			$ 425.50
| Part Number | 6EP1336-2BA10 | 
| Input | |
| type of the power supply network | 1-phase AC | 
| supply voltage at AC | Automatic range selection | 
| ● initial value | |
| supply voltage | 120 V | 
| ● 1 at AC rated value | |
| ● 2 at AC rated value | 230 V | 
| input voltage | 85 … 132 V | 
| ● 1 at AC | |
| ● 2 at AC | 176 … 264 V | 
| design of input wide range input | No | 
| overvoltage overload capability | 2.3 × Vin rated, 1.3 ms | 
| operating condition of the mains buffering | at Vin = 120/230 V | 
| buffering time for rated value of the output current in the event of power failure minimum | 20 ms | 
| operating condition of the mains buffering | at Vin = 120/230 V | 
| line frequency | 50 Hz | 
| ● 1 rated value | |
| ● 2 rated value | 60 Hz | 
| line frequency | 47 … 63 Hz | 
| input current | 7.5 A | 
| ● at rated input voltage 120 V | |
| ● at rated input voltage 230 V | 3.5 A | 
| current limitation of inrush current at 25 °C maximum | 11:00 AM | 
| I2t value maximum | 10 A²·s | 
| fuse protection type | T 10 A (not accessible) | 
| ● in the feeder | Recommended miniature circuit breaker: from 10 A characteristic C or circuit-breaker 3RV2411-1JA10 (120 V) or 3RV2411-1FA10 (230 V) | 
| Output | |
| voltage curve at output | Controlled, isolated DC voltage | 
| output voltage at DC rated value | 24 V | 
| output voltage | 24 V | 
| ● at output 1 at DC rated value | |
| relative overall tolerance of the voltage | 3% | 
| relative control precision of the output voltage | 0.50% | 
| ● on slow fluctuation of input voltage | |
| ● on slow fluctuation of ohm loading | 1% | 
| residual ripple | 150 mV | 
| ● maximum | |
| voltage peak | 240 mV | 
| ● maximum | |
| adjustable output voltage | 24 … 28 V | 
| product function output voltage adjustable | Yes | 
| type of output voltage setting | via potentiometer; max. 480 W | 
| display version for normal operation | Green LED for 24 V OK | 
| type of signal at output | Relay contact (NO contact, rating 50 V DC/ 0.3 A) for “24 V OK” | 
| behavior of the output voltage when switching on | No overshoot of Vout (soft start) | 
| response delay maximum | 1.5 s | 
| voltage increase time of the output voltage | |
| ● typical | 50 ms | 
| ● maximum | 500 ms | 
| output current | |
| ● rated value | 20 A | 
| ● rated rangesupplied active power typical short-term overload current | 0 … 20 A; 24 A up to +45°C; +60 … +70 °C: Derating 5%/K | 
| supplied active power typical | 480 W | 
| short-term overload current | |
| ● on short-circuiting during the start-up typical | 35 A | 
| ● at short-circuit during operation typical | 35 A | 
| duration of overloading capability for excess current | |
| ● on short-circuiting during the start-up typical | 100 ms | 
| ● at short-circuit during operation | 100 ms | 
| product feature | |
| ● bridging of equipment | Yes | 
| number of parallel-switched equipment resources for increasing the power | 2 | 
| Efficiency | |
| efficiency in percent | 90% | 
| power loss [W] | 53 W | 
| ● at rated output voltage for rated value of the output current typical | |
| Closed-loop control | |
| relative control precision of the output voltage with rapid fluctuation of the input voltage by +/- 15% typical | 1% | 
| relative control precision of the output voltage load step of resistive load 50/100/50 % typical | 3% | 
| setting time | 10 ms | 
| ● maximum | |
| Protection and monitoring | |
| design of the overvoltage protection | Yes, according to EN 60950-1 | 
| response value current limitation typical | 21 A | 
| property of the output short-circuit proof | Yes | 
| design of short-circuit protection | Electronic shutdown, automatic restart | 
| enduring short circuit current RMS value | 7:00 AM | 
| ● maximum | |
| overcurrent overload capability in normal operation | overload capability 150 % Iout rated up to 5 s/min | 
| display version for overload and short circuit | – | 
| Safety | |
| galvanic isolation between input and output | Yes | 
| galvanic isolation | Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 | 
| operating resource protection class | Class I | 
| leakage current | 3.5 mA | 
| ● maximum | |
| ● typical | 1 mA | 
| protection class IP | IP20 | 
| Approvals | |
| certificate of suitability | Yes | 
| ● CE marking | |
| ● UL approval | Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1) | 
| ● CSA approval | Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259, cCSAus (CSA C22.2 No. 60950-1, UL 60950-1) | 
| ● cCSAus, Class 1, Division 2 | No | 
| ● ATEX | No | 
| certificate of suitability | No | 
| ● IECEx | |
| ● NEC Class 2 | No | 
| ● ULhazloc approval | No | 
| ● FM registration | No | 
| type of certification CB-certificate | Yes | 
| certificate of suitability | |
| ● EAC approval | Yes | 
| certificate of suitability shipbuilding approval | Yes | 
| shipbuilding approval | DNV GL | 
| Marine classification association | |
| ● American Bureau of Shipping Europe Ltd. (ABS) | No | 
| ● French marine classification society (BV) | No | 
| ● DNV GL | Yes | 
| ● Lloyds Register of Shipping (LRS) | No | 
| ● Nippon Kaiji Kyokai (NK) | No | 
| EMC | |
| standard | EN 55022 Class B | 
| ● for emitted interference | |
| ● for mains harmonics limitation | EN 61000-3-2 | 
| ● for interference immunity | EN 61000-6-2 | 
| environmental conditions | |
| ambient temperature | 0 … 70 °C; with natural convection | 
| ● during operation | |
| ● during transport | -40 … +85 °C | 
| ● during storage | -40 … +85 °C | 
| environmental category according to IEC 60721 | Climate class 3K3, 5 … 95% no condensation | 
| Mechanics | |
| type of electrical connection | screw-type terminals | 
| ● at input | L1, N, PE: 1 screw terminal each for 0.2 … 4 mm² single-core/finely stranded | 
| ● at output | +, -: 2 screw terminals each for 0.2 … 4 mm² | 
| ● for auxiliary contacts | 13, 14 (alarm signal): 1 screw terminal each for 0.14 … 1.5 mm² | 
| width of the enclosure | 115 mm | 
| height of the enclosure | 145 mm | 
| depth of the enclosure | 150 mm | 
| required spacing | 50 mm | 
| ● top | |
| ● bottom | 50 mm | 
| ● left | 0 mm | 
| ● right | 0 mm | 
| net weight | 2.4 kg | 
| product feature of the enclosure housing can be lined up | Yes | 
| fastening method | Snaps onto DIN rail EN 60715 35×7.5/15 | 
| electrical accessories | Buffer module | 
| mechanical accessories | Device identification label 20 mm × 7 mm, pale turquoise 3RT19001SB20 | 
| MTBF at 40 °C | 1 778 916 h | 
| other information | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) |