SIMATIC ET 200eco PN – Digital I/O Devices – Siemens I/O Devices

$ 154.92$ 557.03

SKU: N/A

Digital inputs record 24 V DC signals in the plant and forward them to the controller. Switches and 2, 3 or 4-wire proximity switches can be connected.

Digital outputs switch 24 V DC voltages in the plant, thus transferring internal signals from the controller to the plant. Solenoid valves, DC contactors, and indicator lights can be connected.

The 30 mm and 45 mm wide I/O devices are especially suitable for use in extremely confined spaces. All I/O devices have configurable parameters and diagnostic functions and can thus be freely adapted to the respective process requirements.

Siemens Digital I/O Devices SIMATIC ET 200eco PN Product Specifications:

Article number 6ES7141-6BF00-0AB0 6ES7141-6BG00-0AB0 6ES7141-6BH00-0AB0
ET200eco PN, 8DI, DC24V, 4xM12 ET200eco PN, 8DI, DC24V, 8xM12 ET200eco PN, 16DI, DC24V, 8xM12
General information
Vendor identification (VendorID) 002AH 002AH 002AH
Device identifier (DeviceID) 0306H 0306H 0306H
Supply voltage
Rated value (DC) 24 V 24 V 24 V
Reverse polarity protection Yes Yes Yes
power supply according to NEC Class 2 required Yes Yes Yes
Input current
Current consumption, typ. 100 mA 100 mA 100 mA
from supply voltage 1L+, max. 4 A 4 A 4 A
Encoder supply
Number of outputs 4 8 8
24 V encoder supply
● Short-circuit protection Yes; Electronic Yes; Electronic Yes; Electronic
● Output current, max. 100 mA; per output 100 mA; per output 100 mA; per output
Power loss
Power loss, typ. 5.5 W 4.5 W 6.5 W
Digital inputs
Number of digital inputs 8 8 16
● in groups of 2 1 2
Input characteristic curve in accordance with IEC 61131, type 3 Yes Yes Yes
Number of simultaneously controllable inputs
all mounting positions
— up to 60 °C, max. 8 8 16
Input voltage
● Rated value (DC) 24 V 24 V 24 V
● for signal “0” -3 to +5V -3 to +5V -3 to +5V
● for signal “1” +11 to +30V +11 to +30V +11 to +30V
Input current
● for signal “1”, typ. 7 mA 7 mA 7 mA
Input delay (for rated value of input voltage)
for standard inputs
— at “0” to “1”, max. typically 3 ms typically 3 ms typically 3 ms
— at “1” to “0”, max. typically 3 ms typically 3 ms typically 3 ms
Cable length
● unshielded, max. 30 m 30 m 30 m
Encoder
Connectable encoders
● 2-wire sensor Yes Yes Yes
— permissible quiescent current (2-wire sensor), max. 1.5 mA 1.5 mA 1.5 mA
Interfaces
Transmission procedure 100BASE-TX 100BASE-TX 100BASE-TX
Number of PROFINET interfaces 1 1 1
1. Interface
Interface types
● M12 port Yes Yes Yes
● integrated switch Yes Yes Yes
Interface types
M12 port
● Autonegotiation Yes Yes Yes
● Autocrossing Yes Yes Yes
● Transmission rate, max. 100 Mbit/s 100 Mbit/s 100 Mbit/s
Protocols
Supports protocol for PROFINET IO Yes Yes Yes
PROFINET CBA No No No
PROFIsafe No No No
PROFINET IO Device
Services
— IRT with the option “high flexibility” Yes Yes Yes
— Prioritized startup Yes Yes Yes
Redundancy mode
Media redundancy
— MRP Yes Yes Yes
Open IE communication
● TCP/IP No No No
● SNMP Yes Yes Yes
● DCP Yes Yes Yes
● LLDP Yes Yes Yes
● ping Yes Yes Yes
● ARP Yes Yes Yes
Interrupts/diagnostics/status information
Diagnostics function Yes Yes Yes
Alarms
● Diagnostic alarm Yes Yes Yes
Diagnoses
● Diagnostic information readable Yes Yes Yes
● Monitoring the supply voltage Yes; green “ON” LED Yes; green “ON” LED Yes; green “ON” LED
● Wire-break in signal transmitter cable Yes Yes Yes
● Short-circuit encoder supply Yes; Per channel group Yes; Per channel group Yes; Per channel group
● Group error Yes; Red/yellow “SF/MT” LED Yes; Red/yellow “SF/MT” LED Yes; Red/yellow “SF/MT” LED
Potential separation
between the load voltages Yes Yes Yes
between load voltage and all other switching components No No No
between Ethernet and electronics Yes Yes Yes
Potential separation channels
● between the channels No No No
Isolation
tested with
● 24 V DC circuits 707 V DC (type test) 707 V DC (type test) 707 V DC (type test)
● Test voltage for interface, rms value [Vrms] 1 500 V; According to IEEE 802.3 1 500 V; According to IEEE 802.3 1 500 V; According to IEEE 802.3
Degree and class of protection
IP degree of protection IP65/67 IP65/67 IP65/67
connection method / header
Design of electrical connection 4/5-pin M12 circular connectors 4/5-pin M12 circular connectors 4/5-pin M12 circular connectors
Dimensions
Width 30 mm 60 mm 60 mm
Height 200 mm 175 mm 175 mm
Depth 49 mm 49 mm 49 mm
Weights
Weight, approx. 550 g 910 g 910 g

 

Article number 6ES7142-6BF50-0AB0 6ES7142-6BF00-0AB0 6ES7142-6BG00-0AB0 6ES7142-6BR00-0AB0 6ES7142-6BH00-0AB0
ET200eco PN, 8DO, DC24V/0,5A, 4xM12 ET200eco PN, 8DO, DC24V/1,3A, 4xM12 ET200eco PN, 8DO, DC24V/1,3A, 8xM12 ET200eco PN, 8 DO, DC24V/2A, 8xM12 ET200eco PN, 16DO DC24V/1,3A, 8xM12
General information
Vendor identification (VendorID) 002AH 002AH 002AH 002AH 002AH
Device identifier (DeviceID) 0306H 0306H 0306H 0306H 0306H
Supply voltage
Rated value (DC) 24 V 24 V 24 V 24 V 24 V
Reverse polarity protection Yes Yes Yes Yes Yes
power supply according to NEC Class 2 required Yes Yes Yes Yes Yes
Load voltage 1L+
● Rated value (DC) 24 V 24 V 24 V 24 V 24 V
● permissible range, lower limit (DC) 20.4 V 20.4 V 20.4 V 20.4 V 20.4 V
● permissible range, upper limit (DC) 28.8 V 28.8 V 28.8 V 28.8 V 28.8 V
● Reverse polarity protection Yes Yes Yes Yes Yes
Load voltage 2L+
● Rated value (DC) 24 V 24 V 24 V 24 V 24 V
● permissible range, lower limit (DC) 20.4 V 20.4 V 20.4 V 20.4 V 20.4 V
● permissible range, upper limit (DC) 28.8 V 28.8 V 28.8 V 28.8 V 28.8 V
● Reverse polarity protection Yes Yes Yes Yes Yes
Input current
Current consumption, typ. 100 mA 100 mA 100 mA 100 mA 100 mA
from supply voltage 1L+, max. 4 A 4 A 4 A 4 A 4 A
from load voltage 1L+ (unswitched voltage) 100 mA 4 A 4 A 4 A 4 A
from load voltage 2L+, max. 4 A 4 A 4 A 4 A 4 A
Power loss
Power loss, typ. 3 W 5.5 W 5.5 W 5 W 5.5 W
Digital outputs
Number of digital outputs 8 8 8 8 16
● in groups of 8 4 4 4 8
Short-circuit protection Yes Yes Yes Yes Yes
● Response threshold, typ. 0.7 A 1.8 A 1.8 A 2.8 A 1.8 A
Limitation of inductive shutdown voltage to Typ. (L1+, L2+) -47 V Typ. (L1+, L2+) -47 V Typ. (L1+, L2+) -47 V Typ. (L1+, L2+) -47 V Typ. (L1+, L2+) -47 V
Controlling a digital input Yes Yes Yes Yes Yes
Switching capacity of the outputs
● on lamp load, max. 5 W 5 W 5 W 10 W 5 W
Output current
● for signal “1” rated value 0.5 A 1.3 A; Maximum 1.3 A; Maximum 2 A 1.3 A; Maximum
● for signal “0” residual current, max. 1.5 mA 1.5 mA 1.5 mA 1.5 mA 1.5 mA
Parallel switching of two outputs
● for uprating No No No No No
● for redundant control of a load Yes Yes Yes Yes Yes
Switching frequency
● with resistive load, max. 100 Hz 100 Hz 100 Hz 100 Hz 100 Hz
● with inductive load, max. 0.5 Hz 0.5 Hz 0.5 Hz 0.5 Hz 0.5 Hz
● on lamp load, max. 1 Hz 1 Hz 1 Hz 1 Hz 1 Hz
Total current of the outputs (per group)
all mounting positions
— up to 55 °C, max. 3.9 A
— up to 60 °C, max. 4 A 2.6 A 3.9 A 3.9 A 3.9 A
Cable length
● unshielded, max. 30 m 30 m 30 m 30 m 30 m
Interfaces
Transmission procedure 100BASE-TX 100BASE-TX 100BASE-TX 100BASE-TX 100BASE-TX
Number of PROFINET interfaces 1 1 1 1 1
1. Interface
Interface types
● M12 port Yes
● integrated switch Yes Yes Yes Yes Yes
Interface types
M12 port
● Autonegotiation Yes Yes Yes Yes Yes
● Autocrossing Yes Yes Yes Yes Yes
● Transmission rate, max. 100 Mbit/s 100 Mbit/s 100 Mbit/s 100 Mbit/s 100 Mbit/s
Protocols
Supports protocol for PROFINET IO Yes Yes Yes Yes Yes
PROFINET CBA No No No No No
PROFIsafe No No No No No
PROFINET IO Device
Services
— IRT with the option “high flexibility” Yes Yes Yes Yes Yes
— Prioritized startup Yes Yes Yes Yes Yes
Redundancy mode
Media redundancy
— MRP Yes Yes Yes Yes Yes
Open IE communication
● TCP/IP No No No No No
● SNMP Yes Yes Yes Yes Yes
● DCP Yes Yes Yes Yes Yes
● LLDP Yes Yes Yes Yes Yes
● ping Yes Yes Yes Yes Yes
● ARP Yes Yes Yes Yes Yes
Interrupts/diagnostics/status information
Diagnostics function Yes Yes Yes Yes Yes
Alarms
● Diagnostic alarm Yes Yes Yes Yes Yes
Diagnoses
● Diagnostic information readable Yes Yes Yes Yes Yes
● Monitoring the supply voltage Yes; green “ON” LED Yes; green “ON” LED Yes; green “ON” LED Yes; green “ON” LED Yes; green “ON” LED
● Wire-break in actuator cable Yes Yes Yes Yes Yes
● Short-circuit Yes Yes Yes Yes Yes
● Group error Yes; Red/yellow “SF/MT” LED Yes; Red/yellow “SF/MT” LED Yes; Red/yellow “SF/MT” LED Yes; Red/yellow “SF/MT” LED Yes; Red/yellow “SF/MT” LED
Potential separation
between the load voltages Yes Yes Yes Yes Yes
between load voltage and all other switching components No No No No No
between Ethernet and electronics Yes Yes Yes Yes Yes
Potential separation channels
● between the channels No No No No No
Isolation
tested with
● 24 V DC circuits 707 V DC (type test) 707 V DC (type test) 707 V DC (type test) 707 V DC (type test) 707 V DC (type test)
● Test voltage for interface, rms value [Vrms] 1 500 V; According to IEEE 802.3 1 500 V; According to IEEE 802.3 1 500 V; According to IEEE 802.3 1 500 V; According to IEEE 802.3 1 500 V; According to IEEE 802.3
Degree and class of protection
IP degree of protection IP65/67 IP65/67 IP65/67 IP65/67 IP65/67
Standards, approvals, certificates
Suitable for safety-related tripping of standard modules Yes Yes Yes Yes Yes
Highest safety class achievable for safety-related tripping of standard modules
● Performance level according to ISO 13849-1 PL d PL d PL d PL d PL d
● Category according to ISO 13849-1 Cat. 3 Cat. 3 Cat. 3 Cat. 3 Cat. 3
● SIL acc. to IEC 62061 SIL 2 SIL 2 SIL 2 SIL 2 SIL 2
connection method / header
Design of electrical connection 4/5-pin M12 circular connectors 4/5-pin M12 circular connectors 4/5-pin M12 circular connectors 4/5-pin M12 circular connectors 4/5-pin M12 circular connectors
Dimensions
Width 30 mm 30 mm 60 mm 60 mm 60 mm
Height 200 mm 200 mm 175 mm 175 mm 175 mm
Depth 49 mm 49 mm 49 mm 49 mm 49 mm
Weights
Weight, approx. 550 g 550 g 910 g 910 g 910 g

 

 

Article number 6ES7147-6BG00-0AB0
ET200eco PN, 8 DIO, DC24V/1,3A, 8xM12
General information
Vendor identification (VendorID) 002AH
Device identifier (DeviceID) 0306H
Supply voltage
Rated value (DC) 24 V
Reverse polarity protection Yes
power supply according to NEC Class 2 required Yes
Load voltage 2L+
● Rated value (DC) 24 V
● permissible range, lower limit (DC) 20.4 V
● permissible range, upper limit (DC) 28.8 V
● Reverse polarity protection Yes
Input current
Current consumption, typ. 100 mA
from supply voltage 1L+, max. 4 A
from load voltage 1L+ (unswitched voltage) 4 A
from load voltage 2L+, max. 4 A
Encoder supply
24 V encoder supply
● Short-circuit protection Yes; Electronic
● Output current, max. 100 mA; per output
Power loss
Power loss, typ. 6.5 W
Digital inputs
Number of digital inputs 8
● in groups of 4
Input characteristic curve in accordance with IEC 61131, type 3 Yes
Number of simultaneously controllable inputs
all mounting positions
— up to 60 °C, max. 8
Input voltage
● Rated value (DC) 24 V
● for signal “0” -3 to +5V
● for signal “1” +11 to +30V
Input current
● for signal “1”, typ. 7 mA
Input delay (for rated value of input voltage)
for standard inputs
— at “0” to “1”, max. typically 3 ms
— at “1” to “0”, max. typically 3 ms
Cable length
● unshielded, max. 30 m
Digital outputs
Number of digital outputs 8
● in groups of 4
Short-circuit protection Yes; Electronic
● Response threshold, typ. 1.8 A
Limitation of inductive shutdown voltage to Typ. (L1+, L2+) -47 V
Controlling a digital input Yes
Switching capacity of the outputs
● on lamp load, max. 5 W
Output current
● for signal “1” rated value 1.3 A; Maximum
● for signal “1” permissible range, max. 1.3 A
● for signal “0” residual current, max. 1.5 mA
Parallel switching of two outputs
● for uprating No
● for redundant control of a load Yes
Switching frequency
● with resistive load, max. 100 Hz
● with inductive load, max. 0.5 Hz
● on lamp load, max. 1 Hz
Total current of the outputs (per group)
all mounting positions
— up to 60 °C, max. 3.9 A
Cable length
● unshielded, max. 30 m
Encoder
Connectable encoders
● 2-wire sensor Yes
— permissible quiescent current (2-wire sensor), max. 1.5 mA
Interfaces
Transmission procedure 100BASE-TX
Number of PROFINET interfaces 1
1. Interface
Interface types
● M12 port Yes
● integrated switch Yes
Interface types
M12 port
● Autonegotiation Yes
● Autocrossing Yes
● Transmission rate, max. 100 Mbit/s
Protocols
Supports protocol for PROFINET IO Yes
PROFINET CBA No
PROFIsafe No
PROFINET IO Device
Services
— IRT with the option “high flexibility” Yes
— Prioritized startup Yes
Redundancy mode
Media redundancy
— MRP Yes
Open IE communication
● TCP/IP No
● SNMP Yes
● DCP Yes
● LLDP Yes
● ping Yes
● ARP Yes
Interrupts/diagnostics/status information
Diagnostics function Yes
Alarms
● Diagnostic alarm Yes
Diagnoses
● Diagnostic information readable Yes
● Monitoring the supply voltage Yes; green “ON” LED
● Wire-break in actuator cable Yes
● Wire-break in signal transmitter cable Yes
● Short-circuit Yes
● Short-circuit encoder supply Yes
● Group error Yes; Red/yellow “SF/MT” LED
Potential separation
between the load voltages Yes
between load voltage and all other switching components No
between Ethernet and electronics Yes
Potential separation channels
● between the channels No
Isolation
tested with
● 24 V DC circuits 707 V DC (type test)
● Test voltage for interface, rms value [Vrms] 1 500 V; According to IEEE 802.3
Degree and class of protection
IP degree of protection IP65/67
Standards, approvals, certificates
Suitable for safety-related tripping of standard modules No
connection method / header
Design of electrical connection 4/5-pin M12 circular connectors
Dimensions
Width 60 mm
Height 175 mm
Depth 49 mm
Weights
Weight, approx. 910 g
Weight N/A
Dimensions N/A