W9 – WL9G-3N1132P06 Photoelectric Sensors – Small Photoelectric Sensors – SICK Sensor

USD $ 200.13

SKU: N/A

SICK sensor one of the world’s leading producers of sensors and sensor solutions for industrial applications. SICK is a technology and market leader in Factory and Logistics Automation as well as Process Automation. The sensor range are: Laser Sensors, Cylinder Sensors, Photoelectric Sensors, Fork Sensors, Encoders, Color Sensors, Distance Sensor, Contrast Sensor, Color Sensor, Inductive Proximity Sensors, Fiber Optic Sensor with our signature range sick sensor intelligence.

Part Number: 1061788
Photoelectric Sensor Model: WL9G-3N1132P06
OEM Spec Ref 

Features

Device type Photoelectric sensors
Sensor/ detection principle Photoelectric retro-reflective sensor, autocollimation
Dimensions (W x H x D) 12.2 mm x 50 mm x 23.6 mm
Housing design (light emission) Rectangular
Mounting hole M3
Sensing range max. 0 m … 5 m 1)
Sensing range 0 m … 3 m 1)
Type of light Visible red light
Light source PinPoint LED 2)
Light spot size (distance) Ø 45 mm (1.5 m)
Wave length 650 nm
Adjustment Single teach-in button
AutoAdapt
Special applications Detecting transparent objects
  • 1) Reflector PL80A.
  • 2) Average service life: 100,000 h at TU = +25 °C.

 

Mechanics/electronics

Supply voltage 10 V DC … 30 V DC 1)
Ripple < 5 Vpp 2)
Current consumption 20 mA 3)
Switching output NPN 4)
Output function Complementary
Switching mode Light/dark switching 4)
Output current Imax. ≤ 100 mA 5)
Response time < 0.5 ms 6)
Switching frequency 1,000 Hz 7)
Connection type Cable, 4-wire, 2 m 8)
Cable material PVC
Conductor cross-section 0.14 mm²
Circuit protection 9)

10)

11)

Protection class III
Weight 80 g
Polarisation filter
Special device
Housing material Plastic, VISTAL®
Optics material Plastic, PMMA
Enclosure rating IP66

IP67

IP69K

Items supplied Reflector P250F, mounting bracket BEF-WN-W9-2
Special feature Detecting transparent objects
Ambient operating temperature –40 °C … +60 °C
Ambient temperature, storage –40 °C … +75 °C
UL File No. NRKH.E181493
  • 1) Limit values when operated in short-circuit protected network: max. 8 A.
  • 2) May not exceed or fall below Uv tolerances.
  • 3) Without load.
  • 4) Q = light switching.
  • 5) At and above Tu 50 °C, a max. load current of Imax. = 50 mA is permitted.
  • 6) Signal transit time with resistive load.
  • 7) With light/dark ratio 1:1.
  • 8) Do not bend below 0 °C.
  • 9) A = VS connections reverse-polarity protected.
  • 10) B = inputs and output reverse-polarity protected.
  • 11) C = interference suppression.