basic256Rsa15, Basic256Sha256 | Available security policies: None, Basic128Rsa15, Basic256Rsa15, Basic256Sha256 |
| — User authentication | “anonymous” or by user name & password | “anonymous” or by user name & password | “anonymous” or by user name & password |
| — Number of sessions, max. | 10 | 10 | 10 |
| — Number of subscriptions per session, max. | 50 | 50 | 50 |
| — Sampling interval, min. | 100 ms | 100 ms | 100 ms |
| — Publishing interval, min. | 200 ms | 200 ms | 200 ms |
| — Number of server methods, max. | 20 | 20 | 20 |
| — Number of monitored items, max. | 1 000 | 1 000 | 1 000 |
| — Number of server interfaces, max. | 2 | 2 | 2 |
| — Number of nodes for user-defined server interfaces, max. | 2 000 | 2 000 | 2 000 |
| Further protocols | |||
| ● MODBUS | Yes | Yes | Yes |
| communication functions / header | |||
| S7 communication | |||
| ● supported | Yes | Yes | Yes |
| ● as server | Yes | Yes | Yes |
| ● as client | Yes | Yes | Yes |
| ● User data per job, max. | See online help (S7 communication, user data size) | See online help (S7 communication, user data size) | See online help (S7 communication, user data size) |
| Number of connections | |||
| ● overall | PG Connections: 4 reserved / 4 max; HMI Connections: 12 reserved / 18 max; S7 Connections: 8 reserved / 14 max; Open User Connections: 8 reserved / 14 max; Web Connections: 2 reserved / 30 max; OPC UA Connections: 0 reserved / 10 max; Total Connections: 34 reserved / 64 max | PG Connections: 4 reserved / 4 max; HMI Connections: 12 reserved / 18 max; S7 Connections: 8 reserved / 14 max; Open User Connections: 8 reserved / 14 max; Web Connections: 2 reserved / 30 max; OPC UA Connections: 0 reserved / 10 max; Total Connections: 34 reserved / 64 max | PG Connections: 4 reserved / 4 max; HMI Connections: 12 reserved / 18 max; S7 Connections: 8 reserved / 14 max; Open User Connections: 8 reserved / 14 max; Web Connections: 2 reserved / 30 max; OPC UA Connections: 0 reserved / 10 max; Total Connections: 34 reserved / 64 max |
| Test commissioning functions | |||
| Status/control | |||
| ● Status/control variable | Yes | Yes | Yes |
| ● Variables | Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters | Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters | Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters |
| Forcing | |||
| ● Forcing | Yes | Yes | Yes |
| Diagnostic buffer | |||
| ● present | Yes | Yes | Yes |
| Traces | |||
| ● Number of configurable Traces | 2 | 2 | 2 |
| ● Memory size per trace, max. | 512 kbyte | 512 kbyte | 512 kbyte |
| Interrupts/diagnostics/status information | |||
| Diagnostics indication LED | |||
| ● RUN/STOP LED | Yes | Yes | Yes |
| ● ERROR LED | Yes | Yes | Yes |
| ● MAINT LED | Yes | Yes | Yes |
| Integrated Functions | |||
| Counter | |||
| ● Number of counters | 6 | 6 | 6 |
| ● Counting frequency, max. | 100 kHz | 100 kHz | 100 kHz |
| Frequency measurement | Yes | Yes | Yes |
| controlled positioning | Yes | Yes | Yes |
| Number of position-controlled positioning axes, max. | 8 | 8 | 8 |
| Number of positioning axes via pulse-direction interface | 4; With integrated outputs | Up to 4 with SB 1222 | Up to 4 with SB 1222 |
| PID controller | Yes | Yes | Yes |
| Number of alarm inputs | 4 | 4 | 4 |
| Number of pulse outputs | 4 | ||
| Limit frequency (pulse) | 100 kHz | ||
| Potential separation | |||
| Potential separation digital inputs | |||
| ● Potential separation digital inputs | No | 500V AC for 1 minute | 500V AC for 1 minute |
| ● between the channels, in groups of | 1 | 1 | 1 |
| Potential separation digital outputs | |||
| ● Potential separation digital outputs | Yes | Relays | Relays |
| ● between the channels | No | No | No |
| ● between the channels, in groups of | 1 | 2 | 2 |
| EMC | |||
| Interference immunity against discharge of static electricity | |||
| ● Interference immunity against discharge of static electricity acc. to IEC 61000-4-2 | Yes | Yes | Yes |
| — Test voltage at air discharge | 8 kV | 8 kV | 8 kV |
| — Test voltage at contact discharge | 6 kV | 6 kV | 6 kV |
| Interference immunity to cable-borne interference | |||
| ● Interference immunity on supply lines acc. to IEC 61000-4-4 | Yes | Yes | Yes |
| ● Interference immunity on signal cables acc. to IEC 61000-4-4 | Yes | Yes | Yes |
| Interference immunity against voltage surge | |||
| ● Interference immunity on supply lines acc. to IEC 61000-4-5 | Yes | Yes | Yes |
| Interference immunity against conducted variable disturbance induced by high-frequency fields | |||
| ● Interference immunity against high-frequency radiation acc. to IEC 61000-4-6 | Yes | Yes | Yes |
| Emission of radio interference acc. to EN 55 011 | |||
| ● Limit class A, for use in industrial areas | Yes; Group 1 | Yes; Group 1 | Yes; Group 1 |
| ● Limit class B, for use in residential areas | Yes; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011 | Yes; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011 | Yes; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011 |
| Degree and class of protection | |||
| IP degree of protection | IP20 | IP20 | IP20 |
| Standards, approvals, certificates | |||
| CE mark | Yes | Yes | Yes |
| UL approval | Yes | Yes | Yes |
| cULus | Yes | Yes | Yes |
| FM approval | Yes | Yes | Yes |
| RCM (formerly C-TICK) | Yes | Yes | Yes |
| KC approval | Yes | Yes | Yes |
| Marine approval | Yes | Yes | Yes |
| Ambient conditions | |||
| Free fall | |||
| ● Fall height, max. | 0.3 m; five times, in product package | 0.3 m; five times, in product package | 0.3 m; five times, in product package |
| Ambient temperature during operation | |||
| ● min. | -20 °C | -20 °C | -20 °C |
| ● max. | 60 °C; Number of simultaneously activated inputs or outputs 4 or 3 (no adjacent points) at 60 °C horizontal or 50 °C vertical, 8 or 6 at 55 °C horizontal or 45 °C vertical | 60 °C; Number of simultaneously activated inputs or outputs 4 or 3 (no adjacent points) at 60 °C horizontal or 50 °C vertical, 8 or 6 at 55 °C horizontal or 45 °C vertical | 60 °C; Number of simultaneously activated inputs or outputs 4 or 3 (no adjacent points) at 60 °C horizontal or 50 °C vertical, 8 or 6 at 55 °C horizontal or 45 °C vertical |
| ● horizontal installation, min. | -20 °C | -20 °C | -20 °C |
| ● horizontal installation, max. | 60 °C | 60 °C | 60 °C |
| ● vertical installation, min. | -20 °C | -20 °C | -20 °C |
| ● vertical installation, max. | 50 °C | 50 °C | 50 °C |
| Ambient temperature during storage/transportation | |||
| ● min. | -40 °C | -40 °C | -40 °C |
| ● max. | 70 °C | 70 °C | 70 °C |
| Air pressure acc. to IEC 60068-2-13 | |||
| ● Operation, min. | 795 hPa | 795 hPa | 795 hPa |
| ● Operation, max. | 1 080 hPa | 1 080 hPa | 1 080 hPa |
| ● Storage/transport, min. | 660 hPa | 660 hPa | 660 hPa |
| ● Storage/transport, max. | 1 080 hPa | 1 080 hPa | 1 080 hPa |
| Altitude during operation relating to sea level | |||
| ● Installation altitude, min. | -1 000 m | -1 000 m | -1 000 m |
| ● Installation altitude, max. | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual |
| Relative humidity | |||
| ● Operation, max. | 95 %; no condensation | 95 %; no condensation | 95 %; no condensation |
| Vibrations | |||
| ● Vibration resistance during operation acc. to IEC 60068-2-6 | 2 g (m/s²) wall mounting, 1 g (m/s²) DIN rail | 2 g (m/s²) wall mounting, 1 g (m/s²) DIN rail | 2 g (m/s²) wall mounting, 1 g (m/s²) DIN rail |
| ● Operation, tested according to IEC 60068-2-6 | Yes | Yes | Yes |
| Shock testing | |||
| ● tested according to IEC 60068-2-27 | Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms | Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms | Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms |
| Pollutant concentrations | |||
| ● SO2 at RH < 60% without condensation | S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free | S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free | S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free |
| configuration / header | |||
| configuration / programming / header | |||
| Programming language | |||
| — LAD | Yes | Yes | Yes |
| — FBD | Yes | Yes | Yes |
| — SCL | Yes | Yes | Yes |
| Know-how protection | |||
| ● User program protection/password protection | Yes | Yes | Yes |
| ● Copy protection | Yes | Yes | Yes |
| ● Block protection | Yes | Yes | Yes |
| Access protection | |||
| ● protection of confidential configuration data | Yes | Yes | Yes |
| ● Protection level: Write protection | Yes | Yes | Yes |
| ● Protection level: Read/write protection | Yes | Yes | Yes |
| ● Protection level: Complete protection | Yes | Yes | Yes |
| programming / cycle time monitoring / header | |||
| ● adjustable | Yes | Yes | Yes |
| Dimensions | |||
| Width | 90 mm | 90 mm | 90 mm |
| Height | 100 mm | 100 mm | 100 mm |
| Depth | 75 mm | 75 mm | 75 mm |
| Weights | |||
| Weight, approx. | 370 g | 425 g | 385 g |