The FM 455 closed-loop control module is the intelligent 16-channel closed-loop control module for universal closed-loop control tasks.
Siemens Function Modules SIMATIC S7-400 Product Specifications:
Article number | 6ES7455-1VS00-0AE0 |
SIMATIC S7-400, CONTROL MODULE | |
Supply voltage | |
Load voltage L+ | |
● Rated value (DC) | 24 V |
● permissible range, lower limit (DC) | 20.4 V |
● permissible range, upper limit (DC) | 28.8 V |
Input current | |
from load voltage L+ (without load), max. | 400 mA; typ. 330 mA |
Power loss | |
Power loss, typ. | 10.7 W |
Power loss, max. | 16.2 W |
Digital inputs | |
Number of digital inputs | 16 |
Input characteristic curve in accordance with IEC 61131, type 2 | Yes |
Input voltage | |
● Rated value (DC) | 24 V |
● for signal “0” | -3 to +5V |
● for signal “1” | 13 to 30V |
Input current | |
● for signal “1”, typ. | 7 mA |
Cable length | |
● shielded, max. | 1 000 m |
● unshielded, max. | 600 m |
Digital outputs | |
Number of digital outputs | 32 |
Short-circuit protection | Yes; Electronic |
Limitation of inductive shutdown voltage to | L+ (-1.5 V) |
Controlling a digital input | Yes |
Switching capacity of the outputs | |
● on lamp load, max. | 5 W |
Load resistance range | |
● lower limit | 240 Ω |
● upper limit | 4 kΩ |
Output voltage | |
● for signal “1”, min. | L+ (-2.5 V) |
Output current | |
● for signal “1” rated value | 0.1 A |
● for signal “1” permissible range for 0 to 60 °C, min. | 5 mA |
● for signal “1” permissible range for 0 to 60 °C, max. | 150 mA |
● for signal “0” residual current, max. | 0.5 mA |
Parallel switching of two outputs | |
● for logic links | Yes |
Switching frequency | |
● with resistive load, max. | 100 Hz |
● with inductive load, max. | 0.5 Hz |
● on lamp load, max. | 100 Hz |
Cable length | |
● shielded, max. | 1 000 m |
● unshielded, max. | 600 m |
Analog inputs | |
Number of analog inputs | 16; With thermocouples or 2-wire connection; 8 with Pt 100 or 4-wire connection |
permissible input voltage for voltage input (destruction limit), max. | 20 V |
permissible input current for current input (destruction limit), max. | 40 mA |
Input ranges | |
● Voltage | Yes |
● Current | Yes |
● Thermocouple | Yes |
● Resistance thermometer | Yes |
Input ranges (rated values), voltages | |
● 0 to +10 V | Yes |
— Input resistance (0 to 10 V) | 100 kΩ |
● -1.75 V to +11.75 V | Yes |
— Input resistance (-1.75 V to +11.75 V) | 100 kΩ |
● -80 mV to +80 mV | Yes |
— Input resistance (-80 mV to +80 mV) | 10 MΩ |
Input ranges (rated values), currents | |
● 0 to 20 mA | Yes |
— Input resistance (0 to 20 mA) | 50 Ω |
● 0 to 23.5 mA | Yes |
— Input resistance (0 to 23.5 mA) | 50 Ω |
● -3.5 mA to +23.5 mA | Yes |
— Input resistance (-3.5 mA to +23.5 mA) | 50 Ω |
● 4 mA to 20 mA | Yes |
— Input resistance (4 mA to 20 mA) | 50 Ω |
Input ranges (rated values), thermocouples | |
● Type B | Yes |
— Input resistance (Type B) | 10 MΩ |
● Type J | Yes |
— Input resistance (type J) | 10 MΩ |
● Type K | Yes |
— Input resistance (Type K) | 10 MΩ |
● Type R | Yes |
— Input resistance (Type R) | 10 MΩ |
● Type S | Yes |
— Input resistance (Type S) | 10 MΩ |
Input ranges (rated values), resistance thermometer | |
● Pt 100 | Yes |
— Input resistance (Pt 100) | 10 MΩ |
Thermocouple (TC) | |
Temperature compensation | |
— internal temperature compensation | Yes; Parameterizable |
— external temperature compensation with Pt100 | Yes; Parameterizable |
Characteristic linearization | |
● parameterizable | Yes |
— for thermocouples | Type B, J, K, R, S |
— for resistance thermometer | Pt100 (standard) |
Cable length | |
● shielded, max. | 200 m; 50 m at 80 mV and thermocouples |
Analog outputs | |
Number of analog outputs | |
Voltage output, short-circuit protection | |
Voltage output, short-circuit current, max. | |
Current output, no-load voltage, max. | |
Output ranges, voltage | |
● 0 to 10 V | |
● -10 V to +10 V | |
Output ranges, current | |
● 0 to 20 mA | |
● -20 mA to +20 mA | |
● 4 mA to 20 mA | |
Connection of actuators | |
● for voltage output two-wire connection | |
● for current output two-wire connection | |
Load impedance (in rated range of output) | |
● with voltage outputs, min. | |
● with voltage outputs, capacitive load, max. | |
● with current outputs, max. | |
● with current outputs, inductive load, max. | |
Cable length | |
● shielded, max. | |
Analog value generation for the inputs | |
Integration and conversion time/resolution per channel | |
● Resolution with overrange (bit including sign), max. | 14 bit; 12 bit or 14 bit, parameterizable |
Analog value generation for the outputs | |
Settling time | |
● for resistive load | |
● for capacitive load | |
● for inductive load | |
Encoder | |
Connection of signal encoders | |
● for voltage measurement | Yes |
● for current measurement as 4-wire transducer | Yes |
Connectable encoders | |
● 2-wire sensor | Yes |
— permissible quiescent current (2-wire sensor), max. | 1.5 mA |
Errors/accuracies | |
Operational error limit in overall temperature range | |
● Voltage, relative to input range, (+/-) | ±0.6 to ±1% |
● Current, relative to input range, (+/-) | ±0.6 to ±1% |
● Resistance thermometer, relative to input range, (+/-) | ±0.6 to ±1% |
● Voltage, relative to output range, (+/-) | |
● Current, relative to output range, (+/-) | |
Basic error limit (operational limit at 25 °C) | |
● Voltage, relative to input range, (+/-) | ±0.4 to ±0.6 % |
● Current, relative to input range, (+/-) | ±0.4 to ±0.6 % |
● Resistance thermometer, relative to input range, (+/-) | ±0.4 to ±0.6 % |
● Voltage, relative to output range, (+/-) | |
● Current, relative to output range, (+/-) | |
Interrupts/diagnostics/status information | |
Substitute values connectable | Yes; Parameterizable |
Integrated Functions | |
Control technology | |
● Number of closed-loop controllers | 16; With thermocouples or 2-wire connection; 8 with Pt 100 or 4-wire connection |
Potential separation | |
Potential separation controller | |
● between the channels | No |
● between the channels and backplane bus | Yes; Optocoupler |
Isolation | |
Isolation tested with | 500 V DC |
connection method / header | |
required front connector | 2x 48-pin |
Dimensions | |
Width | 50 mm |
Height | 290 mm |
Depth | 210 mm |
Weights | |
Weight, approx. | 1 400 g |
Weight | 1.561 kg |
---|---|
Dimensions | 23.3 × 30.3 × 6.5 cm |
Related products
-
Select options This product has multiple variants. The options may be chosen on the product page Details
-
Select options This product has multiple variants. The options may be chosen on the product page Details
-
Select options This product has multiple variants. The options may be chosen on the product page Details
-
Select options This product has multiple variants. The options may be chosen on the product page Details
-
Select options This product has multiple variants. The options may be chosen on the product page Details