			$ 72.45
| input | |
| type of the power supply network | 1-phase AC or DC | 
| supply voltage at AC | |
| ● minimum rated value | 100 V | 
| ● maximum rated value | 230 V | 
| ● initial value | 85 V | 
| ● full-scale value | 264 V | 
| input voltage at DC | 110 … 300 V | 
| wide range input | Yes | 
| overvoltage overload capability | 2.3 × Vin rated, 1.3 ms | 
| buffering time for rated value of the output current in the event of power failure minimum | 20 ms | 
| operating condition of the mains buffering | at Vin = 230 V | 
| line frequency | 50/60 Hz | 
| line frequency | 47 … 63 Hz | 
| input current | |
| ● at rated input voltage 100 V | 0.28 A | 
| ● at rated input voltage 230 V | 0.18 A | 
| current limitation of inrush current at 25 °C maximum | 28 A | 
| I2t value maximum | 0.7 A²·s | 
| fuse protection type | internal | 
| fuse protection type in the feeder | Recommended miniature circuit breaker: from 16 A characteristic B or from 10 A characteristic C | 
| output | |
| voltage curve at output | Controlled, isolated DC voltage | 
| output voltage at DC rated value | 24 V | 
| output voltage | |
| ● at output 1 at DC rated value | 24 V | 
| output voltage adjustable | No; – | 
| relative overall tolerance of the voltage | 3 % | 
| relative control precision of the output voltage | |
| ● on slow fluctuation of input voltage | 0.1 % | 
| ● on slow fluctuation of ohm loading | 0.2 % | 
| residual ripple | |
| ● maximum | 200 mV | 
| ● typical | 40 mV | 
| voltage peak | |
| ● maximum | 300 mV | 
| ● typical | 20 mV | 
| display version for normal operation | Green LED for output voltage OK | 
| behavior of the output voltage when switching on | Overshoot of Vout approx. 5 % | 
| response delay maximum | 1 s | 
| voltage increase time of the output voltage | |
| ● typical | 25 ms | 
| output current | |
| ● rated value | 0.6 A | 
| ● rated range | 0 … 0.6 A | 
| supplied active power typical | 14 W | 
| short-term overload current | |
| ● at short-circuit during operation typical | 1 A | 
| bridging of equipment | No | 
| efficiency | |
| efficiency in percent | 82 % | 
| power loss [W] | |
| ● at rated output voltage for rated value of the output current typical | 2.6 W | 
| ● during no-load operation maximum | 0.75 W | 
| closed-loop control | |
| relative control precision of the output voltage with rapid fluctuation of the input voltage by +/- 15% typical | 0.1 % | 
| relative control precision of the output voltage at load step of resistive load 10/90/10 % typical | 3 % | 
| setting time | |
| ● load step 10 to 90% typical | 3 ms | 
| ● load step 90 to 10% typical | 3 ms | 
| protection and monitoring | |
| design of the overvoltage protection | Yes, according to EN 60950-1 | 
| property of the output short-circuit proof | Yes | 
| design of short-circuit protection | Electronic shutdown, automatic restart | 
| ● typical | 0.7 A | 
| safety | |
| galvanic isolation between input and output | Yes | 
| galvanic isolation | Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 | 
| operating resource protection class | Class I | 
| leakage current | |
| ● maximum | 3.5 mA | 
| ● typical | 0.4 mA | 
| protection class IP | IP20 | 
| EMC | |
| standard | |
| ● for emitted interference | EN 55022 Class B | 
| ● for mains harmonics limitation | not applicable | 
| ● for interference immunity | EN 61000-6-2 | 
| standards, specifications, approvals | |
| certificate of suitability | |
| ● CE marking | Yes | 
| ● UL approval | Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURus- Recognized (UL 60950, CSA C22.2 No. 60950), File E151273, NEC class 2 (acc. to UL 1310) | 
| ● CSA approval | Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURus- Recognized (UL 60950, CSA C22.2 No. 60950), File E151273, NEC class 2 (acc. to UL 1310) | 
| ● EAC approval | Yes | 
| ● NEC Class 2 | Yes; according to UL1310, File E151273 | 
| type of certification | |
| ● CB-certificate | Yes | 
| MTBF at 40 °C | 3 910 833 h | 
| standards, specifications, approvals hazardous environments | |
| certificate of suitability | |
| ● IECEx | No | 
| ● ATEX | No | 
| ● ULhazloc approval | No | 
| ● cCSAus, Class 1, Division 2 | No | 
| ● FM registration | No | 
| standards, specifications, approvals marine classification | |
| shipbuilding approval | Yes | 
| Marine classification association | |
| ● American Bureau of Shipping Europe Ltd. (ABS) | Yes | 
| ● French marine classification society (BV) | No | 
| ● Det Norske Veritas (DNV) | Yes | 
| ● Lloyds Register of Shipping (LRS) | No | 
| standards, specifications, approvals Environmental Product Declaration | |
| Environmental Product Declaration | Yes | 
| global warming potential [CO2 eq] | |
| ● total | 73.5 kg | 
| ● during manufacturing | 2.3 kg | 
| ● during operation | 71.1 kg | 
| ● after end of life | 0.08 kg | 
| ambient conditions | |
| ambient temperature | |
| ● during operation | -20 … +70; with natural convection | 
| ● during transport | -40 … +85 | 
| ● during storage | -40 … +85 | 
| environmental category according to IEC 60721 | Climate class 3K3, 5 … 95% no condensation | 
| connection method | |
| type of electrical connection | screw terminal | 
| ● at input | L, N, PE: Removable screw terminal, each for 1 x 0.5 … 2.5 mm² | 
| ● at output | +: 1 screw terminal for 0.5 … 2.5 mm²; -: 2 screw terminals for 0.5 … 2.5 mm² | 
| ● for auxiliary contacts | – | 
| mechanical data | |
| width × height × depth of the enclosure | 22.5 × 80 × 100 mm | 
| installation width × mounting height | 22.5 mm × 180 mm | 
| required spacing | |
| ● top | 50 mm | 
| ● bottom | 50 mm | 
| ● left | 0 mm | 
| ● right | 0 mm | 
| fastening method | Snaps onto DIN rail EN 60715 35×7.5/15 | 
| ● DIN-rail mounting | Yes | 
| ● S7 rail mounting | No | 
| ● wall mounting | No | 
| housing can be lined up | Yes | 
| net weight | 0.12 kg | 
| accessories | |
| electrical accessories | Removable spring-type terminal 6EP1971-5BA00 |