CS1W-DRM21-V1 – CS-series DeviceNet Unit – Programmable Controllers – Omron
$ 635.49
SKU: CS1W-DRM21-V1
Omron Automation Systems include Programmable Controllers that support machine control, and Network/Software products to support easy information exchange with host systems.
Lineup
Product | Appearance | Specifications | Model | Stand- ards |
|||
---|---|---|---|---|---|---|---|
Number of licenses |
Media | ||||||
DeviceNet Unit |
For CS Series Functions as either a master or a slave. 2,048 I/O points |
CS1W-DRM21-V1 | UC1, N, L, CE |
||||
CX-One FA Integrated Tool Package Ver.4.[] |
The CX-One is a package that integrates the Support Software for OMRON PLCs and components. CX- One runs on the following OS. OS: Windows XP (Service Pack 3 or higher, 32-bit version)/ Windows Vista (32-bit/64-bit version)/ Windows 7 (32-bit/64-bit version)/ Windows 8 (32-bit/64-bit version)/ Windows 8.1 (32-bit/64-bit version)/ Windows 10 (32-bit/64-bit version)CX-One Ver.4.[] includes CX-Integrator Ver.2.[]. For details, refer to the CX-One catalog (Cat. No. R134). |
1 license * |
DVD | CXONE-AL01D-V4 | – |
Specifications
Communications Specifications
Item | Specifications | |||
---|---|---|---|---|
Communications protocol | DeviceNet | |||
Connection methods | Multi-drop and T-branch connections can be combined (for trunk and branch lines) *1 | |||
Baud rate | 500 Kbps, 250 Kbps, or 125 Kbps | |||
Communications media | Special 5-wire cables (2 signal lines, 2 power lines, 1 shield line) Special 4-wire flat cables (2 signal lines, 2 power lines) |
|||
Communications distances for special 5-wire cables |
Baud rate | Network length | Branch line length | Total branch line length |
500 kbps | 100 m max. | 6 m max. | 39 m max. | |
250 kbps | 250 m max. *2 | 6 m max. | 78 m max. | |
125 kbps | 500 m max. *2 | 6 m max. | 156 m max. | |
Communications distances for special 4-wire flat cables |
Baud rate | Network length | Branch line length | Total branch line length |
500 kbps | 75 m max. | 6 m max. | 35 m max. | |
250 kbps | 150 m max. | 6 m max. | 48 m max. | |
125 kbps | 265 m max. | 6 m max. | 135 m max. | |
Communications power supply | 24 V DC supplied externally | |||
Max. number of nodes | 64 nodes (including Masters, Slaves, and Configurator) |
*1. Terminators are required at both ends of trunk line.
*2. Indicates the maximum network length when thick cables are used. Reduce the network length to 100 m max. when using thin cables.
*2. Indicates the maximum network length when thick cables are used. Reduce the network length to 100 m max. when using thin cables.
Network Specifications
Specifications
Communications power supply voltage | 11 to 25 VDC *1 | |||
---|---|---|---|---|
Current consumption | Communications: 30 mA max. Internal circuit: 290 mA max. |
|||
Max. number of connectable slaves |
Remote I/O, explicit message service | 63 *2 | ||
Max. number of I/O points |
Fixed allocations | When used as a master | 2,048 points | |
When used as a slave | 32 points | |||
User-set allocations |
Using allocated DM Area words |
When used as a master | 16,000 points | |
When used as a slave | 3,200 points | |||
Using Configurator |
When used as a master | 32,000 points | ||
When used as a slave | 4,800 points | |||
Number of allocated words |
Fixed allocations | When used as a master | 64 input and 64 output words Software switch/status area: 25 words |
|
When used as a slave | 1 input word, 1 output word *3 | |||
User-set allocations |
Using allocated DM Area words |
When used as a master | 500 input and 500 output words Software switch/status area: 25 words |
|
When used as a slave | 100 input and 100 output words *3 Software switch/status area: 25 words |
|||
Using Configurator |
When used as a master | 500 input words x 2 blocks, 500 output words x 2 blocks Software switch/Status area: 25 words |
||
When used as a slave | 100 input words x 1 blocks, 100 output words x 2 blocks Software switch/Status area: 25 words |
|||
Max. message length | 542 bytes *4 | |||
Max. number of Units mountable to PLC |
Fixed allocations | 3 | ||
User-set allocations | 16 | |||
Weight | 172 g max. |
*1. Refer to the DeviceNet Operation Manual (W267) for the communications power supply specifications.
*2. The Device Unit uses a node, and so connection is possible to 63 slaves only.
*3. When the DeviceNet is used as a slave, “input” and “output” respectively refer to input from the slave to the master and output from the master to the slave.
*4. The maximum message length includes the command code when using the CMND instruction
*2. The Device Unit uses a node, and so connection is possible to 63 slaves only.
*3. When the DeviceNet is used as a slave, “input” and “output” respectively refer to input from the slave to the master and output from the master to the slave.
*4. The maximum message length includes the command code when using the CMND instruction