G9SA – Emergency-stop Units – Omron Safety Relay Units

$ 139.70

SKU: N/A

Specify the power supply voltage when ordering.

G9SA Master Units

Emergency-stop Units

Main contacts Auxiliary contact Number of input channels Rated voltage Model
3PST-NO SPST-NC 1 channel or 2 channels possible 24 VAC/VDC G9SA-301
100 to 240 VAC
5PST-NO 24 VAC/VDC G9SA-501
100 to 240 VAC

 

 

Ratings

Power Input

Model G9SA-301/TH301 G9SA-501 G9SA-321-T[]
Power supply
voltage
24 VAC/VDC: 24 VAC, 50/60 Hz, or 24 VDC
100 to 240 VAC: 100 to 240 VAC, 50/60 Hz
Operating
voltage range
85% to 110% of rated power supply voltage
Power
consumption*
24 VAC/VDC: 5.7 VA/1.7 W max.
100 to 240 VAC: 9 VA max.
24 VAC/VDC: 7.4 VA/2.6 W max.
100 to 240 VAC: 11 VA max.
24 VAC/VDC: 8.6 VA/3.3 W max.
100 to 240 VAC: 12.5 VA max.

 

 

* When an Expansion Unit is connected, the power consumption is increased by 2 VA/2 W max.

Inputs

Model G9SA-301/321-T[]/TH301 G9SA-501
Input current * 40 mA max. 60 mA max

 

* When an Expansion Unit is connected, the input current is increased by 30 mA max.

Contacts

Model
Load
G9SA-301/501/321-T[]/TH301/EX301/EX031-T[]
Resistive load
Rated load 250 VAC, 5 A
30 VDC, 5 A
Rated carry current 5 A

 

 

Characteristics

Model G9SA-301/TH301 G9SA-501/321-T[] G9SA-EX301/EX031-T[]
Contact resistance *1 100 mΩ
Operating time *2 30 ms max.
Response time *3 10 ms max.
Isolation
specification
Isolation voltage (Ui) 250 VAC
Impulse withstand voltage (Uimp) 4 kV
Insulation
resistance
*4
Between input and
output
100 MΩ min. (at 500 VDC)
Between different
poles of output
Dielectric
strength
Between input and
output
2,500 VAC 1min.
Between different
poles of output
Vibration resistance 10 to 55 to 10 Hz, 0.375-mm single amplitude
(0.75-mm double amplitude)
Shock
resistance
Destruction 300 m/s2
Malfunction 100 m/s2
Durability *5 Mechanical 5,000,000 operations min. (at approx. 7,200 operations/hr)
Electrical 100,000 operations min. (at approx. 1,800 operations/hr)
Failure rate (P Level) (reference value) 5 VDC, 1 mA
Ambient operating temperature -25 to 55°C (with no icing or condensation)
Ambient operating humidity 35% to 85%
Terminal tightening torque 0.6 N·m
Weight *6 Approx. 210 g Approx. 270 g Approx. 130 g

 

 

*1. The contact resistance was measured with 1 A at 5 VDC using the voltage-drop method.
*2. Not Including bounce time.
*3. The response time is the time it takes for the main contact to open after the input is turned OFF. Includes bounce time.
*4. The insulation resistance was measured with 500 VDC at the same places that the dielectric strength was checked.
*5. The durability is for an ambient temperature of 15 to 35℃ and an ambient humidity of 25% to 75%.
*6. Weight shown is for 24-VAC/VDC type. For 100 to 240-VAC type, add approximately 20 g.

 

Weight N/A
Model

G9SA-301 AC/DC24