$ 32.20 – $ 34.04Price range: $ 32.20 through $ 34.04
| main information | ||
| Part Number | GV2PM08C | GV2PM14C |
| Product Series | TeSys Deca | TeSys Deca |
| product name | TeSys GV2 | TeSys GV2 |
| product short name | GV2PM | GV2PM |
| product type | Breaker | Breaker |
| Applications | Motor protection | Motor protection |
| number of poles | 3P | 3P |
| Additional information | ||
| Grid type | AC | AC |
| Network frequency | 50/60 Hz conforming to IEC 60947-2 | 50/60 Hz conforming to IEC 60947-2 |
| control type | Knob | Knob |
| installation method | Rail installation | Rail installation |
| installation location | Vertical | horizontal vertical |
| horizontal direction | ||
| Motor power (kW) | 0.75 kW at 230 V AC 50/60 Hz | 2.2 kW at 230 V AC 50/60 Hz |
| 1.5 kW at 400 V | 4 kW at 400 V | |
| 1.5 kW at 415 V | 4 kW at 415 V | |
| 1.5 kW at 440 V AC 50/60 Hz | 4 kW at 440 V AC 50/60 Hz | |
| Rated current [In] | 4A | 10A |
| Trip unit type | Thermomagnetic | Thermomagnetic |
| Electromagnetic trip current | 51A | 138A |
| Thermal overload protection setting range | 2.5…4A | 6…10A |
| isolation function | Applies to IEC 60947-1 § 7-1-6 | Applies to IEC 60947-1 § 7-1-6 |
| Mechanical shock resistance | 0.5 J IK04 | 0.5 J IK04 |
| phase loss sensitivity | Is compliant with IEC 60947-4-1 § 7-2-1-5-2 | Is compliant with IEC 60947-4-1 § 7-2-1-5-2 |
| use category | Type AC conforms to IEC 60947-2 | Type AC conforms to IEC 60947-2 |
| AC-3 conforms to IEC 60947-4-1 | AC-3 conforms to IEC 60947-4-1 | |
| Rated working voltage [Ue] | 690 V AC 50/60 Hz conforming to IEC 60947-2 | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Rated insulation voltage [Ui] | 690 V AC 50/60 Hz conforming to IEC 60947-2 | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| 600 V AC 50/60 Hz conforming to UL 508 | 600 V AC 50/60 Hz conforming to UL 508 | |
| 600 V AC 50/60 Hz conforming to CSA C22.2 No 14 | 600 V AC 50/60 Hz conforming to CSA C22.2 No 14 | |
| Conventional thermal current [Ith] | 4 A conforming to IEC 60947-4-1 | 9 A conforming to IEC 60947-4-1 |
| Rated impulse withstand voltage [Uimp] | 6 kV according to IEC 947-2 | 6 kV according to IEC 947-2 |
| power consumption per pole | 2.5W | 2.5W |
| Mechanical life | 100000 times | 100000 times |
| Electrical life | 100000 cycles for AC-3 at 440 V In | 100000 cycles for AC-3 at 440 V In |
| 100000 cycles for AC-3 at 440 V In/2 | 100000 cycles for AC-3 at 440 V In/2 | |
| maximum conversions | 25 cyc/h | 25 cyc/h |
| specified load | Continuous according to IEC 60947-4-1 | Continuous according to IEC 60947-4-1 |
| Wiring capacity | Power circuit: Screw-in terminals 2 1…6 mm² Cable option: Solid without wire terminals Power circuit: | Power circuit: Screw-in terminals 2 1…6 mm² Cable option: Solid without wire terminals Power circuit: |
| Screw-in terminals 2 1.5…6 mm² Cable option: Flexible without wire terminals | Screw-in terminals 2 1.5…6 mm² Cable option: Flexible without wire terminals | |
| Power circuit: Screw-in terminals 2 1…4 mm² Cable selection: Flexible with wire terminals | Power circuit: Screw-in terminals 2 1…4 mm² Cable selection: Flexible with wire terminals | |
| Tightening torque | 1.7 Nm via screw-in terminal cable 1…4 mm² | 1.7 Nm via screw-in terminal cable 1…4 mm² |
| 1.7 Nm via screw-in terminal cable 1…6 mm² | 1.7 Nm via screw-in terminal cable 1…6 mm² | |
| 1.7 Nm via screw-in terminal cable 1.5…6 mm² | 1.7 Nm via screw-in terminal cable 1.5…6 mm² | |
| Breaking capacity | Icu: >= 100 kA at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 | Icu: >= 100 kA at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 |
| Icu: >= 100 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 | Icu: >= 100 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 | |
| Icu: >= 100 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 | Icu: 15 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 | |
| Icu: >= 100 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 | Icu: 10 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 | |
| Icu: 3 kA at 690 V AC 50/ 60 Hz conforming to IEC 60947-2 | Icu: 3 kA at 690 V AC 50/60 Hz conforming to IEC 60947-2 | |
| Rated operating short-circuit breaking capacity [Ics] | 75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2 | 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
| 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 | ||
| 75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2 2 | ||
| high | 89mm | 89 mm |
| width | 44.5 mm | 44.5 mm |
| depth | 91 mm | 91 mm |
| product weight | 0.26kg | 0.26kg |
| environment | ||
| Standards compliant | GB 14048.4 | GB 14048.4 |
| IEC 60947-1 | IEC 60947-1 | |
| IEC 60947-2 | IEC 60947-2 | |
| IEC 60947-4-1 | IEC 60947-4-1 | |
| certified product | CCC | CCC |
| UKCA | UKCA | |
| CE | CE | |
| Protective measures | TH | TH |
| IP protection class | IP20 complies with screwed (body) | IP20 complies with screwed (body) |
| Shock and vibration resistance | Shock resistance 11 ms (30 gn) conforming to IEC 60068-2-27 | Shock resistance 11 ms (30 gn) conforming to IEC 60068-2-27 |
| Shock resistance (5 gn (5…150 Hz)) conforming to IEC 60068-2-6 | Shock resistance (5 gn (5…150 Hz)) conforming to IEC 60068-2-6 | |
| ambient temperature | -20…40 °C In cabinet | -20…40 °C In cabinet |
| -20…60 °C Body | -20…60 °C Body | |
| storage environment temperature | -40…80°C | -40…80°C |
| Fire resistance and abnormal high temperature resistance | 960 °C conforming to IEC 60695-2-1 | 960 °C conforming to IEC 60695-2-1 |
| working altitude | <= 2000m | <= 2000m |
| packaging unit | ||
| Unit Type of Package 1 | PCE | PCE |
| Number of Units in Package 1 | 1 | 1 |
| Package 1 Height | 4.93cm | 5.14cm |
| Package 1 Width | 9.02 cm | 9.29cm |
| Package 1 Length | 9.38cm | 9.78cm |
| Package 1 Weight | 282.6g | 299.2g |
| Unit Type of Package 2 | S02 | S02 |
| Number of Units in Package 2 | 20 | 20 |
| Package 2 Height | 15.0cm | 15.0cm |
| Package 2 Width | 30.0cm | 30.0cm |
| Package 2 Length | 40.0cm | 40.0cm |
| Package 2 Weight | 6.044 kg | 6.376 kg |
| Unit Type of Package 3 | P06 | P06 |
| Number of Units in Package 3 | 400 | 400 |
| Package 3 Height | 90.0cm | 90.0cm |
| Package 3 Width | 60.0cm | 60.0cm |
| Package 3 Length | 80.0cm | 80.0cm |
| Package 3 Weight | 130.88kg | 137.52kg |
| contract warranty | ||
| Warranty | 18 months | 18 months |