High-current terminal block, nom. voltage: 1000 V, nominal current: 192 A, connection method: Screw connection, number of connections: 2, number of positions: 1, cross section: 16 mm² – 95 mm², AWG: 4 – 3/0, width: 20.3 mm, height: 78.3 mm, color: gray, mounting type: NS 35/7,5, NS 35/15, NS 35/15-2,3, NS 32
| Article Number | 3213140 |
|---|---|
| Number of positions | 1 |
| Number of levels | 1 |
| Number of connections | 2 |
| Potentials | 1 |
| Nominal cross section | 70 mm² |
| Color | gray |
| Insulating material | PA |
| Flammability rating according to UL 94 | V0 |
| Area of application | Railway industry |
| Machine building | |
| Plant engineering | |
| Mounting type | NS 35/7,5 |
| Rated surge voltage | 8 kV |
| Degree of pollution | 3 |
| Overvoltage category | III |
| Insulating material group | I |
| Maximum load current | 192 A (with 70 mm² conductor cross section) |
| Nominal current IN | 192 A |
| Nominal voltage UN | 1000 V |
| Open side panel | No |
| Shock protection test specification | DIN EN 50274 (VDE 0660-514):2002-11 |
| Back of the hand protection | guaranteed |
| Note regarding shock protection | Finger-safe protection is not guaranteed if bridges are positioned. |
| Result of surge voltage test | Test passed |
| Result of power-frequency withstand voltage test | Test passed |
| Power frequency withstand voltage setpoint | 2.2 kV |
| Result of the test for mechanical stability of terminal points (5 x conductor connection) | Test passed |
| Result of flexion and pull-out test | Test passed |
| Bending test rotation speed | 10 rpm |
| Bending test turns | 135 |
| Bending test conductor cross section/weight | 25 mm² / 4.5 kg |
| 70 mm²/10.4 kg | |
| Tensile test result | Test passed |
| Conductor cross section tensile test | 25 mm² |
| Tractive force setpoint | 135 N |
| Conductor cross section tensile test | 70 mm² |
| Tractive force setpoint | 285 N |
| Conductor cross section tensile test | 95 mm² |
| Tractive force setpoint | 351 N |
| Result of tight fit on support | Test passed |
| Tight fit on carrier | NS 35/NS 32 |
| Setpoint | 10 N |
| Result of voltage-drop test | Test passed |
| Result of temperature-rise test | Test passed |
| Requirement temperature-rise test | Increase in temperature ≤ 45 K |
| Short circuit stability result | Test passed |
| Conductor cross section short circuit testing | 70 mm² |
| Short-time current | 8.4 kA |
| Result of thermal test | Test passed |
| Proof of thermal characteristics (needle flame) effective duration | 30 s |
| Oscillation, broadband noise test result | Test passed |
| Test specification, oscillation, broadband noise | DIN EN 50155 (VDE 0115-200):2008-03 |
| Test spectrum | Service life test category 1, class B, body mounted |
| Test frequency | f1 = 5 Hz to f2 = 150 Hz |
| ASD level | 1.857 (m/s²)²/Hz |
| Acceleration | 0.8g |
| Test duration per axis | 5 h |
| Test directions | X-, Y- and Z-axis |
| Shock test result | Test passed |
| Test specification, shock test | DIN EN 50155 (VDE 0115-200):2008-03 |
| Shock form | Half-sine |
| Acceleration | 5g |
| Shock duration | 30 ms |
| Number of shocks per direction | 3 |
| Test directions | X-, Y- and Z-axis |
| Relative insulation material temperature index (Elec., UL 746 B) | 130 °C |
| Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) | 130 °C |
| Static insulating material application in cold | -60 °C |
| Surface flammability NFPA 130 (ASTM E 162) | passed |
| Specific optical density of smoke NFPA 130 (ASTM E 662) | passed |
| Calorimetric heat release NFPA 130 (ASTM E 1354) | 28 MJ/kg |
| Smoke gas toxicity NFPA 130 (SMP 800C) | passed |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 – HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 – HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 – HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 – HL 3 |
| Width | 20.3 mm |
|---|---|
| Length | 70.5 mm |
| Height | 78.3 mm |
| Height NS 35/7,5 | 80 mm |
| Height NS 35/15 | 87.5 mm |
| Height NS 32 | 85 mm |
| Connection method | Screw connection |
|---|---|
| Screw thread | M8 |
| Stripping length | 24 mm |
| Tightening torque, min | 8 Nm |
| Tightening torque max | 10 Nm |
| Connection in acc. with standard | IEC 60947-7-1 |
| Note | Note: Product releases, connection cross sections and notes on connecting aluminum cables can be found in the download area. |
| Conductor cross section solid min. | 16 mm² |
| Conductor cross section solid max. | 95 mm² |
| Conductor cross section AWG min. | 4 |
| Conductor cross section AWG max. | 3/0 |
| Conductor cross section flexible min. | 25 mm² |
| Conductor cross section flexible max. | 70 mm² |
| Min. AWG conductor cross section, flexible | 3 |
| Max. AWG conductor cross section, flexible | 2/0 |
| Conductor cross section flexible, with ferrule without plastic sleeve min. | 16 mm² |
| Conductor cross section flexible, with ferrule without plastic sleeve max. | 70 mm² |
| Conductor cross section flexible, with ferrule with plastic sleeve min. | 16 mm² |
| Conductor cross section flexible, with ferrule with plastic sleeve max. | 70 mm² |
| 2 conductors with same cross section, solid min. | 16 mm² |
| 2 conductors with same cross section, solid max. | 25 mm² |
| 2 conductors with same cross section, stranded min. | 16 mm² |
| 2 conductors with same cross section, stranded max. | 25 mm² |
| Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, minimum | 16 mm² |
| Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, maximum | 25 mm² |
| Internal cylindrical gage | A11 |
| Operating temperature | -60 °C … 105 °C (max. short-term operating temperature 125°C) |
|---|---|
| Ambient temperature (storage/transport) | -25 °C … 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C) |
| Permissible humidity (storage/transport) | 30 % … 70 % |
| Ambient temperature (assembly) | -5 °C … 70 °C |
| Ambient temperature (actuation) | -5 °C … 70 °C |
| Connection in acc. with standard | CSA |
|---|---|
| IEC 60947-7-1 | |
| Flammability rating according to UL 94 | V0 |
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
|---|---|
| No hazardous substances above threshold values |