$ 184.00
| input | |
| type of the power supply network | DC voltage |
| supply voltage at DC | 12 … 48 V |
| input voltage at DC | 10 … 58 V |
| output | |
| voltage curve at output | Controlled DC voltage |
| number of outputs | 1 |
| output voltage at DC rated value | 24 V |
| formula for output voltage | Vin – approx. 0.6 V |
| output voltage | |
| ● at output 1 at DC rated value | 24 V |
| output voltage adjustable | No |
| output current | |
| ● rated value | 40 A |
| bridging of equipment | No |
| efficiency | |
| efficiency in percent | 97.5 % |
| power loss [W] | |
| ● at rated output voltage for rated value of the output current typical |
25 W |
| ● during no-load operation maximum | 0.1 W |
| safety | |
| galvanic isolation between input and output | No |
| operating resource protection class | Class III |
| protection class IP | IP20 |
| EMC | |
| standard | |
| ● for emitted interference | EN 61000-6-3 |
| ● for interference immunity | EN 61000-6-2 |
| standards, specifications, approvals | |
| certificate of suitability | |
| ● CE marking | Yes |
| ● UL approval | Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259 |
| ● CSA approval | Yes; CSA C22.2 No. 62368-1 |
| ● NEC Class 2 | No |
| MTBF at 40 °C | 6 100 000 h |
| standards, specifications, approvals hazardous environments | |
| certificate of suitability | |
| ● IECEx | No |
| ● ATEX | No |
| ● ULhazloc approval | No |
| ● cCSAus, Class 1, Division 2 | No |
| ● FM registration | No |
| standards, specifications, approvals marine classification | |
| shipbuilding approval | No |
| Marine classification association | |
| ● American Bureau of Shipping Europe Ltd. (ABS) | No |
| ● French marine classification society (BV) | No |
| ● Det Norske Veritas (DNV) | No |
| ● Lloyds Register of Shipping (LRS) | No |
| standards, specifications, approvals Environmental Product Declaration | |
| Environmental Product Declaration | Yes |
| global warming potential [CO2 eq] | |
| ● total | 805.5 kg |
| ● during manufacturing | 51.1 kg |
| ● during operation | 1 051.5 kg |
| ● after end of life | 0.81 kg |
| ambient conditions | |
| ambient temperature | |
| ● during operation | -40 … +70; with natural convection |
| ● during transport | -40 … +85 |
| ● during storage | -40 … +85 |
| environmental category according to IEC 60721 | Climate class 3K3, 5 … 95% no condensation |
| connection method | |
| type of electrical connection | push-in terminals |
| ● at input | In1, In2: each for 0.75 … 16 mm² |
| ● at output | Out1: 0.75 … 16 mm² |
| mechanical data | |
| width × height × depth of the enclosure | 45 × 135 × 125 mm |
| installation width × mounting height | 45 mm × 225 mm |
| required spacing | |
| ● top | 45 mm |
| ● bottom | 45 mm |
| ● left | 0 mm |
| ● right | 0 mm |
| fastening method | Snaps onto DIN rail EN 60715 35×7.5/15 |
| ● DIN-rail mounting | Yes |
| ● S7 rail mounting | No |
| ● wall mounting | No |
| housing can be lined up | Yes |
| net weight | 0.51 kg |