$ 489.90
| Signal type | Digital Input |
| Safety Integrity Level (SIL) | SIL 2 |
| Connection | terminals 23+, 24- or power feed module/Power Rail | |
| Rated voltage | Ur | 20 … 30 V DC |
| Rated current | Ir | approx. 100 mA |
| Power dissipation/power consumption | ≤ 2 W / 2.2 W |
| Programming interface | programming socket |
| Connection side | field side | ||||||
| Connection | Input I: intrinsically safe: terminals 1+, 3- Input II: non-intrinsically safe: terminals 13+, 14- |
||||||
| Input I | sensor acc. to EN 60947-5-6 (NAMUR) or mechanical contact | ||||||
|
|||||||
| Input II | startup override: 1 … 1000 s, adjustable in steps of 1 s | ||||||
|
|||||||
| Connection side | control side | ||||||||
| Connection | output I: terminals 10, 11, 12 output II: terminals 16, 17, 18 outout III: terminasl 19+, 20- output IV: terminals 8+, 7- |
||||||||
| Output I, II | signal, relay | ||||||||
|
|||||||||
| Output III | electronic output, passive | ||||||||
|
|||||||||
| Output IV | analog | ||||||||
|
|||||||||
| Collective error message | Power Rail | ||||||||
| Input I | ||||||||||||
|
||||||||||||
| Output I, II | ||||||||||||
|
||||||||||||
| Output IV | ||||||||||||
|
||||||||||||
| Input I/other circuits | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Output I, II/other circuits | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Mutual output I, II, III | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Output III/power supply and collective error | basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff |
| Output III/start-up override | basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff |
| Output III/IV | basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff |
| Output IV/power supply and collective error | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff |
| Start-up override/power supply and collective error | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff |
| Interface/power supply and collective error | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff |
| Interface/output III | basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff |
| Display elements | LEDs , display |
| Control elements | Control panel |
| Configuration | via operating buttons via PACTware |
| Labeling | space for labeling at the front |
| Electromagnetic compatibility | ||||
|
||||
| Low voltage | ||||
|
||||
| Electromagnetic compatibility | NE 21:2006 |
| Degree of protection | IEC 60529:2001 |
| Input | EN 60947-5-6:2000 |
| Ambient temperature | -20 … 60 °C (-4 … 140 °F) |
| Degree of protection | IP20 | ||||||
| Connection | screw terminals | ||||||
| Mass | 300 g | ||||||
| Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2 | ||||||
|
|||||||
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | ||||||
| EU-type examination certificate | TÜV 99 ATEX 1471 | ||||||
|
|||||||
| Supply | |||||||
|
|||||||
| Input I | terminals 1+, 3-: Ex ia | ||||||
|
|||||||
| Input II | terminals 13+, 14- non-intrinsically safe | ||||||
|
|||||||
| Output I, II | terminals 10, 11, 12; 16, 17, 18 non-intrinsically safe | ||||||
|
|||||||
| Output III | terminals 19+, 20- non-intrinsically safe | ||||||
|
|||||||
| Output IV | terminals 8+, 7- non-intrinsically safe | ||||||
|
|||||||
| Interface | RS 232 | ||||||
|
|||||||
| Certificate | TÜV 02 ATEX 1885 X | ||||||
|
|||||||
| Output I, II | |||||||
|
|||||||
| Galvanic isolation | |||||||
|
|||||||
| Directive conformity | |||||||
|
|||||||
| FM approval | |||||
|
|||||
| UL approval | E223772 | ||||
| IECEx approval | |||||
|
|||||
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |