Main
Part Number LP1K0901BD LP1K1210BD LP1K0910BD LP1K1201BD
Product Series TeSys K TeSys K TeSys K TeSys K
Product Series TeSys TeSys K TeSys K TeSys K
product type Contactor Contactor Contactor Contactor
product short name LP1K LP1K LP1K LP1K
Application field of contactor Applied to non-inductive or micro-inductive loads, and resistance furnaces
to AC loads with a power factor greater than or equal to 0.95
Applied to non-inductive or micro-inductive loads, and resistance furnaces
to AC loads with a power factor greater than or equal to 0.95
Applied to AC loads with power factor greater than or equal to 0.95
Applied to non-inductive or slightly inductive loads, resistance furnaces
Applied to non-inductive or micro-inductive loads, and resistance furnaces
to AC loads with a power factor greater than or equal to 0.95
use category AC-1
AC-4
AC-3
AC-3e
AC-3
AC-1
AC-4
AC-3e
AC-3
AC-1
AC-4
AC-3e
AC-1
AC-4
AC-3
AC-3e
number of poles 3P 3P 3P 3P
Loop contact type 3 NO 3 NO 3 NO 3 NO
Rated operating current [Ie] 20 A 50 °C) at <= 440 V AC AC-1 for power circuit
9 A at <= 440 V AC AC-3 for power circuit
16 A at 70 °C) at 690 V AC AC- 1 for power circuit
9 A at <= 440 V AC AC-3e for power circuit
12 A 50 °C) at <= 440 V AC-3 for power circuit
10 A 60 °C) at <= 440 V AC-3 for power circuit
20 A 50 °C) at <= 690 V AC-1 for power circuit
16 A 60 °C) at <= 690 V AC-1 for power circuit
12 A 50 °C) at <= 440 V AC-3e for power circuit
10 A 60 °C ) at <= 440 V AC-3e for power circuits
20 A 50 °C) at <= 440 V AC AC-1 for power circuit
9 A at <= 440 V AC AC-3 for power circuit
16 A at 70 °C) at 690 V AC AC- 1 for power circuit
9 A at <= 440 V AC AC-3e for power circuit
12 A 50 °C) at <= 440 V AC-3 for power circuit
10 A 60 °C) at <= 440 V AC-3 for power circuit
20 A 50 °C) at <= 690 V AC-1 for power circuit
16 A 60 °C) at <= 690 V AC-1 for power circuit
12 A 50 °C) at <= 440 V AC-3e for power circuit
10 A 60 °C ) at <= 440 V AC-3e for power circuits
Auxiliary contact type 1 NC 1 NO 1 NO 1 NC
Additional information
Auxiliary contact type Type Momentary 1 NC 1 NO 1 NO 1 NC
Control voltage limit Operating: 0.8…1.15 Uc 50 °C)
Release: 0.1…0.75 Uc 50 °C)
Operating: 0.8…1.15 Uc 50 °C)
Release: 0.1…0.75 Uc 50 °C)
Operating: 0.8…1.15 Uc 50 °C)
Release: 0.1…0.75 Uc 50 °C)
Operating: 0.8…1.15 Uc 50 °C)
Release: 0.1…0.75 Uc 50 °C)
Rated insulation voltage [Ui] Power circuit: 600 V conforming to UL 508
Power circuit: 690 V conforming to IEC 60947-4-1
Signaling circuit: 690 V conforming to IEC 60947-4-1
Signaling circuit: 690 V conforming to IEC 60947-5-1
Signaling circuit: 600 V conforming UL 508
Power Circuit: 600 V per CSA C22.2 No 14
Signal Circuit: 600 V per CSA C22.2 No 14
Power circuit: 600 V conforming to UL 508
Power circuit: 690 V conforming to IEC 60947-4-1
Signaling circuit: 690 V conforming to IEC 60947-4-1
Signaling circuit: 690 V conforming to IEC 60947-5-1
Signaling circuit: 600 V conforming UL 508
Power Circuit: 600 V per CSA C22.2 No 14
Signal Circuit: 600 V per CSA C22.2 No 14
Power circuit: 600 V conforming to UL 508
Power circuit: 690 V conforming to IEC 60947-4-1
Signaling circuit: 690 V conforming to IEC 60947-4-1
Signaling circuit: 690 V conforming to IEC 60947-5-1
Signaling circuit: 600 V conforming UL 508
Power Circuit: 600 V per CSA C22.2 No 14
Signal Circuit: 600 V per CSA C22.2 No 14
Power circuit: 600 V conforming to UL 508
Power circuit: 690 V conforming to IEC 60947-4-1
Signaling circuit: 690 V conforming to IEC 60947-4-1
Signaling circuit: 690 V conforming to IEC 60947-5-1
Signaling circuit: 600 V conforming UL 508
Power Circuit: 600 V per CSA C22.2 No 14
Signal Circuit: 600 V per CSA C22.2 No 14
Rated impulse withstand voltage [Uimp] 8kV 8kV 8kV 8kV
Overvoltage category III III III III
installation method DIN rail installation
base plate installation
Chassis mounting
rail installation
DIN rail installation
base plate installation
DIN rail installation
base plate installation
flame retardant V1 Conforms to UL 94
requirements2 Conforms to NF F 16-101
requirements2 Conforms to NF F 16-102
V1 Conforms to UL 94
requirements2 Conforms to NF F 16-101
requirements2 Conforms to NF F 16-102
V1 Conforms to UL 94
requirements2 Conforms to NF F 16-101
requirements2 Conforms to NF F 16-102
V1 Conforms to UL 94
requirements2 Conforms to NF F 16-101
requirements2 Conforms to NF F 16-102
Tightening torque 0.8…1.3 Nm Bolting No 2 Phillips screw
0.8…1.3 Nm Bolting Ø 6 Flat
0.8…1.3 Nm Bolting pozidriv No 2
0.8…1.3 Nm Bolting No 2 Phillips screw
0.8…1.3 Nm Bolting Ø 6 Flat
0.8…1.3 Nm Bolting pozidriv No 2
0.8…1.3 Nm Bolting No 2 Phillips screw
0.8…1.3 Nm Bolting Ø 6 Flat
0.8…1.3 Nm Bolting pozidriv No 2
0.8…1.3 Nm Bolting No 2 Phillips screw
0.8…1.3 Nm Bolting Ø 6 Flat
0.8…1.3 Nm Bolting pozidriv No 2
Rated working voltage [Ue] Power circuit: 690 V AC 50/60 Hz
Signal circuit: <= 690 V AC 50/60 Hz
Power circuit: 690 V AC 50/60 Hz
Signal circuit: 690 V AC 50/60 Hz
Power circuit: 690 V AC 50/60 Hz
Signal circuit: <= 690 V AC 50/60 Hz
Power circuit: 690 V AC 50/60 Hz
Signal circuit: 690 V AC 50/60 Hz
Conventional thermal current [Ith] 20 A at <50 °C for power circuits
10 A at <50 °C for signal circuits
20 A at <50 °C for power circuits
10 A at <50 °C for signal circuits
20 A at <50 °C for power circuits
10 A at <50 °C for signal circuits
20 A at <50 °C for power circuits
10 A at <50 °C for signal circuits
Rated making capacity [Irms] 110 A AC for power circuits according to NF C 63-110
110 A AC for power circuits according to IEC 60947
110 A AC for signal circuits according to IEC 60947
110 A AC for signal circuits according to IEC 60947
144 A AC for power circuits according to NF C 63-110
144 A AC for power circuits according to IEC 60947
110 A AC for power circuits according to NF C 63-110
110 A AC for power circuits according to IEC 60947
110 A AC for signal circuits according to IEC 60947
110 A AC for signal circuits according to IEC 60947
144 A AC for power circuits according to NF C 63-110
144 A AC for power circuits according to IEC 60947
Rated breaking capacity 110 A at 415 V conforming to IEC 60947
110 A at 440 V conforming to IEC 60947
80 A at 500 V conforming to IEC 60947
110 A at 220…230 V conforming to IEC 60947
110 A at 380 …400 V conforming to IEC 60947
70 A at 660…690 V conforming to IEC 60947
110 A at 440 V conforming to IEC 60947
80 A at 500 V conforming to IEC 60947
70 A at 660…690 V conforming to IEC 60947
110 A at 415 V conforming to IEC 60947
110 A at 440 V conforming to IEC 60947
80 A at 500 V conforming to IEC 60947
110 A at 220…230 V conforming to IEC 60947
110 A at 380 …400 V conforming to IEC 60947
70 A at 660…690 V conforming to IEC 60947
110 A at 440 V conforming to IEC 60947
80 A at 500 V conforming to IEC 60947
70 A at 660…690 V conforming to IEC 60947
Fuses for use with relays 25 A gG at <= 440 V for power circuits
25 A aM for power circuits
10 A gG for signal circuits according to IEC 60947
10 A gG for signal circuits according to VDE 0660
25 A gG at <= 440 V for power circuits
25 A aM for power circuits
10 A gG for signal circuits according to IEC 60947
10 A gG for signal circuits according to VDE 0660
25 A gG at <= 440 V for power circuits
25 A aM for power circuits
10 A gG for signal circuits according to IEC 60947
10 A gG for signal circuits according to VDE 0660
25 A gG at <= 440 V for power circuits
25 A aM for power circuits
10 A gG for signal circuits according to IEC 60947
10 A gG for signal circuits according to VDE 0660
average impedance 3 mΩ – Ith 20 A 50 Hz for power circuits 3 mΩ – Ith 20 A 50 Hz for power circuits 3 mΩ – Ith 20 A 50 Hz for power circuits 3 mΩ – Ith 20 A 50 Hz for power circuits
Surge power (W) 3W (20°C) 3W (20°C) 3W (20°C) 3W (20°C)
Holding power consumption(W) 3 W at 20 °C 3 W at 20 °C 3 W at 20 °C 3 W at 20 °C
action time 30…40 ms coil energization and NO contact closure
10 ms coil discharge and NO opening
30…40 ms coil energization and NO contact closure
10 ms coil discharge and NO opening
30…40 ms coil energization and NO contact closure
10 ms coil discharge and NO opening
30…40 ms coil energization and NO contact closure
10 ms coil discharge and NO opening
Safety and reliability level B10d = Contactor for 1369863 nominal loads according to EN/ISO 13849-1
B10d = Contactor for 20000000 mechanical loads according to EN/ISO 13849-1
B10d = Contactor for 1369863 nominal loads according to EN/ISO 13849-1
B10d = Contactor for 20000000 mechanical loads according to EN/ISO 13849-1
B10d = Contactor for 1369863 nominal loads according to EN/ISO 13849-1
B10d = Contactor for 20000000 mechanical loads according to EN/ISO 13849-1
B10d = Contactor for 1369863 nominal loads according to EN/ISO 13849-1
B10d = Contactor for 20000000 mechanical loads according to EN/ISO 13849-1
Mechanical life 10 Mcycles 10 Mcycles 10 Mcycles 10 Mcycles
operating frequency 3600 times/hour 3600 times/hour 3600 times/hour 3600 times/hour
Minimum switching current [Imin] 5 mA for signal loop 5 mA for signal loop 5 mA for signal loop 5 mA for signal loop
Minimum switching voltage 17 V for signal return 17 V for signal return 17 V for signal return 17 V for signal return
Insulation resistance > 10 MΩ for signal loops > 10 MΩ for signal loops > 10 MΩ for signal loops > 10 MΩ for signal loops
high 58 mm 58 mm 58 mm 58 mm
width 45 mm 45 mm 45 mm 45 mm
depth 57 mm 57 mm 57 mm 57 mm
Product Weight 0.225 kg 0.225 kg 0.225 kg 0.225 kg
environment
certified product UL
CSA
UKCA
UL
CSA
UKCA
UL
CSA
UKCA
UL
CSA
UKCA
operating temperature -25…50°C -25…50°C -25…50°C -25…50°C
storage environment temperature -50…80 °C -50…80 °C -50…80 °C -50…80 °C
working altitude 2000 meters without 2000 meters without 2000 meters without 2000 meters without
packaging unit
Unit Type of Package 1 PCE PCE PCE PCE
Number of Units in Package 1 1 1 1 1
Package 1 Height 5.0cm 5.0cm 5.0cm 5.0cm
Package 1 Width 6.0cm 6.0cm 6.0cm 6.0cm
Package 1 Length 6.5cm 6.5cm 6.5cm 6.5cm
Package 1 Weight 221.0g 223.0g 223.0g 221.0g
Unit Type of Package 2 S02 S02 S02 S02
Number of Units in Package 2 40 40 40 40
Package 2 Height 15.0cm 15.0cm 15.0cm 15.0cm
Package 2 Width 30.0cm 30.0cm 30.0cm 30.0cm
Package 2 Length 40.0cm 40.0cm 40.0cm 40.0cm
Package 2 Weight 9.101kg 9.157kg 9.168kg 9.101kg
Unit Type of Package 3 P06 P06 P06 P06
Number of Units in Package 3 640 640 640 640
Package 3 Height 75.0cm 75.0cm 75.0cm 75.0cm
Package 3 Width 80.0cm 80.0cm 80.0cm 80.0cm
Package 3 Length 60.0cm 60.0cm 60.0cm 60.0cm
Package 3 Weight 153.616kg 154.512kg 154.688kg 153.616kg
contract warranty
Warranty 18 months 18 months 18 months 18 months

 

Additional information