Contact Us:
sales@inosaki.com

Upper Communication Unit for Digital Sensors – Panasonic Fiber Optic Sensor

$ 321.42

Features

  • Control and settings can be carried out remotely
  • High general applicability so that any type of PLC can be used
  • Communication speed 57.6 kbps Series connection of a maximum of 31 nodes is possible
  • Up to 16 digital sensors* can be connected side by side
  • Save wiring, construction and space

* The maximum number of units is 12 for configurations including either the FX-501(P)/502(P) or LS-501(P).

 

Specifications

Type Main unit
Model No. SC-GU1-485
CE marking directive compliance EMC Directive, RoHS Directive
Applicable digital sensor / input unit FX-501(P), FX-502(P), FX-301(P) (Note 2), FX-305(P), LS-501(P), LS-403, DPS-401(P), DPS-402(P), SC-A01, SC-A02, SC-T1JA
Connectable units Max. 16 units of digital sensor / analog input unit per SC-GU1-485 (Note 3)
Connectable nodes Max. 31 nodes
Supply voltage 24 V DC ±10 % Ripple P-P 10 % or less
Current consumption 45 mA or less (SC-GU1-EU: 10 mA or less)
Communication method Two-wire half duplex communication
Communication speed 57,600 bps / 38,400 bps / 19,200 bps / 9,600 bps, Selectable by DIP switch
Synchronization method Asynchronous communication method
Electrical characteristic Conforming to EIA RS-485
Total extension length Communication cable: 100 m 328.084 ft or less [SC-GU1-485 (termination) to PLC]
Power supply cable: Less than 10 m 32.808 ft
Indicators Power
(POWER)
Green LED (Lights up when the power is ON)
Communication
(COMM)
Green LED (Lights up during communication)
Upper communication error
(C.Err)
Red LED
[Blinks when communication error between PLC (Programmable Logic Controller) and Master or Master and Slave, or command error occurs]
Lower communication error
(S.Err)
Red LED (Blinks when communication error between the main unit and sensors occur)
Ambient temperature –10 to +55 ℃ +14 to +131 ℉
(If 4 to 7 units are connected in cascade: –10 to +50 ℃ +14 to +122 ℉, if 8 to 16 units are connected in cascade: –10 to +45 ℃ +14 to +113 ℉)
(No dew condensation or icing allowed),
Storage: –20 to +70 ℃ –4 to +158 ℉
Ambient humidity 35 to 85 % RH, Storage: 35 to 85 % RH
Voltage withstandability 1,000 V AC for one min. between all supply terminals connected together and enclosure
Insulation resistance 20 MΩ, or more, with 250 V DC megger between all supply terminals connected together and enclosure
Vibration resistance 10 to 150 Hz frequency, 0.75 mm 0.030 in double amplitude in X, Y and Z directions for two hours each
Shock resistance 98 m/s2 acceleration (10 G approx.) in X, Y and Z directions five times each
Material Enclosure: Heat-resistant ABS, Connector cap: silicone rubber
Weight Net weight : 35 g approx. (SC-GU1-EU: 10 g approx.), Gross weight: 120 g approx.
Accessories SC-GU1-EU (End unit): 1 pc.
CN-73-C2 [Quick-connection cable (cable length 2 m 6.562 ft)]: 1 pc.
SC-GU1-CC02 [Link cable (cable length 0.2 m 0.656 ft)]: 1 pc.
Notes: 1) Where measurement conditions have not been specified precisely, the conditions used were an ambient temperature of +20℃ +68℉
2) Applicable units are for the FX-301(P) after version update. Do not use the previous version of FX-301(P). The updated version of FX-301(P) has the“NAVI” printed only on single side.
3) The maximum number of units is 12 for configurations including either the FX-501(P)/502(P) or LS-501(P).

Additional information

Related Products

M10
PEPPERLFUCHS_Inductive Sensors_NCB2-12GM35-N0-V1_1
THK_Linear Bushing_LME
Festo_Flow control valves_GRE-14_10352
M3
Festo_Pneumatic fittings_QSY-G1-2-12_186188
Select your currency