| Item number | 2718206 |
| Packing unit | 50 pc |
| Minimum order quantity | 1 pc |
| Product key | BE1218 |
| Catalog page | Page 487 (C-1-2019) |
| GTIN | 4017918062279 |
| Weight per piece (including packing) | 27.155 g |
| Weight per piece (excluding packing) | 27.15 g |
| Customs tariff number | 85369010 |
| Country of origin | PL |
| Product type | Motor terminal block |
| Number of connections | 7 |
| Number of rows | 4 |
| Potentials | 4 |
| Insulation characteristics | |
| Overvoltage category | III |
| Degree of pollution | 3 |
| Rated surge voltage | 6 kV |
| Maximum power dissipation for nominal condition | 0.77 W |
| Number of connections per level | 2 |
| Nominal cross section | 2.5 mm² |
| 2nd, 3rd and 4th level | |
| Screw thread | M3 |
| Note | Please observe the current carrying capacity of the DIN rails. |
| Tightening torque | 0.5 … 0.6 Nm |
| Stripping length | 8 mm |
| Internal cylindrical gage | A3 |
| Connection in acc. with standard | IEC 60947-7-1/IEC 60947-7-2 |
| Conductor cross section rigid | 0.2 mm² … 4 mm² |
| Cross section AWG | 24 … 12 (converted acc. to IEC) |
| Conductor cross section flexible | 0.2 mm² … 2.5 mm² |
| Conductor cross section, flexible [AWG] | 24 … 14 (converted acc. to IEC) |
| Conductor cross-section flexible (ferrule without plastic sleeve) | 0.25 mm² … 2.5 mm² |
| Flexible conductor cross section (ferrule with plastic sleeve) | 0.25 mm² … 2.5 mm² |
| Cross-section with insertion bridge, rigid | 4 mm² |
| Cross-section with insertion bridge, flexible | 2.5 mm² |
| Nominal current | 24 A |
| Maximum load current | 26 A (with a 2.5 mm² conductor cross section) |
| Nominal voltage | 400 V (when using EB insertion bridges, the nominal voltage is reduced to 250 V.) |
| Nominal cross section | 2.5 mm² |
| Rated data (ATEX/IECEx) | |
| Identification | II 2 G Ex eb IIC Gb |
| Operating temperature range | -50 °C … 105 °C |
| Ex-certified accessories | 1205053 SZS 0,6X3,5 |
| 1201442 E/UK | |
| List of bridges | Insertion bridge / EB 2- DIK GY / 2715898 |
| Insertion bridge / EB 2- DIK RD / 2716693 | |
| Insertion bridge / EB 2- DIK BU / 2716648 | |
| Insertion bridge / EB 3- DIK GY / 2715908 | |
| Insertion bridge / EB 3- DIK RD / 2716745 | |
| Insertion bridge / EB 3- DIK BU / 2716651 | |
| Insertion bridge / EB 10- DIK GY / 2715937 | |
| Insertion bridge / EB 10- DIK RD / 2716774 | |
| Insertion bridge / EB 10- DIK BU / 2716680 | |
| Bridge data | 16 A / 2.5 mm² ΔT 45 K |
| Ex temperature increase | 37 K (20 A / 2.5 mm²) |
| at bridging with insertion bridge | 176 V |
| Rated insulation voltage | 160 V |
| output | (Permanent) |
| Ex level General | |
| Rated voltage | 176 V |
| Rated current | 20 A (ΔT 45 K) |
| Maximum load current | 25 A (ΔT 45 K) |
| Ex connection data General | |
| Torque range | 0.5 Nm … 0.6 Nm |
| Nominal cross section | 2.5 mm² |
| Rated cross section AWG | 14 |
| Connection capacity rigid | 0.2 mm² … 4 mm² |
| Connection capacity AWG | 24 … 12 |
| Connection capacity flexible | 0.2 mm² … 2.5 mm² |
| Connection capacity AWG | 24 … 14 |
| 2 conductors with same cross section, solid | 0.2 mm² … 1 mm² |
| 2 conductors with the same cross-section AWG rigid | 24 … 17 |
| 2 conductors with same cross section, stranded | 0.2 mm² … 1 mm² |
| 2 conductors with the same cross-section AWG flexible | 24 … 17 |
| output | (Permanent) |
| Ex level Level 1 | |
| Contact resistance | 0.8 mΩ |
| output | (Permanent) |
| Ex level Level 2 | |
| Contact resistance | 0.6 mΩ |
| output | (Permanent) |
| Ex level Level 3 | |
| Contact resistance | 0.5 mΩ |
| Surge voltage test | |
| Test voltage setpoint | 7.3 kV |
| Result | Test passed |
| Temperature-rise test | |
| Requirement temperature-rise test | Increase in temperature ≤ 45 K |
| Result | Test passed |
| Short-time withstand current 2.5 mm² | 0.3 kA |
| Short-time withstand current 4 mm² | 0.48 kA |
| Result | Test passed |
| Power-frequency withstand voltage | |
| Test voltage setpoint | 1.89 kV |
| Result | Test passed |
| Width | 6.2 mm |
| Height | 82.5 mm |
| Depth on NS 35/7,5 | 70 mm |
| Depth on NS 35/15 | 77.5 mm |
| Color | gray (RAL 7042) |
| Flammability rating according to UL 94 | V2 |
| Insulating material group | I |
| Insulating material | PA |
| Static insulating material application in cold | -40 °C |
| Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) | 125 °C |
| Relative insulation material temperature index (Elec., UL 746 B) | 125 °C |
| Mechanical data | |
| Open side panel | No |
| Mechanical strength | |
| Result | Test passed |
| Attachment on the carrier | |
| DIN rail/fixing support | NS 35 |
| Test force setpoint | 1 N |
| Result | Test passed |
| Test for conductor damage and slackening | |
| Rotation speed | 10 rpm |
| Revolutions | 135 |
| Conductor cross section/weight | 0.2 mm² / 0.2 kg |
| 2.5 mm² / 0.7 kg | |
| 4 mm² / 0.9 kg | |
| Result | Test passed |
| Test for conductor damage and slackening | |
| Rotation speed | 10 rpm |
| Revolutions | 135 |
| Conductor cross section/weight | 0.2 mm² / 0.2 kg |
| 2.5 mm² / 0.7 kg | |
| 4 mm² / 0.9 kg | |
| Result | Test passed |
| Test for conductor damage and slackening | |
| Rotation speed | 10 rpm |
| Revolutions | 135 |
| Conductor cross section/weight | 0.2 mm² / 0.2 kg |
| 2.5 mm² / 0.7 kg | |
| 4 mm² / 0.9 kg | |
| Result | Test passed |
| Needle-flame test | |
| Time of exposure | 30 s |
| Result | Test passed |
| Ambient conditions | |
| Ambient temperature (operation) | -60 °C … 110 °C (Operating temperature range incl. self-heating; for max. short-term operating temperature, see RTI Elec.) |
| Ambient temperature (storage/transport) | -25 °C … 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C) |
| Ambient temperature (assembly) | -5 °C … 70 °C |
| Ambient temperature (actuation) | -5 °C … 70 °C |
| Permissible humidity (operation) | 20 % … 90 % |
| Permissible humidity (storage/transport) | 30 % … 70 % |
| Connection in acc. with standard | IEC 60947-7-1/IEC 60947-7-2 |
| Mounting type | NS 35/7,5 |
| NS 35/15 |