Inosaki is one of the largest Phoenix Contact Distributors to provide terminal block, interface module, power supply and relay. And our best offer for terminal block types are Feed-through, Fuse Modular, Spring Cage, Double Level, and Multi-level, hence the series model references to PT Series, ST Series, TB Series, UT Series, UK Series. In additional for power supply are QUINT Power, STEP Power, Trio Power, and UNO Power. Please email us for catalog: sales@inosaki.my
Dimensions
Width |
151 mm |
Height |
304 mm |
Depth |
120 mm |
Installation distance right/left |
20 mm / 20 mm |
Installation distance top/bottom |
50 mm / 100 mm |
Ambient conditions
Degree of protection |
IP67 |
Inflammability class in acc. with UL 94 (housing / terminal blocks) |
V0 |
Ambient temperature (operation) |
-25 °C … 85 °C (Derating >60°C: 2.5 %/K) |
Ambient temperature (start-up type tested) |
-40 °C |
Ambient temperature (storage/transport) |
-40 °C … 85 °C |
Max. permissible relative humidity (operation) |
≤ 95 % (at 25 °C, non-condensing) |
Climatic class |
3K3 (in acc. with EN 60721) |
Degree of pollution |
4 |
Installation height |
≤ 4000 m (> 2000 m, Derating: 10 %/1000 m) |
Input data
Nominal input voltage range |
100 V AC … 240 V AC |
|
110 V DC … 250 V DC |
Input voltage range |
100 V AC … 240 V AC 10 % |
|
110 V DC … 250 V DC 10 % |
Dielectric strength maximum |
≤ 300 V AC 15 s |
AC frequency range |
50 Hz … 60 Hz |
Discharge current to PE |
< 3.5 mA |
Current consumption |
5.6 A (100 V AC) |
|
2.4 A (240 V AC) |
Nominal power consumption |
36.8 W |
Inrush current |
typ. 20 A (at 25 °C) |
Mains buffering time |
typ. 10 ms (120 V AC) |
|
typ. 15 ms (230 V AC) |
Input fuse |
10 A (internal (device protection)) |
Recommended breaker for input protection |
10 A … 16 A (Characteristics B, C, D, K) |
Type of protection |
Transient surge protection |
Protective circuit/component |
Varistor |
Output data
Nominal output voltage |
24 V DC ±1 % |
Nominal output current (IN) |
20 A |
Dynamic Boost (IDyn.Boost) |
30 A (5 s) |
Derating |
> 60 °C … 70 °C (2.5%/K) |
Protection against overvoltage at the output (OVP) |
≤ 30 V DC |
Control deviation |
< 1 % (change in load, static 10 % … 90 %) |
|
< 3 % (Dynamic load change 10 % … 90 %, 10 Hz) |
|
< 0.1 % (change in input voltage ±10 %) |
Residual ripple |
≤ 30 mVPP |
Output power |
480 W |
Typical response time |
< 1 s |
Maximum power dissipation in no-load condition |
< 3 W (120 V AC) |
|
< 2.5 W (230 V AC) |
Power loss nominal load max. |
< 48 W (120 V AC) |
|
< 36 W (230 V AC) |
General
Article Number |
1039830 |
Net weight |
3.7 kg |
Efficiency |
91 % (100 V AC) |
|
93 % (230 V AC) |
MTBF (IEC 61709, SN 29500) |
> 1400000 h (25 °C) |
|
> 800000 h (40 °C) |
|
> 400000 h (60 °C) |
Insulation voltage input/output |
4 kV AC (type test) |
|
1.5 kV AC (routine test) |
Degree of protection |
IP67 |
Protection class |
I |
Inflammability class in acc. with UL 94 (housing / terminal blocks) |
V0 |
Assembly instructions |
Alignable: 20 mm horizontally, 50 mm vertically above, 100 mm vertically below |
Connection data, input
Connection method |
Circular connector |
Type of locking |
M12 screw locking |
Coding |
S-coded |
Number of positions |
3 |
Connection data, output
Connection method |
Circular connector |
Type of locking |
M17 standard and SPEEDCON locking |
Coding |
N-coded |
Number of positions |
4 |
Connection data for signaling
Connection method |
Circular connector |
Type of locking |
SPEEDCON M12 |
Coding |
A-coded |
Number of positions |
5 |
Standards
Standard – Electrical safety |
IEC 61010-2-201 (SELV) |
Standard – Safety extra-low voltage |
EN 60204-1 (PELV) |
Standard – Safe isolation |
DIN VDE 0100-410 |
Standard – Limitation of mains harmonic currents |
EN 61000-3-2 |
Overvoltage category EN 61010-1 |
III (≤ 2000 m) |
|
II (≤ 4000 m) |
EMC data
Electromagnetic compatibility |
Conformance with EMC Directive 2014/30/EU |
Low Voltage Directive |
Conformance with Low Voltage Directive 2014/35/EC |
Conducted noise emission |
EN 55016 |
|
EN 61000-6-3 (Class B) |
Noise emission |
EN 55016 |
|
EN 61000-6-3 (Class B) |
Flicker |
EN 61000-3-3 |
Electrostatic discharge |
EN 61000-4-2 |
Contact discharge |
6 kV (Test Level 4) |
Discharge in air |
8 kV (Test Level 4) |
Electromagnetic HF field |
EN 61000-4-3 |
Frequency range |
80 MHz … 1 GHz |
Test field strength |
10 V/m (Test Level 3) |
Frequency range |
1 GHz … 2 GHz |
Test field strength |
10 V/m (Test Level 3) |
Frequency range |
2 GHz … 3 GHz |
Test field strength |
10 V/m (Test Level 3) |
Comments |
Criterion A |
Fast transients (burst) |
EN 61000-4-4 |
Input |
4 kV (Test Level 4 – asymmetrical) |
Output |
2 kV (Test Level 3 – asymmetrical) |
Signal |
2 kV (Test Level 2 – asymmetrical) |
Comments |
Criterion A |
Surge voltage load (surge) |
EN 61000-4-5 |
Input |
3 kV (Test Level 3 – symmetrical) |
|
4 kV (Test Level 4 – asymmetrical) |
Output |
1 kV (Test Level 2 – symmetrical) |
|
2 kV (Test Level 1 – asymmetrical) |
Signal |
1 kV (Test Level 2 – asymmetrical) |
Comments |
Criterion B |
Conducted interference |
EN 61000-4-6 |
Frequency range |
0.15 MHz … 80 MHz |
Voltage |
10 V (Test Level 3) |
Comments |
Criterion A |
Voltage dips |
EN 61000-4-11 |
Voltage |
230 V AC |
Frequency |
50 Hz |
Voltage dip |
70 % |
Number of periods |
25 periods |
Additional text |
Test Level 2 |
Comments |
Criterion A |
Voltage dip |
40 % |
Number of periods |
10 periods |
Additional text |
Test Level 2 |
Comments |
Criterion B |
Voltage dip |
0 % |
Number of periods |
1 period |
Additional text |
Test Level 2 |
Comments |
Criterion B |
Criterion A |
Normal operating behavior within the specified limits. |
Criterion B |
Temporary impairment to operational behavior that is corrected by the device itself. |
Criterion C |
Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements. |
Environmental Product Compliance
REACh SVHC |
Lead 7439-92-1 |