TRIO-PS-IP67/1AC/24DC/20 – 1039830 – Phoenix Contact Power Supply

$ 1,040.60

SKU: Phoenix Contact 1039830

Inosaki is one of the largest Phoenix Contact Distributors to provide terminal block, interface module, power supply and relay. And our best offer for terminal block types are Feed-through, Fuse Modular, Spring Cage, Double Level, and Multi-level, hence the series model references to  PT Series, ST Series, TB Series, UT Series, UK Series. In additional for power supply are QUINT Power, STEP Power, Trio Power, and UNO Power. Please email us for catalog: sales@inosaki.my

Dimensions

Width 151 mm
Height 304 mm
Depth 120 mm
Installation distance right/left 20 mm / 20 mm
Installation distance top/bottom 50 mm / 100 mm

Ambient conditions

Degree of protection IP67
Inflammability class in acc. with UL 94 (housing / terminal blocks) V0
Ambient temperature (operation) -25 °C … 85 °C (Derating >60°C: 2.5 %/K)
Ambient temperature (start-up type tested) -40 °C
Ambient temperature (storage/transport) -40 °C … 85 °C
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Climatic class 3K3 (in acc. with EN 60721)
Degree of pollution 4
Installation height ≤ 4000 m (> 2000 m, Derating: 10 %/1000 m)

Input data

Nominal input voltage range 100 V AC … 240 V AC
110 V DC … 250 V DC
Input voltage range 100 V AC … 240 V AC 10 %
110 V DC … 250 V DC 10 %
Dielectric strength maximum ≤ 300 V AC 15 s
AC frequency range 50 Hz … 60 Hz
Discharge current to PE < 3.5 mA
Current consumption 5.6 A (100 V AC)
2.4 A (240 V AC)
Nominal power consumption 36.8 W
Inrush current typ. 20 A (at 25 °C)
Mains buffering time typ. 10 ms (120 V AC)
typ. 15 ms (230 V AC)
Input fuse 10 A (internal (device protection))
Recommended breaker for input protection 10 A … 16 A (Characteristics B, C, D, K)
Type of protection Transient surge protection
Protective circuit/component Varistor

Output data

Nominal output voltage 24 V DC ±1 %
Nominal output current (IN) 20 A
Dynamic Boost (IDyn.Boost) 30 A (5 s)
Derating > 60 °C … 70 °C (2.5%/K)
Protection against overvoltage at the output (OVP) ≤ 30 V DC
Control deviation < 1 % (change in load, static 10 % … 90 %)
< 3 % (Dynamic load change 10 % … 90 %, 10 Hz)
< 0.1 % (change in input voltage ±10 %)
Residual ripple ≤ 30 mVPP
Output power 480 W
Typical response time < 1 s
Maximum power dissipation in no-load condition < 3 W (120 V AC)
< 2.5 W (230 V AC)
Power loss nominal load max. < 48 W (120 V AC)
< 36 W (230 V AC)

General

Article Number 1039830
Net weight 3.7 kg
Efficiency 91 % (100 V AC)
93 % (230 V AC)
MTBF (IEC 61709, SN 29500) > 1400000 h (25 °C)
> 800000 h (40 °C)
> 400000 h (60 °C)
Insulation voltage input/output 4 kV AC (type test)
1.5 kV AC (routine test)
Degree of protection IP67
Protection class I
Inflammability class in acc. with UL 94 (housing / terminal blocks) V0
Assembly instructions Alignable: 20 mm horizontally, 50 mm vertically above, 100 mm vertically below

Connection data, input

Connection method Circular connector
Type of locking M12 screw locking
Coding S-coded
Number of positions 3

Connection data, output

Connection method Circular connector
Type of locking M17 standard and SPEEDCON locking
Coding N-coded
Number of positions 4

Connection data for signaling

Connection method Circular connector
Type of locking SPEEDCON M12
Coding A-coded
Number of positions 5

Standards

Standard – Electrical safety IEC 61010-2-201 (SELV)
Standard – Safety extra-low voltage EN 60204-1 (PELV)
Standard – Safe isolation DIN VDE 0100-410
Standard – Limitation of mains harmonic currents EN 61000-3-2
Overvoltage category EN 61010-1 III (≤ 2000 m)
II (≤ 4000 m)

EMC data

Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
Conducted noise emission EN 55016
EN 61000-6-3 (Class B)
Noise emission EN 55016
EN 61000-6-3 (Class B)
Flicker EN 61000-3-3
Electrostatic discharge EN 61000-4-2
Contact discharge 6 kV (Test Level 4)
Discharge in air 8 kV (Test Level 4)
Electromagnetic HF field EN 61000-4-3
Frequency range 80 MHz … 1 GHz
Test field strength 10 V/m (Test Level 3)
Frequency range 1 GHz … 2 GHz
Test field strength 10 V/m (Test Level 3)
Frequency range 2 GHz … 3 GHz
Test field strength 10 V/m (Test Level 3)
Comments Criterion A
Fast transients (burst) EN 61000-4-4
Input 4 kV (Test Level 4 – asymmetrical)
Output 2 kV (Test Level 3 – asymmetrical)
Signal 2 kV (Test Level 2 – asymmetrical)
Comments Criterion A
Surge voltage load (surge) EN 61000-4-5
Input 3 kV (Test Level 3 – symmetrical)
4 kV (Test Level 4 – asymmetrical)
Output 1 kV (Test Level 2 – symmetrical)
2 kV (Test Level 1 – asymmetrical)
Signal 1 kV (Test Level 2 – asymmetrical)
Comments Criterion B
Conducted interference EN 61000-4-6
Frequency range 0.15 MHz … 80 MHz
Voltage 10 V (Test Level 3)
Comments Criterion A
Voltage dips EN 61000-4-11
Voltage 230 V AC
Frequency 50 Hz
Voltage dip 70 %
Number of periods 25 periods
Additional text Test Level 2
Comments Criterion A
Voltage dip 40 %
Number of periods 10 periods
Additional text Test Level 2
Comments Criterion B
Voltage dip 0 %
Number of periods 1 period
Additional text Test Level 2
Comments Criterion B
Criterion A Normal operating behavior within the specified limits.
Criterion B Temporary impairment to operational behavior that is corrected by the device itself.
Criterion C Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.

Environmental Product Compliance

REACh SVHC Lead 7439-92-1