$ 202.63 – $ 209.07
The SIPLUS ET 200SP IM 155-6PN ST (BA) TX RAIL is designed mainly for standard PROFINET applications with average station expansion of up to 32 modules (max. 512 IO signals). All I/O modules, including PROFIsafe, can be used. In addition, the station can be expanded with as many as 16 IP67 modules of the SIMATIC ET 200AL series using BA-Send/BU-Send.
The SIPLUS ET 200SP IM 155-6PN HF T1 RAIL/ET 200SP IM 155-6PN HF TX RAIL are designed mainly for PROFINET applications with a high, flexible demand for functions, as well as large station expansion of up to 64 modules (max. 1024 IO signals). All I/O modules, including PROFIsafe, can be used. In addition, the station can be expanded with as many as 16 IP67 modules of the SIMATIC ET 200AL series using BA-Send/BU-Send.
Article number | 6AG2155-6AA01-4BN0 | 6AG2155-6AU01-4BN0 | 6AG2155-6AU01-1CN0 | 6AG2155-6AU01-4CN0 |
SIPLUS ET 200SP IM155-6PN ST BA TX RAIL | SIPLUS ET 200SP IM155-6PN ST TX RAIL | SIPLUS ET 200SP IM155-6PN HF T1 RAIL | SIPLUS ET 200SP IM155-6PN HF TX RAIL | |
General information | ||||
Product type designation | IM 155-6 PN ST | IM 155-6 PN ST | IM 155-6 PN/2 HF | IM 155-6 PN/2 HF |
Firmware version | ||||
● FW update possible | Yes | Yes | ||
Product function | ||||
● I&M data | Yes; I&M0 to I&M3 | Yes; I&M0 to I&M3 | Yes; I&M0 to I&M3 | Yes; I&M0 to I&M3 |
● Module swapping during operation (hot swapping) | Yes; Single hot swapping | Yes; Single hot swapping | Yes; Multi-hot swapping | Yes; Multi-hot swapping |
● Isochronous mode | No | No | Yes | Yes |
● Tool changer | Yes; Docking station and docking unit | Yes; Docking station and docking unit | ||
● Local coupling, IO data | No | No | ||
● Local coupling, data records | No | No | ||
Engineering with | ||||
● STEP 7 TIA Portal configurable/integrated from version | see entry ID: 109746275 | see entry ID: 109746275 | see entry ID: 109746275 | see entry ID: 109746275 |
Configuration control | ||||
via dataset | Yes | Yes | Yes | Yes |
Supply voltage | ||||
Rated value (DC) | 24 V | 24 V | 24 V | 24 V |
permissible range, lower limit (DC) | 19.2 V | 19.2 V | 19.2 V | 19.2 V |
permissible range, upper limit (DC) | 28.8 V | 28.8 V | 28.8 V | 28.8 V |
Reverse polarity protection | Yes | Yes | Yes | Yes |
Short-circuit protection | Yes | Yes | ||
Mains buffering | ||||
● Mains/voltage failure stored energy time | 10 ms | 10 ms | 10 ms | 10 ms |
Input current | ||||
Current consumption (rated value) | 450 mA | 450 mA | ||
Current consumption, max. | 550 mA | 550 mA | 700 mA | 700 mA |
Inrush current, max. | 3.7 A | 3.7 A | 4.5 A | 4.5 A |
I²t | 0.09 A²·s | 0.09 A²·s | 0.25 A²·s | 0.25 A²·s |
Power | ||||
Infeed power to the backplane bus | 4.5 W | 4.5 W | ||
Power loss | ||||
Power loss, typ. | 1.9 W | 1.9 W | 2.4 W | 2.4 W |
Address area | ||||
Address space per module | ||||
● Address space per module, max. | 256 byte; per input / output | 256 byte; per input / output | 288 byte; For input and output data respectively | 288 byte; For input and output data respectively |
Address space per station | ||||
● Address space per station, max. | 512 byte; Dependent on configuration | 512 byte; Dependent on configuration | 1 440 byte; Dependent on configuration | 1 440 byte; Dependent on configuration |
Hardware configuration | ||||
Rack | ||||
● Modules per rack, max. | 32; + 16 ET 200AL modules | 32; + 16 ET 200AL modules | 64; + 16 ET 200AL modules | 64; + 16 ET 200AL modules |
Submodules | ||||
● Number of submodules per station, max. | 256 | 256 | 256 | 256 |
Time stamping | ||||
Accuracy | 10 ms | 10 ms | ||
Interfaces | ||||
Number of PROFINET interfaces | 1; 2 ports (switch) | 1; 2 ports (switch) | 1; 2 ports (switch) | 1; 2 ports (switch) |
1. Interface | ||||
Interface types | ||||
● RJ 45 (Ethernet) | Yes; Pre-assembled BusAdapter BA 2x RJ45 | |||
● Number of ports | 2 | 2 | 2; via BusAdapter | 2; via BusAdapter |
● integrated switch | Yes | Yes | Yes | Yes |
● BusAdapter (PROFINET) | Yes; Applicable BusAdapter: BA 2x RJ45, BA 2x FC | Yes; Applicable BusAdapter: BA 2x RJ45, BA 2x FC | Yes; Compatible BusAdapter: BA 2x RJ45, BA 2x FC, BA 2x SCRJ, BA SCRJ / RJ45, BA SCRJ / FC, BA 2x LC, BA LC / RJ45, BA LC / FC | Yes; Compatible BusAdapter: BA 2x RJ45, BA 2x FC, BA 2x SCRJ, BA SCRJ / RJ45, BA SCRJ / FC, BA 2x LC, BA LC / RJ45, BA LC / FC |
Protocols | ||||
● PROFINET IO Device | Yes | Yes | Yes | Yes |
● Open IE communication | Yes | Yes | Yes | Yes |
● Media redundancy | Yes; PROFINET MRP | Yes; PROFINET MRP | Yes; PROFINET MRP | Yes; PROFINET MRP |
Interface types | ||||
RJ 45 (Ethernet) | ||||
● Transmission procedure | PROFINET with 100 Mbit/s full duplex (100BASE-TX) | PROFINET with 100 Mbit/s full duplex (100BASE-TX) | PROFINET with 100 Mbit/s full duplex (100BASE-TX) | PROFINET with 100 Mbit/s full duplex (100BASE-TX) |
● 10 Mbps | Yes; for Ethernet services | Yes; for Ethernet services | No | No |
● 100 Mbps | Yes; PROFINET with 100 Mbit/s full duplex (100BASE-TX) | Yes; PROFINET with 100 Mbit/s full duplex (100BASE-TX) | Yes; PROFINET with 100 Mbit/s full duplex (100BASE-TX) | Yes; PROFINET with 100 Mbit/s full duplex (100BASE-TX) |
● Autonegotiation | Yes | Yes | Yes | Yes |
● Autocrossing | Yes | Yes | Yes | Yes |
Protocols | ||||
Number of connections | ||||
● Number of MtM communication relationships/connections, max. | 16 | 16 | ||
PROFINET IO Device | ||||
Services | ||||
— IRT | Yes; with send cycles of between 250 µs and 4 ms in increments of 125 µs | Yes; with send cycles of between 250 µs and 4 ms in increments of 125 µs | Yes; 250 μs, 500 μs, 1 ms, 2 ms, 4 ms additionally with IRT with high performance: 250 µs to 4 ms in 125 µs frame | Yes; 250 μs, 500 μs, 1 ms, 2 ms, 4 ms additionally with IRT with high performance: 250 µs to 4 ms in 125 µs frame |
— PROFIenergy | Yes | Yes | Yes | Yes |
— Prioritized startup | Yes | Yes | Yes | Yes |
— Shared device | Yes | Yes | Yes | Yes |
— Number of IO Controllers with shared device, max. | 2 | 2 | 4 | 4 |
Redundancy mode | ||||
● PROFINET system redundancy (S2) | No | No | Yes; NAP S2 | Yes; NAP S2 |
● Redundant PROFINET configuration (R1) | No | No | ||
● H-Sync forwarding | Yes | Yes | ||
Media redundancy | ||||
— MRP | Yes | Yes | Yes | Yes |
— MRPD | No | No | No | No |
Open IE communication | ||||
● TCP/IP | Yes | Yes | Yes | Yes |
● SNMP | Yes | Yes | Yes | Yes |
● LLDP | Yes | Yes | Yes | Yes |
Isochronous mode | ||||
Equidistance | Yes | Yes | ||
shortest clock pulse | 250 µs | 250 µs | ||
max. cycle | 4 ms | 4 ms | ||
Bus cycle time (TDP), min. | 250 µs | 250 µs | ||
Jitter, max. | 1 µs | 1 µs | ||
Interrupts/diagnostics/status information | ||||
Status indicator | Yes | Yes | Yes | Yes |
Alarms | Yes | Yes | Yes | Yes |
Diagnostics function | Yes | Yes | Yes | Yes |
Diagnostics indication LED | ||||
● RUN LED | Yes; green LED | Yes; green LED | Yes; green LED | Yes; green LED |
● ERROR LED | Yes; red LED | Yes; red LED | Yes; red LED | Yes; red LED |
● MAINT LED | Yes; Yellow LED | Yes; Yellow LED | Yes; Yellow LED | Yes; Yellow LED |
● Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED | Yes; green PWR LED | Yes; green PWR LED | Yes; green PWR LED |
● Connection display LINK TX/RX | Yes; 2x green link LEDs on BusAdapter | Yes; 2x green link LEDs on BusAdapter | Yes; 2x green link LEDs on BusAdapter | Yes; 2x green link LEDs on BusAdapter |
Potential separation | ||||
between backplane bus and electronics | No | No | No | No |
between PROFINET and all other circuits | Yes; 1 500 V AC | Yes; 1 500 V AC | Yes | Yes |
between supply and all other circuits | No | No | No | No |
Permissible potential difference | ||||
between different circuits | Safety extra low voltage SELV | Safety extra low voltage SELV | ||
Isolation | ||||
Isolation tested with | 750 V DC (type test) and according to EN 50155 (routine test) | 750 V DC (type test) and according to EN 50155 (routine test) | 750 V DC (type test) and according to EN 50155 (routine test) | 750 V DC (type test) and according to EN 50155 (routine test) |
Standards, approvals, certificates | ||||
Network loading class | 2 | 2 | 3 | 3 |
Security level | According to Security Level 1 Test Cases V1.1.1 | According to Security Level 1 Test Cases V1.1.1 | According to Security Level 1 Test Cases V1.1.1 | According to Security Level 1 Test Cases V1.1.1 |
Railway application | ||||
● EN 50121-3-2 | Yes; EMC for rail vehicles | Yes; EMC for rail vehicles | Yes; EMC for rail vehicles | Yes; EMC for rail vehicles |
● EN 50121-4 | Yes; EMC for signal and telecommunications systems | Yes; EMC for signal and telecommunications systems | Yes; EMC for signal and telecommunications systems | Yes; EMC for signal and telecommunications systems |
● EN 50124-1 | Yes; Railway applications – overvoltage category OV2; pollution degree PD2; rated surge voltage UNi = 0.5 kV; UNm = 24 V DC | Yes; Railway applications – overvoltage category OV2; pollution degree PD2; rated surge voltage UNi = 0.5 kV; UNm = 24 V DC | Yes; Railway applications – overvoltage category OV2; pollution degree PD2; rated surge voltage UNi = 0.5 kV; UNm = 24 V DC | Yes; Railway applications – overvoltage category OV2; pollution degree PD2; rated surge voltage UNi = 0.5 kV; UNm = 24 V DC |
● EN 50125-1 | Yes; Rail vehicles – see ambient conditions | Yes; Rail vehicles – see ambient conditions | Yes; Rail vehicles – see ambient conditions | Yes; Rail vehicles – see ambient conditions |
● EN 50125-2 | Yes; Stationary electrical equipment – see ambient conditions | Yes; Stationary electrical equipment – see ambient conditions | Yes; Stationary electrical equipment – see ambient conditions | Yes; Stationary electrical equipment – see ambient conditions |
● EN 50125-3 | Yes; Signal and telecommunications systems – see ambient conditions; vibrations and shocks: Application point outside of tracks (1 m to 3 m away from track) | Yes; Signal and telecommunications systems – see ambient conditions; vibrations and shocks: Application point outside of tracks (1 m to 3 m away from track) | Yes; Signal and telecommunications systems – see ambient conditions; vibrations and shocks: Application point outside of tracks (1 m to 3 m away from track) | Yes; Signal and telecommunications systems – see ambient conditions; vibrations and shocks: Application point outside of tracks (1 m to 3 m away from track) |
● EN 50155 | Yes; Rail vehicles – temperature class OT4, ST1/ST2, horizontal mounting position | Yes; Rail vehicles – temperature class OT4, ST1/ST2, horizontal mounting position | Yes; Rail vehicles – temperature class OT1, ST1/ST2, horizontal mounting position | Yes; Rail vehicles – temperature class OT4, ST1/ST2, horizontal mounting position |
● EN 61373 | Yes; Rail vehicles – vibrations and shocks: Category 1 Class A/B | Yes; Rail vehicles – vibrations and shocks: Category 1 Class A/B | Yes; Rail vehicles – vibrations and shocks: Category 1 Class A/B | Yes; Rail vehicles – vibrations and shocks: Category 1 Class A/B |
● Fire protection acc. to EN 45545-2 | Yes; For proof of conformity, see Service & Support | Yes; For proof of conformity, see Service & Support | Yes; For proof of conformity, see Service & Support | Yes; For proof of conformity, see Service & Support |
Ambient conditions | ||||
Ambient temperature during operation | ||||
● horizontal installation, min. | -40 °C; = Tmin (incl. condensation/frost) | -40 °C; = Tmin (incl. condensation/frost) | -30 °C; = Tmin (incl. condensation/frost) | -40 °C; = Tmin (incl. condensation/frost) |
● horizontal installation, max. | 70 °C; = Tmax; +85 °C for 10 min (OT4, ST1/ST2 acc. to EN 50155) | 70 °C; = Tmax; +85 °C for 10 min (OT4, ST1/ST2 acc. to EN 50155) | 60 °C; = Tmax; +70 °C for 10 min (OT1, ST1/ST2 acc. to EN 50155) | 70 °C; = Tmax; +85 °C for 10 min (OT4, ST1/ST2 acc. to EN 50155) |
● vertical installation, min. | -40 °C; = Tmin | -40 °C; = Tmin | -30 °C; = Tmin | -40 °C; = Tmin |
● vertical installation, max. | 50 °C; = Tmax | 50 °C; = Tmax | 50 °C; = Tmax | 50 °C; = Tmax |
Altitude during operation relating to sea level | ||||
● Installation altitude above sea level, max. | 2 000 m | 2 000 m | 2 000 m | 2 000 m |
● Ambient air temperature-barometric pressure-altitude | Tmin … Tmax at 1 140 hPa … 795 hPa (-1 000 m … +2 000 m) | Tmin … Tmax at 1 140 hPa … 795 hPa (-1 000 m … +2 000 m) | Tmin … Tmax at 1 140 hPa … 795 hPa (-1 000 m … +2 000 m) | Tmin … Tmax at 1 140 hPa … 795 hPa (-1 000 m … +2 000 m) |
Relative humidity | ||||
● With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation | 100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation | 100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation | 100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation |
Resistance | ||||
Coolants and lubricants | ||||
— Resistant to commercially available coolants and lubricants | Yes; Incl. diesel and oil droplets in the air | Yes; Incl. diesel and oil droplets in the air | Yes; Incl. diesel and oil droplets in the air | Yes; Incl. diesel and oil droplets in the air |
Use in stationary industrial systems | ||||
— to biologically active substances according to EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
— to chemically active substances according to EN 60721-3-3 | Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * | Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * | Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * | Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
— to mechanically active substances according to EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust, * | Yes; Class 3S4 incl. sand, dust, * | Yes; Class 3S4 incl. sand, dust, * | Yes; Class 3S4 incl. sand, dust, * |
— Against mechanical environmental conditions acc. to EN 60721-3-3 | Yes; Class 3M8 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0) | Yes; Class 3M8 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0) | Yes; Class 3M8 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0) | |
Use on land craft, rail vehicles and special-purpose vehicles | ||||
— to biologically active substances according to EN 60721-3-5 | Yes; Class 5B2 mold, fungus and dry rot spores (with the exception of fauna); Class 5B3 on request | Yes; Class 5B2 mold, fungus and dry rot spores (with the exception of fauna); Class 5B3 on request | Yes; Class 5B2 mold, fungus and dry rot spores (with the exception of fauna); Class 5B3 on request | Yes; Class 5B2 mold, fungus and dry rot spores (with the exception of fauna); Class 5B3 on request |
— to chemically active substances according to EN 60721-3-5 | Yes; Class 5C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * | Yes; Class 5C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * | Yes; Class 5C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * | Yes; Class 5C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
— to mechanically active substances according to EN 60721-3-5 | Yes; Class 5S3 incl. sand, dust; * | Yes; Class 5S3 incl. sand, dust; * | Yes; Class 5S3 incl. sand, dust; * | Yes; Class 5S3 incl. sand, dust; * |
— Against mechanical environmental conditions acc. to EN 60721-3-5 | Yes; Class 5M2 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0) | Yes; Class 5M2 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0) | Yes; Class 5M2 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0) | |
— against mechanical environmental conditions in agriculture acc. to ISO 15003 | Yes; level 1 (Location LE) using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0) | Yes; level 1 (Location LE) using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0) | Yes; level 1 (Location LE) using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0) | |
Usage in industrial process technology | ||||
— Against chemically active substances acc. to EN 60654-4 | Yes; Class 3 (excluding trichlorethylene) | Yes; Class 3 (excluding trichlorethylene) | Yes; Class 3 (excluding trichlorethylene) | Yes; Class 3 (excluding trichlorethylene) |
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04 | Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil) | Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil) | Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil) | Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil) |
Remark | ||||
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04 | * The supplied plug covers must remain in place over the unused interfaces during operation! | * The supplied plug covers must remain in place over the unused interfaces during operation! | * The supplied plug covers must remain in place over the unused interfaces during operation! | * The supplied plug covers must remain in place over the unused interfaces during operation! |
Conformal coating | ||||
● Coatings for printed circuit board assemblies acc. to EN 61086 | Yes; Class 2 for high reliability | Yes; Class 2 for high reliability | Yes; Class 2 for high reliability | Yes; Class 2 for high reliability |
● Protection against fouling acc. to EN 60664-3 | Yes; Type 1 protection | Yes; Type 1 protection | Yes; Type 1 protection | Yes; Type 1 protection |
● Electronic equipment on rolling stock acc. to EN 50155 | Yes; Class PC2 protective coating acc. to EN 50155:2017 | Yes; Class PC2 protective coating acc. to EN 50155:2017 | Yes; Class PC2 protective coating acc. to EN 50155:2017 | Yes; Class PC2 protective coating acc. to EN 50155:2017 |
● Military testing according to MIL-I-46058C, Amendment 7 | Yes; Discoloration of coating possible during service life | Yes; Discoloration of coating possible during service life | Yes; Discoloration of coating possible during service life | Yes; Discoloration of coating possible during service life |
● Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830A | Yes; Conformal coating, Class A | Yes; Conformal coating, Class A | Yes; Conformal coating, Class A | Yes; Conformal coating, Class A |
connection method / header | ||||
ET-Connection | ||||
● via BU/BA Send | Yes; + 16 ET 200AL modules | Yes; + 16 ET 200AL modules | Yes; + 16 ET 200AL modules | Yes; + 16 ET 200AL modules |
Mechanics/material | ||||
Strain relief | Yes; Optional | Yes; Optional | ||
Dimensions | ||||
Width | 50 mm | 50 mm | 50 mm | 50 mm |
Height | 117 mm | 117 mm | 117 mm | 117 mm |
Depth | 74 mm | 74 mm | 74 mm | 74 mm |
Weights | ||||
Weight, approx. | 190 g; IM 155-6 PN BA with 2x RJ45 ports and server module | 147 g; without BusAdapter | 120 g; without BusAdapter | 120 g; without BusAdapter |
Other | ||||
Note: | for use in railway applications, also observe the product information “SIPLUS extreme RAIL” A5E37661960A, Online Support article 109736776 | for use in railway applications, also observe the product information “SIPLUS extreme RAIL” A5E37661960A, Online Support article 109736776 | for use in railway applications, also observe the product information “SIPLUS extreme RAIL” A5E37661960A, Online Support article 109736776 | for use in railway applications, also observe the product information “SIPLUS extreme RAIL” A5E37661960A, Online Support article 109736776 |
Weight | N/A |
---|---|
Dimensions | N/A |
INOSAKI Limited
RM B 5/F Gaylord Comm,
Bldg 114-118 Lockhart Rd.
Hong Kong
INOSAKI Sdn. Bhd.
2-1-9, Ground Floor, One Square, Tingkat Mahsuri 1,
11900 Bayan Lepas, Penan
INOSAKI Pte. Ltd.
101 Upper Cross Street,
No. 06-17, People’s Park Centre,
Singapore (058357)