KCD2-EL – Signal Converters – PEPPERL+FUCHS Displays and Signal Processing

$ 99.00

SKU: KCD2-EL

Sensors used in the automation industry transmit a wide range of digital and analog signals. In many counting and control processes, these signals need to be clearly displayed, monitored, or processed. To help you find the perfect solution for such applications, we offer a wide range of counters, process displays, signal converters, and switch amplifiers that are all optimized for use with our sensors. The user-friendliness and durability of our products is always a priority at Pepperl+Fuchs.

Functional safety related parameters
MTTFd 1612 a
Indicators/operating means
LED yellow switch output
lead breakage: LED off, output locked
Electrical specifications
Operating voltage 10 … 30 V DC
Ripple ≤ 10 %
Operating current approx. 22 mA
Input
Connection terminals 1+, 2-
Connectable sensor types NAMUR
Pulse length/pulse interval ≥ 0.5 ms / ≥ 0.5 ms
Short-circuit current approx. 8 mA
Sensor supply 8 V DC
Switching point 1.2 … 2.1 mA hysteresis approx. 0.2 mA
Line fault detection with
Trip value 1 kHz
Output
Connection terminal 4-
Current 200 mA short-circuit protected
Transistor NPN
Signal level UB – 1.8V
Transfer characteristics
Mode of operation NO contact
Switching frequency 1 kHz
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU EN 61326-1:2013
Standard conformity
Degree of protection EN 60529:2000
Noise immunity EN 61326-1:2013
Ambient conditions
Ambient temperature -25 … 70 °C (-13 … 158 °F)
Storage temperature -25 … 85 °C (-13 … 185 °F)
Mechanical specifications
Degree of protection IP20
Connection self-opening apparatus connection terminals, max. core cross-section 0.34 … 2.5 mm2
Mass 60 g
Dimensions 20x60x40
(in mm)
Weight 0.06 kg