$ 80.52 – $ 80.74
Main | |||
Part Number | LRD4365 | LRD4367 | LRD4369 |
Product Series | TeSys | TeSys | TeSys |
product name | TeSys LRD TeSys Deca |
TeSys LRD TeSys Deca |
TeSys LRD TeSys Deca |
product type | Type E 3 pole thermal overload relay | Type E 3 pole thermal overload relay | Type E 3 pole thermal overload relay |
product short name | LRD | LRD | LRD |
Relay application | Motor protection | Motor protection | Motor protection |
The scope of products | LC1D115 LC1D150 |
LC1D150 LC1D115 |
LC1D150 |
Network Type | AC DC |
AC DC |
DC AC |
Thermal release drag rating | Class 10A conforming to IEC 60947-4-1 | Class 10A conforming to IEC 60947-4-1 | Class 10A conforming to IEC 60947-4-1 |
Relay setting range | 80…104A | 95…120A | 110…140A |
Rated insulation voltage [Ui] | Power circuit: 1000 V conforming to IEC 60947-4-1 Power circuit: 600 V conforming to CSA Power circuit: 600 V conforming to UL |
Power circuit: 1000 V conforming to IEC 60947-4-1 Power circuit: 600 V conforming to CSA Power circuit: 600 V conforming to UL |
Power circuit: 1000 V conforming to IEC 60947-4-1 |
Additional information | |||
Network frequency | 0…400Hz | 0…400Hz | 0…400Hz |
installation method | Base plate mounting, with special accessories DIN rail mounting, with special accessories under the contactor |
Base plate mounting, with special accessories DIN rail mounting, with special accessories under the contactor |
Base plate mounting, with special accessories DIN rail mounting, with special accessories under the contactor |
Trip threshold | 1.14 ± 0.06 In conforming to IEC 60947-4-1 | 1.14 ± 0.06 In conforming to IEC 60947-4-1 | 1.14 ± 0.06 In conforming to IEC 60947-4-1 |
Auxiliary contact type | 1 NO + 1 NC | 1 NO + 1 NC | 1 NO + 1 NC |
Conventional thermal current [Ith] | 5 A for signal circuits | 5 A for signal circuits | 5 A for signal circuits |
Current setting range | 0.06 A at 440 V DC-13 for signal circuit 0.12 A at 600 V AC-15 for signal circuit |
0.06 A at 440 V DC-13 for signal circuit 0.12 A at 600 V AC-15 for signal circuit |
0.06 A at 440 V DC-13 for signal circuit 0.12 A at 600 V AC-15 for signal circuit |
Rated working voltage [Ue] | 1000 V AC 0…400 Hz for power circuits according to IEC 60947-4-1 | 1000 V AC 0…400 Hz for power circuits according to IEC 60947-4-1 | 1000 V AC 0…400 Hz for power circuits according to IEC 60947-4-1 |
Fuses for use with relays | 4 A gG for signal circuit 4 A BS for signal circuit |
4 A gG for signal circuit 4 A BS for signal circuit |
4 A gG for signal circuit 4 A BS for signal circuit |
Rated impulse withstand voltage [Uimp] | 6 kV according to IEC 60947-1 | 6 kV according to IEC 60947-1 | 6 kV according to IEC 60947-1 |
phase loss sensitivity | Two phases 1.3 Ir, the other phase is 0 | Two phases 1.3 Ir, the other phase is 0 | Two phases 1.3 Ir, the other phase is 0 |
control type | Red (push) button: stop (make N/C contact act, not affect N/O contact) blue (push) button: reset |
Red (push) button: stop (make N/C contact act, not affect N/O contact) blue (push) button: reset |
Red (push) button: stop (make N/C contact act, not affect N/O contact) blue (push) button: reset |
Temperature compensation | -20…60°C | -20…60°C | -20…60°C |
Wiring capacity | Power circuit: screw-on1 cable 4…35 mm² flexible with control circuit: screw-on2 cable 1…2.5 mm² flexible without control circuit: screw-on2 cable 1…2.5 mm² flexible with control circuit: screw-on Fastening2 Cable 1…2.5 mm² rigid without power circuit: screw fastened1 cable 4…50 mm² flexible without power circuit: screw fastened1 cable 4…50 mm² rigid without power circuit |
Power circuit: screw-on1 cable 4…35 mm² flexible with control circuit: screw-on2 cable 1…2.5 mm² flexible without control circuit: screw-on2 cable 1…2.5 mm² flexible with control circuit: screw-on Fastening2 Cable 1…2.5 mm² rigid without power circuit: screw fastened1 cable 4…50 mm² flexible without power circuit: screw fastened1 cable 4…50 mm² rigid without power circuit |
Power circuit: screw-on1 cable 4…35 mm² flexible with control circuit: screw-on2 cable 1…2.5 mm² flexible without control circuit: screw-on2 cable 1…2.5 mm² flexible with control circuit: screw-on Fastening2 Cable 1…2.5 mm² rigid without power circuit: screw fastened1 cable 4…50 mm² flexible without power circuit: screw fastened1 cable 4…50 mm² rigid without power circuit |
Tightening torque | Control circuit: 1.7 Nm Bolt-on Power circuit: 9 Nm Bolt-on |
Control circuit: 1.7 Nm Bolt-on Power circuit: 9 Nm Bolt-on |
Control circuit: 1.7 Nm Bolt-on Power circuit: 9 Nm Bolt-on |
depth | 132 mm | 132 mm | 132 mm |
Product Weight | 0.9kg | 0.9kg | 0.9kg |
environment | |||
climate tolerance | Conforms to IACS E10 | Conforms to IACS E10 | Conforms to IACS E10 |
IP protection class | IP20 conforming to IEC 60529 | IP20 conforming to IEC 60529 | IP20 conforming to IEC 60529 |
ambient temperature | -20…60 °C without derating according to IEC 60947-4-1 | -20…60 °C without derating according to IEC 60947-4-1 | -20…60 °C without derating according to IEC 60947-4-1 |
storage environment temperature | -60…70°C | -60…70°C | -60…70°C |
flame retardant | V1 complies with UL 94 | V1 complies with UL 94 | V1 complies with UL 94 |
Shock and vibration resistance | Shock resistance: 6 gn conforming to IEC 60068-2-6 Shock resistance: 15 gn (11ms) conforming to IEC 60068-2-7 |
Shock resistance: 6 gn conforming to IEC 60068-2-6 Shock resistance: 15 gn (11ms) conforming to IEC 60068-2-7 |
Shock resistance: 6 gn conforming to IEC 60068-2-6 Shock resistance: 15 gn (11ms) conforming to IEC 60068-2-7 |
Insulation properties | 2.2 kV at 50 Hz conforming to IEC 60947-1 | 2.2 kV at 50 Hz conforming to IEC 60947-1 | 2.2 kV at 50 Hz conforming to IEC 60947-1 |
Standards compliant | EN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 UL 60947-5-1 DIN 3852-Y CSA C22.2 No 60947-5-1 GB/T 14048.4 GB/T 14048.5 EN50495 |
EN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 UL 60947-5-1 DIN 3852-Y CSA C22.2 No 60947-5-1 GB/T 14048.4 GB/T 14048.5 EN50495 |
EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.4 GB/T 14048.5 EN 50495 |
certified product | IEC UL CSA CCC EAC ATEX INERIS |
IEC UL CSA CCC EAC ATEX INERIS |
IEC CCC EAC ATEX INERIS |
packaging unit | |||
Unit Type of Package 1 | PCE | PCE | PCE |
Number of Units in Package 1 | 1 | 1 | 1 |
Package 1 Height | 11cm | 15.2cm | 13.8cm |
Package 1 Width | 13.5cm | 13.8cm | 10.5cm |
Package 1 Length | 15.5cm | 10.2cm | 15.5cm |
Package 1 Weight | 836g | 834g | 833g |
Unit Type of Package 2 | S03 | S03 | S03 |
Number of Units in Package 2 | 10 | 10 | 10 |
Package 2 Height | 30cm | 30cm | 30cm |
Package 2 Width | 30cm | 30cm | 30cm |
Package 2 Length | 40cm | 40cm | 40cm |
Package 2 Weight | 8.85kg | 8.84kg | 8.835kg |
Unit Type of Package 3 | P06 | P06 | P06 |
Number of Units in Package 3 | 80 | 80 | 80 |
Package 3 Height | 75cm | 77cm | 75cm |
Package 3 Width | 60cm | 80cm | 60cm |
Package 3 Length | 80cm | 60cm | 80cm |
Package 3 Weight | 81.084kg | 79.22kg | 77.68kg |
contract warranty | |||
Warranty | 18 months | 18 months | 18 months |
Weight | N/A |
---|---|
Dimensions | N/A |
INOSAKI Limited
RM B 5/F Gaylord Comm,
Bldg 114-118 Lockhart Rd.
Hong Kong
INOSAKI Sdn. Bhd.
2-1-9, Ground Floor, One Square, Tingkat Mahsuri 1,
11900 Bayan Lepas, Penan
INOSAKI Pte. Ltd.
101 Upper Cross Street,
No. 06-17, People’s Park Centre,
Singapore (058357)