Inosaki is one of the largest Phoenix Contact Distributors to provide terminal block, interface module, power supply and relay. And our best offer for terminal block types are Feed-through, Fuse Modular, Spring Cage, Double Level, and Multi-level, hence the series model references to PT Series, ST Series, TB Series, UT Series, UK Series. In additional for power supply are QUINT Power, STEP Power, Trio Power, and UNO Power. Please email us for catalog: sales@inosaki.my
Test disconnect terminal block, with two test sockets for 4 mm test plugs, or for receiving bridge bars or screw bridges, connection method: Screw connection, cross section: 1 mm2 – 6 mm2 , AWG: 18 – 10, width: 8.2 mm, mounting type: NS 35/7,5, NS 35/15, NS 32,
General
Article Number | 3001605 |
Number of levels | 1 |
Number of connections | 2 |
Potentials | 1 |
Nominal cross section | 6 mm² |
Color | dark gray |
Insulating material | PA |
Flammability rating according to UL 94 | V0 |
Mounting type | NS 35/7,5 |
NS 35/15 | |
NS 32 | |
Rated surge voltage | 6 kV |
Degree of pollution | 3 |
Overvoltage category | III |
Insulating material group | I |
Maximum load current | 57 A (with 10 mm² conductor cross section) |
Nominal current IN | 41 A (with 6 mm² conductor connection) |
Nominal voltage UN | 500 V |
Open side panel | Yes |
Shock protection test specification | DIN EN 50155 (VDE 0115-200):2008-03 |
Back of the hand protection | guaranteed |
Finger protection | guaranteed |
Result of surge voltage test | Test passed |
Surge voltage test setpoint | 7.3 kV |
Result of power-frequency withstand voltage test | Test passed |
Result of the test for mechanical stability of terminal points (5 x conductor connection) | Test passed |
Result of flexion and pull-out test | Test passed |
Bending test rotation speed | 10 rpm |
Bending test turns | 135 |
Bending test conductor cross section/weight | 1 mm² / 0.4 kg |
6 mm² / 1.4 kg | |
Tensile test result | Test passed |
Tractive force setpoint | 10 N |
Conductor cross section tensile test | 2.5 mm² |
Tractive force setpoint | 50 N |
Conductor cross section tensile test | 4 mm² |
Tractive force setpoint | 60 N |
Result of tight fit on support | Test passed |
Tight fit on carrier | NS 35 |
Result of voltage-drop test | Test passed |
Requirements, voltage drop | U1 ≤ 3.2 mV; U2 ≤ 1.5 x U1 |
Result of temperature-rise test | Test passed |
Requirement temperature-rise test | Increase in temperature ≤ 45 K |
Short circuit stability result | Test passed |
Conductor cross section short circuit testing | 2.5 mm² |
Short-time current | 0.3 kA |
Result of thermal test | Test passed |
Proof of thermal characteristics (needle flame) effective duration | 30 s |
Result of aging test | Test passed |
Ageing test for screwless modular terminal block temperature cycles | 192 |
Oscillation, broadband noise test result | Test passed |
Test specification, oscillation, broadband noise | DIN EN 50155 (VDE 0115-200):2018-05 |
Test spectrum | Service life test category 2, bogie-mounted |
Test frequency | f1 = 5 Hz to f2 = 250 Hz |
ASD level | 6.12 (m/s²)²/Hz |
Acceleration | 3.12g |
Test duration per axis | 5 h |
Test directions | X-, Y- and Z-axis |
Shock test result | Test passed |
Shock form | Half-sine |
Acceleration | 0.58g |
Shock duration | 30 ms |
Number of shocks per direction | 3 |
Test directions | X-, Y- and Z-axis (pos. and neg.) |
Ambient temperature (operation) | -60 °C … 105 °C (max. short-term operating temperature 130°C) |
Ambient temperature (storage/transport) | -25 °C … 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C) |
Ambient temperature (assembly) | -5 °C … 70 °C |
Ambient temperature (actuation) | -5 °C … 70 °C |
Permissible humidity (storage/transport) | 30 % … 70 % |
Dimensions
Width | 8.2 mm |
End cover width | 2.2 mm |
Height NS 35/15 | 55 mm |
Height NS 35/7,5 | 47.5 mm |
Height | 2.028 “ |
Height NS 32 | 52.5 mm |
Length | 73 mm |
Connection data
Connection | 1 level |
Grounding foot | No |
Nominal cross section | 6 mm² |
Maximum load current | 57 A (with 10 mm² conductor cross section) |
esignation | Level 1 above 1 below 1 |
Connection labeling | 1 level |
Screw thread | M4 |
Note | Terminal point |
Tightening torque | 1.4 … 1.5 Nm |
Stripping length | 10 mm |
Internal cylindrical gage | A5 |
Connection in acc. with standard | IEC 60947-7-1 |
Conductor cross section solid | 1 mm² … 6 mm² |
Cross section AWG | 18 … 10 |
Conductor cross section flexible | 1 mm² … 6 mm² |
Conductor cross section, flexible [AWG] | 18 … 10 |
Flexible conductor cross section flexible (ferrule, w/o plastic sleeve) | 1 mm² … 6 mm² |
Flexible conductor cross section (ferrule with plastic sleeve) | 1 mm² … 6 mm² |
Nominal current | 41 A (with 6 mm² conductor connection) |
Maximum load current | 41 A (with 6 mm² conductor connection) |
Nominal voltage | 500 V |
Nominal cross section | 6 mm² |