Sensors used in the automation industry transmit a wide range of digital and analog signals. In many counting and control processes, these signals need to be clearly displayed, monitored, or processed. To help you find the perfect solution for such applications, we offer a wide range of counters, process displays, signal converters, and switch amplifiers that are all optimized for use with our sensors. The user-friendliness and durability of our products is always a priority at Pepperl+Fuchs.

Functional safety related parameters
MTTFd 100 a
Supply
Rated voltage 200 … 230 V AC ; 100 … 130 V AC; 50/60 Hz
20 VDC … 30 VDC
Fusing external fusing 4 A
Power consumption AC: < 5 VA
DC: < 5 W
Input 1
Connection terminals 8-, 9+
Connectable sensor types NAMUR sensors according to DIN EN 60947-5-6
Open loop voltage 8.2 V DC
Short-circuit current 6.5 mA
Switching point 1.2 … 2.1 mA Switching hysteresis approx. 0.2 mA
Input frequency 0.002 … 10000 Hz, pulse length/duration: ≥ 20µs
Impedance 1.2 kΩ
Input 2
Switching point high: 16 … 30 V DC; max.10 mA due to integrated constant current sink; R≅ 3 kΩ
low: 0 … 6 V DC
Input frequency 0.002 … 40000 Hz, pulse length/duration: ≥ 12µs
Connection terminals 7+, 13- sensor supply
terminals 14, 15 NPN/PNP input (galvanically isolated)
Connectable sensor types Two, three, or four-wire proximity switch, incremental rotary encoder, or externally generated pulses 16 … 30 V
Sensor supply 19 … 28 V DC non-stabilised; ≤ 30 mA short-circuit protected
Input 3
Start-up override Triggering by external signal 16 … 30 V or Place jumper between terminals 2/3 or by switching on supply voltage (terminal 2 and terminal 3 permanently bridged)
Hold-up time 0.1 … 999.9 s (External trigger signal)
Output
Relay 1 changeover contact
NO, NC, COM
Sensor supply 24 V DC ± 10 %, 30 mA , short-circuit protected
Contact loading 250 V AC/2 A/ cos φ ≥ 0.7
40 V DC/2 A
Delay ≤ 20 ms (incl. calculation time)
Mechanical life ≥ 30.000.000 switching cycles
Transfer characteristics
Changing interval 5 ms (Internal processing time)
Time delay before availability ≤ 400 ms
Measuring error 0 … 40000 Hz: ≤ ±0,10%
Display: ±1 digit
Timer function ON-delay, OFF-delay, one shot, pulse extension
Time 0 … 999.9 s ; mode of operation reversible
Standard conformity
Electromagnetic compatibility acc. to EN 50081-2 / EN 50082-2
Ambient conditions
Ambient temperature -25 … 40 °C (-13 … 104 °F)
Storage temperature -40 … 85 °C (-40 … 185 °F)
Relative humidity max. 80 %, not condensing
Altitude 0 … 2000 m
Operating conditions The device has only to be used in an indoor area.
Mechanical specifications
Connection assembly Caution: Please be aware that the device may only be connected to a switchable power supply. The switch or circuit breaker must be easy to reach and identified as the separator for the device.
Degree of protection IP20
Connection coded, removable terminals , max. core cross section 0.34 … 2.5 mm2
Construction type modular terminal housing in Makrolon, System KF
For use in the switch cabinet/switch cabinet module
Mounting snap-on to 35 mm standard rail or screw fixing