Analog output modules convert a 16-bit digital value into a current or a voltage and output this to the process. They are suitable, for example, for controlling proportional valves or small servo drives.
The following analog output modules are available:
Article number | 6ES7532-5HD00-0AB0 | 6ES7532-5HF00-0AB0 | 6ES7532-5ND00-0AB0 | |
S7-1500, AQ 4xU/I ST | S7-1500, AQ 8xU/I HS | S7-1500, AQ 4xU/I HF | ||
General information | ||||
Product type designation | AQ 4xU/I ST | AQ 8xU/I HS | AQ 4xU/I HF | |
HW functional status | from FS04 | From FS01 | From FS01 | |
Firmware version | V2.2.0 | V2.1.0 | V1.1.0 | |
● FW update possible | Yes | Yes | Yes | |
Product function | ||||
● I&M data | Yes; I&M0 to I&M3 | Yes; I&M0 to I&M3 | Yes; I&M0 to I&M3 | |
● Isochronous mode | No | Yes | Yes | |
● Prioritized startup | No | No | Yes | |
● Output range scalable | No | No | ||
Engineering with | ||||
● STEP 7 TIA Portal configurable/integrated from version | V12 / V12 | V14 / – | V14 / – | |
● STEP 7 configurable/integrated from version | V5.5 SP3 / – | V5.5 SP3 / – | V5.5 SP3 / – | |
● PROFIBUS from GSD version/GSD revision | V1.0 / V5.1 | V1.0 / V5.1 | V1.0 / V5.1 | |
● PROFINET from GSD version/GSD revision | V2.3 / – | V2.3 / – | V2.3 / – | |
Operating mode | ||||
● Oversampling | No | Yes | No | |
● MSO | Yes | Yes | Yes | |
CiR – Configuration in RUN | ||||
Reparameterization possible in RUN | Yes | Yes | Yes | |
Calibration possible in RUN | Yes | Yes | Yes | |
Supply voltage | ||||
Rated value (DC) | 24 V | 24 V | 24 V | |
permissible range, lower limit (DC) | 19.2 V | 19.2 V | 19.2 V | |
permissible range, upper limit (DC) | 28.8 V | 28.8 V | 28.8 V | |
Reverse polarity protection | Yes | Yes | Yes | |
Input current | ||||
Current consumption, max. | 190 mA; with 24 V DC supply | 320 mA; with 19.2 V supply | 160 mA | |
Power | ||||
Power available from the backplane bus | 0.6 W | 1.15 W | 0.95 W | |
Power loss | ||||
Power loss, typ. | 4 W | 7 W | 5 W | |
Analog outputs | ||||
Number of analog outputs | 4 | 8 | 4 | |
Voltage output, short-circuit protection | Yes | Yes | Yes | |
Voltage output, short-circuit current, max. | 24 mA | 45 mA | 24 mA | |
Current output, no-load voltage, max. | 22 V | 20 V | 22 V | |
Cycle time (all channels), min. | 3.2 ms; independent of number of activated channels | 125 µs; independent of number of activated channels | 125 µs; independent of number of activated channels | |
Output ranges, voltage | ||||
● 0 to 10 V | Yes | Yes | Yes | |
● 1 V to 5 V | Yes | Yes | Yes | |
● -5 V to +5 V | No | No | No | |
● -10 V to +10 V | Yes | Yes | Yes | |
Output ranges, current | ||||
● 0 to 20 mA | Yes | Yes | Yes | |
● -20 mA to +20 mA | Yes | Yes | Yes | |
● 4 mA to 20 mA | Yes | Yes | Yes | |
Connection of actuators | ||||
● for voltage output two-wire connection | Yes | Yes | Yes | |
● for voltage output four-wire connection | Yes | Yes | Yes | |
● for current output two-wire connection | Yes | Yes | Yes | |
Load impedance (in rated range of output) | ||||
● with voltage outputs, min. | 1 kΩ; 0.5 kOhm at 1 to 5 V | 1 kΩ | 1 kΩ; 0.5 kOhm at 1 to 5 V | |
● with voltage outputs, capacitive load, max. | 1 µF | 100 nF | 1 µF | |
● with current outputs, max. | 750 Ω | 500 Ω | 750 Ω | |
● with current outputs, inductive load, max. | 10 mH | 1 mH | 10 mH | |
Cable length | ||||
● shielded, max. | 800 m; for current, 200 m for voltage | 200 m | 800 m; for current, 200 m for voltage | |
Analog value generation for the outputs | ||||
Integration and conversion time/resolution per channel | ||||
● Resolution with overrange (bit including sign), max. | 16 bit | 16 bit | 16 bit | |
● Conversion time (per channel) | 0.5 ms | 50 µs; independent of number of activated channels | 125 µs; independent of number of activated channels | |
Settling time | ||||
● for resistive load | 1.5 ms | 30 µs; see additional description in the manual | 0.2 ms; see additional description in the manual | |
● for capacitive load | 2.5 ms | 100 µs; see additional description in the manual | 1.8 ms; see additional description in the manual | |
● for inductive load | 2.5 ms | 100 µs; see additional description in the manual | 2 ms; see additional description in the manual | |
Errors/accuracies | ||||
Output ripple (relative to output range, bandwidth 0 to 50 kHz), (+/-) | 0.02 % | 0.02 % | 0.02 % | |
Linearity error (relative to output range), (+/-) | 0.15 % | 0.15 % | 0.015 % | |
Temperature error (relative to output range), (+/-) | 0.002 %/K | 0.002 %/K | 0.002 %/K | |
Crosstalk between the outputs, max. | -100 dB | -100 dB | -100 dB | |
Repeat accuracy in steady state at 25 °C (relative to output range), (+/-) | 0.05 % | 0.05 % | 0.005 % | |
note regarding accuracy | at temperatures below 0 °C, the figures for operating error and temperature error are doubled | at temperatures below 0 °C, the figures for operating error and temperature error are doubled | at temperatures below 0 °C, the figures for operating error and temperature error are doubled | |
Operational error limit in overall temperature range | ||||
● Voltage, relative to output range, (+/-) | 0.3 % | 0.3 % | ±10 V; 0 V to 10 V: ±0.12%; 1 V to 5 V: ±0.1% | |
● Current, relative to output range, (+/-) | 0.3 % | 0.3 % | ±20 mA; 0 mA to 20 mA: ±0.2%; 4 mA to 20 mA: ±0.12% | |
Basic error limit (operational limit at 25 °C) | ||||
● Voltage, relative to output range, (+/-) | 0.2 % | 0.2 % | 0.06 % | |
● Current, relative to output range, (+/-) | 0.2 % | 0.2 % | 0.1 % | |
Isochronous mode | ||||
Execution and activation time (TCO), min. | 100 µs | 100 µs | ||
Bus cycle time (TDP), min. | 250 µs | 250 µs | ||
Interrupts/diagnostics/status information | ||||
Diagnostics function | Yes | Yes | Yes | |
Substitute values connectable | Yes | Yes | Yes | |
Alarms | ||||
● Diagnostic alarm | Yes | Yes | Yes | |
Diagnoses | ||||
● Monitoring the supply voltage | Yes | Yes | Yes | |
● Wire-break | Yes; Only for output type “current” | Yes; Only for output type “current” | Yes; Only for output type “current” | |
● Short-circuit | Yes; Only for output type “voltage” | Yes; Only for output type “voltage” | Yes; Only for output type “voltage” | |
● Overflow/underflow | Yes | Yes | Yes | |
Diagnostics indication LED | ||||
● RUN LED | Yes; green LED | Yes; green LED | Yes; green LED | |
● ERROR LED | Yes; red LED | Yes; red LED | Yes; red LED | |
● Monitoring of the supply voltage (PWR-LED) | Yes; green LED | Yes; green LED | Yes; green LED | |
● Channel status display | Yes; green LED | Yes; green LED | Yes; green LED | |
● for channel diagnostics | Yes; red LED | Yes; red LED | Yes; red LED | |
● for module diagnostics | Yes; red LED | Yes; red LED | Yes; red LED | |
Potential separation | ||||
Potential separation channels | ||||
● between the channels | No | No | Yes | |
● between the channels, in groups of | 4 | 8 | 1 | |
● between the channels and backplane bus | Yes | Yes | Yes | |
● Between the channels and load voltage L+ | Yes | Yes | Yes | |
Permissible potential difference | ||||
between different circuits | 60 V DC/30 V AC; insulation rated for 120 V AC basic insulation: between the channels and the supply voltage L+; between the channels and the backplane bus; between the channels | |||
between S- and MANA (UCM) | 8 V DC | 8 V DC | ||
Isolation | ||||
Isolation tested with | 707 V DC (type test) | 707 V DC (type test) | 2 000 V DC between the channels and the supply voltage L+; 2 000 V DC between the channels and the backplane bus; 2 000 V DC between the channels; 707 V DC (type test) between the supply voltage L+ and the backplane bus | |
Standards, approvals, certificates | ||||
Suitable for safety-related tripping of standard modules | Yes; From FS05 | Yes; from FS04 | Yes; From FS03 | |
Highest safety class achievable for safety-related tripping of standard modules | ||||
● Performance level according to ISO 13849-1 | PL d | PL d | PL d | |
● Category according to ISO 13849-1 | Cat. 3 | Cat. 3 | Cat. 3 | |
● SIL acc. to IEC 62061 | SIL 2 | SIL 2 | SIL 2 | |
● SILCL according to IEC 62061 | ||||
● remark on safety-oriented shutdown | https://support.industry.siemens.com/cs/de/de/view/39198632 | |||
Ambient conditions | ||||
Ambient temperature during operation | ||||
● horizontal installation, min. | -30 °C; From FS06 | -30 °C; From FS03 | -25 °C; From FS02 | |
● horizontal installation, max. | 60 °C | 60 °C | 60 °C | |
● vertical installation, min. | -30 °C; From FS06 | -30 °C; From FS03 | -25 °C; From FS02 | |
● vertical installation, max. | 40 °C | 40 °C | 40 °C | |
Altitude during operation relating to sea level | ||||
● Installation altitude above sea level, max. | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual | ||
Dimensions | ||||
Width | 35 mm | 35 mm | 35 mm | |
Height | 147 mm | 147 mm | 147 mm | |
Depth | 129 mm | 129 mm | 129 mm | |
Weights | ||||
Weight, approx. | 310 g | 325 g | 300 g | |
Other | ||||
Note: |
Weight | N/A |
---|---|
Dimensions | N/A |