Multi-level terminal block, nom. voltage: 500 V, nominal current: 20 A, connection method: Spring-cage connection, number of connections: 6, cross section: 0.08 mm² – 4 mm², AWG: 28 – 12, width: 5.2 mm, color: gray, mounting type: NS 35/7,5, NS 35/15
| Article Number | 3036042 |
|---|---|
| Number of levels | 3 |
| Number of connections | 6 |
| Potentials | 3 |
| Nominal cross section | 2.5 mm² |
| Color | gray |
| Insulating material | PA |
| Flammability rating according to UL 94 | V0 |
| Mounting type | NS 35/7,5 |
| Rated surge voltage | 6 kV |
| Degree of pollution | 3 |
| Overvoltage category | III |
| Insulating material group | I |
| Maximum load current | 28 A (with 4 mm² conductor cross section) |
| Nominal current IN | 20 A |
| Nominal voltage UN | 500 V |
| Open side panel | Yes |
| Shock protection test specification | DIN EN 50274 (VDE 0660-514):2002-11 |
| Back of the hand protection | guaranteed |
| Finger protection | guaranteed |
| Result of surge voltage test | Test passed |
| Surge voltage test setpoint | 7.3 kV |
| Result of power-frequency withstand voltage test | Test passed |
| Power frequency withstand voltage setpoint | 1.89 kV |
| Result of the test for mechanical stability of terminal points (5 x conductor connection) | Test passed |
| Result of flexion and pull-out test | Test passed |
| Bending test rotation speed | 10 rpm |
| Bending test turns | 135 |
| Bending test conductor cross section/weight | 0.08 mm² / 0.1 kg |
| 2.5 mm² / 0.7 kg | |
| Tensile test result | Test passed |
| Conductor cross section tensile test | 0.08 mm² |
| Tractive force setpoint | 5 N |
| Conductor cross section tensile test | 2.5 mm² |
| Tractive force setpoint | 50 N |
| Conductor cross section tensile test | 4 mm² |
| Tractive force setpoint | 60 N |
| Result of tight fit on support | Test passed |
| Tight fit on carrier | NS 35 |
| Result of voltage-drop test | Test passed |
| Requirements, voltage drop | U1 ≤ 3,2 mV U2 ≤ 1,5 x U1 dT ≤ 45 K |
| Result of temperature-rise test | Test passed |
| Requirement temperature-rise test | Increase in temperature ≤ 45 K |
| Short circuit stability result | Test passed |
| Conductor cross section short circuit testing | 2.5 mm² |
| Short-time current | 0.3 kA |
| Result of thermal test | Test passed |
| Proof of thermal characteristics (needle flame) effective duration | 30 s |
| Result of aging test | Test passed |
| Ageing test for screwless modular terminal block temperature cycles | 192 |
| Oscillation, broadband noise test result | Test passed |
| Test specification, oscillation, broadband noise | DIN EN 50155 (VDE 0115-200):2018-05 |
| Test spectrum | Service life test category 1, class B, body mounted |
| Test frequency | f1 = 5 Hz to f2 = 150 Hz |
| ASD level | 0.964 (m/s²)²/Hz |
| Acceleration | 0.58g |
| Test duration per axis | 5 h |
| Test directions | X-, Y- and Z-axis |
| Shock test result | Test passed |
| Shock form | Half-sine |
| Acceleration | 30g |
| Shock duration | 18 ms |
| Number of shocks per direction | 3 |
| Test directions | X-, Y- and Z-axis (pos. and neg.) |
| Relative insulation material temperature index (Elec., UL 746 B) | 130 °C |
| Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) | 125 °C |
| Static insulating material application in cold | -60 °C |
| Surface flammability NFPA 130 (ASTM E 162) | passed |
| Specific optical density of smoke NFPA 130 (ASTM E 662) | passed |
| Calorimetric heat release NFPA 130 (ASTM E 1354) | 27,5 MJ/kg |
| Smoke gas toxicity NFPA 130 (SMP 800C) | passed |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 – HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 – HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 – HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 – HL 3 |
| Width | 5.2 mm |
|---|---|
| End cover width | 2.2 mm |
| Length | 99.5 mm |
| Height NS 35/7,5 | 58 mm |
| Height NS 35/15 | 65.5 mm |
| Connection | 1st, 2nd and 3rd level |
|---|---|
| Connection method | Spring-cage connection |
| Stripping length | 8 mm … 10 mm |
| Connection in acc. with standard | IEC 60947-7-1 |
| Conductor cross section solid min. | 0.08 mm² |
| Conductor cross section solid max. | 4 mm² |
| Conductor cross section AWG min. | 28 |
| Conductor cross section AWG max. | 12 |
| Conductor cross section flexible min. | 0.08 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Min. AWG conductor cross section, flexible | 28 |
| Max. AWG conductor cross section, flexible | 14 |
| Conductor cross section flexible, with ferrule without plastic sleeve min. | 0.14 mm² |
| Conductor cross section flexible, with ferrule without plastic sleeve max. | 2.5 mm² |
| Conductor cross section flexible, with ferrule with plastic sleeve min. | 0.14 mm² |
| Conductor cross section flexible, with ferrule with plastic sleeve max. | 2.5 mm² |
| Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, maximum | 0.5 mm² |
| Internal cylindrical gage | A3 |
| Operating temperature | -60 °C … 105 °C (max. short-term operating temperature 130°C) |
|---|---|
| Ambient temperature (storage/transport) | -25 °C … 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C) |
| Permissible humidity (storage/transport) | 30 % … 70 % |
| Ambient temperature (assembly) | -5 °C … 70 °C |
| Ambient temperature (actuation) | -5 °C … 70 °C |
| Connection in acc. with standard | CSA |
|---|---|
| IEC 60947-7-1 | |
| Flammability rating according to UL 94 | V0 |
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
|---|---|
| No hazardous substances above threshold values |