PBS2-RB010SG2SS0LMA0Z – Pressure Sensors – SICK Sensor
$ 405.26
SICK sensor one of the world’s leading producers of sensors and sensor solutions for industrial applications. SICK is a technology and market leader in Factory and Logistics Automation as well as Process Automation. The sensor range are: Laser Sensors, Cylinder Sensors, Photoelectric Sensors, Fork Sensors, Encoders, Color Sensors, Distance Sensor, Contrast Sensor, Color Sensor, Inductive Proximity Sensors, Fiber Optic Sensor with our signature range sick sensor intelligence.
Part Number: 6073475
Mounting systems: PBS2-RB010SG2SS0LMA0Z
OEM Spec Ref
Features
Medium | Liquid, gaseous |
Pressure type | Gauge pressure |
Pressure unit | bar |
Measuring range | 0 bar … 10 bar, 0 psi … 145 psi |
Process temperature | –20 °C … +85 °C |
Zero point adjustment | Max. + 3 % of span |
Output signal | IO-Link/PNP/NPN + PNP/NPN |
Rotatable housing | Display against housing with electrical connection: 330 °
Housing against process connection: 320 ° |
Display | 14-Segment LED, red, 4-digit, character height 9 mm, can be rotated electronically by 180°
Update: 1,000, 500, 200, 100 ms (adjustable) |
Mechanics/electronics
Process connection | G ¼ female |
Wetted parts | Pressure connection: stainless steel 316L
Pressure sensor: stainless steel 316L (for measurement ranges from 0 bar … 10 bar rel stainless steel 13-8 PH) |
Internal transmission fluid | Silicone oil (only with pressure ranges < 0 bar … 10 bar and ≤ 0 bar abs … 25 bar abs) |
Pressure port | 3.5 mm, Standard |
Housing material | Lower body: stainless steel 304, Plastic head: PC + ABS, Buttons: TPE-E, Display window: PC |
Connection type | Round connector M12 x 1, 4-pin, IP67 |
Supply voltage | 15 V DC … 35 V DC |
Power consumption | 45 mA (for configurations without analog output signal)
70 mA (for configurations with analog output signal) |
Total current consumption | Max. 600 mA (including switching current) |
Electrical safety | Protection class: III
Overvoltage protection: 40 V DC Short-circuit protection: QA, Q1, Q2 towards M Reverse polarity protection: L+ to M |
Isolation voltage | 500 V DC |
CE-conformity | EMC Directive: 2014/30 / EU (EN 61326-1:2013; EN 61326-2-3:2013), Pressure equipment directive: 2014/68 / EU, Hazardous materials (RoHS): 2011/65 / EU (EN 50581:2012) |
Weight sensor | Approx. 220 g |
Seal | Without seal |
Enclosure rating | IP67 / IP67 |
Protection class III | ✔ |
MTTF | 104 years |
Performance
Non-linearity | ≤ ± 0.25 %, of span (Best Fit Straight Line, BFSL) according to IEC 61298-2 |
Accuracy | ≤ ± 0.5 % of the span |
Setting accuracy of switching outputs | ≤ ± 0.5 % of span |
Response time | ≤ 5 ms |
Long-term drift/one-year stability | ≤ ± 0.1 % of the span according to IEC 61298-2
≤ 0.2 % of the span According to IEC 61298-2 for measuring range ≤ 0.6 bar or flush-mounted membrane (0 psi … 10 psi) |
Temperature coefficient in rated temperature range | Average TC of the zero point: ≤± 0.16% of the span / 10 K, Average TC of the span ≤± 0.16% of the span / 10 K |
Rated temperature range | 0 °C … +80 °C |
Service life | Minimum 100 Mio. life cycles |
Ambient Data
Ambient temperature | –20 °C … +80 °C |
Storage temperature | –20 °C … +70 °C |
Relative humidity | ≤ 75 % |
Shock load | 50 g, 6 ms according to IEC 60068-2-27 (mechanical shock) |
Vibration load | 20 g, 10 Hz … 2,000 Hz (IEC 60068-2-6, at resonance) |
Weight | 0.34 kg |
---|---|