Contact Us:
sales@inosaki.com

UNO-PS/1AC/15DC/30W – 2903000 – Phoenix Contact Power Supply

$ 94.60

SKU Phoenix Contact 2903000 Category

Inosaki – Your Trusted Phoenix Contact Distributor
Inosaki proudly stands as one of the largest distributors of Phoenix Contact products, offering a comprehensive range of terminal blocks, interface modules, power supplies, and relays.

Our Best-Selling Terminal Blocks: Feed-Through, Fuse Modular, Spring Cage, Double Level, Multi-Level

Series Models: PT Series, ST Series, TB Series, UT Series, and UK Series, PTV Series, UKH Series, Micro Series.

Reliable Power Supply Solutions

Discover industry-leading Phoenix Contact power supplies, such as:

  • QUINT Power – Premium performance for critical systems
  • STEP Power – Compact design for space-saving applications
  • Trio Power – Rugged and reliable for industrial needs
  • UNO Power – Cost-effective and efficient

Get Your Phoenix Contact Catalog Today
Need detailed product information? Contact us at sales@inosaki.com to request your Phoenix Contact catalog.

Product Description

UNO POWER power supplies with basic functionality
Thanks to their high power density, compact UNO POWER power supplies are the ideal solution for loads up to 240 W, particularly in compact control boxes. The power supply units are available in various performance classes and overall widths. Their high degree of efficiency and low idling losses ensure a high level of energy efficiency.

Dimensions

Width 22.5 mm
Height 90 mm
Depth 84 mm
Installation distance right/left 0 mm / 0 mm
Installation distance top/bottom 30 mm / 30 mm

 

Ambient conditions

Degree of protection IP20
Inflammability class in acc. with UL 94 (housing / terminal blocks) V0
Ambient temperature (operation) -25 °C … 70 °C (> 55 °C Derating: 2.5 %/K)
Ambient temperature (storage/transport) -40 °C … 85 °C
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Climatic class 3K3 (in acc. with EN 60721)
Degree of pollution 2

 

Input data

Nominal input voltage range 100 V AC … 240 V AC
Input voltage range 85 V AC … 264 V AC
Frequency range (fN) 50 Hz … 60 Hz 10 %
Current consumption typ. 0.8 A (100 V AC)
typ. 0.4 A (240 V AC)
Nominal power consumption 70.8 VA
Inrush current < 30 A (typ.)
Mains buffering time > 20 ms (120 V AC)
> 115 ms (230 V AC)
Input fuse 2 A (slow-blow, internal)
Recommended breaker for input protection 6 A … 16 A (Characteristics B, C, D, K)
Power factor (cos phi) 0.49
Type of protection Transient surge protection
Protective circuit/component Varistor

 

 

Output data

Nominal output voltage 15 V DC ±1 %
Nominal output current (IN) 2 A (-25 °C … 55 °C)
Derating 55 °C … 70 °C (2.5%/K)
Connection in parallel yes, for redundancy and increased capacity
Connection in series yes
Feedback voltage resistance < 25 V DC
Protection against overvoltage at the output (OVP) ≤ 25 V DC
Control deviation < 1 % (change in load, static 10 % … 90 %)
< 3 % (Dynamic load change 10 % … 90 %, 10 Hz)
< 0.1 % (change in input voltage ±10 %)
Residual ripple < 40 mVPP (with nominal values)
Output power 30 W
Typical response time < 1 s
Maximum power dissipation in no-load condition < 0.3 W
Power loss nominal load max. < 4.6 W

 

General

Article Number 2903000
Net weight 0.15 kg
Efficiency typ. 85 % (120 V AC)
typ. 86 % (230 V AC)
MTBF (IEC 61709, SN 29500) > 911000 h (40 °C)
Insulation voltage input/output 4 kV AC (type test)
3 kV AC (routine test)
Degree of protection IP20
Protection class II (in closed control cabinet)
Inflammability class in acc. with UL 94 (housing / terminal blocks) V0
Housing material Polycarbonate
Foot latch material POM (Polyoxymethylene)
Mounting position horizontal DIN rail NS 35, EN 60715
Assembly instructions alignable: 0 mm horizontally, 30 mm vertically

 

Connection data, input

Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 14
Stripping length 8 mm
Screw thread M3

 

Connection data, output

Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 14
Stripping length 8 mm
Screw thread M3

 

Standards

EMC requirements for noise immunity EN 61000-6-1
EN 61000-6-2
EMC requirements for noise emission EN 61000-6-3
EN 61000-6-4
Standard – Safety of transformers EN 61558-2-16
Standard – Electrical safety IEC 62368-1 (SELV)
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations EN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltage IEC 62368-1 (SELV) und EN 60204-1 (PELV)
Standard – Safe isolation DIN VDE 0100-410
Standard – Limitation of mains harmonic currents EN 61000-3-2
Mains variation/undervoltage EN 61000-4-11

 

Conformance/approvals

UL approvals UL/C-UL listed UL 508
UL/C-UL Listed ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location)
UL/C-UL Recognized UL 60950-1
CSA CAN/CSA-C22.2 No. 60950-1-07
CSA-C22.2 No. 107.1-01
CAN/CSA-C22.2 No. 213 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location)

 

EMC data

Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
Electrostatic discharge EN 61000-4-2
Contact discharge 6 kV (Test Level 3)
Discharge in air 8 kV (Test Level 3)
Electromagnetic HF field EN 61000-4-3
Frequency range 80 MHz … 1 GHz
Test field strength 10 V/m (Test Level 3)
Frequency range 1 GHz … 6 GHz
Test field strength 10 V/m (Test Level 3)
Comments Criterion A
Fast transients (burst) EN 61000-4-4
Input 4 kV (Test Level 4 – asymmetrical)
Output 2 kV (Test Level 3 – asymmetrical)
Comments Criterion B
Surge voltage load (surge) EN 61000-4-5
Input 2 kV (Test Level 3 – symmetrical)
4 kV (Test Level 4 – asymmetrical)
Output 1 kV (Test Level 2 – symmetrical)
2 kV (Test Level 3 – asymmetrical)
Comments Criterion B
Conducted interference EN 61000-4-6
Frequency range 10 kHz … 80 MHz
Voltage 10 V (Test Level 3)
Comments Criterion A
Voltage dips EN 61000-4-11
Criterion A Normal operating behavior within the specified limits.
Criterion B Temporary impairment to operational behavior that is corrected by the device itself.

Additional information

Related Products

Mitutoyo_Inside Micrometers_337-302
Panasonic_Sensor Supporting Bracket
Omron_Other Units_CJ1W-II101
GX-H15A
Festo_Directional control valves_VUVG-L14-T32C-MH-G18-1P3_564212 05
FT02-150
Select your currency