$ 961.17 – $ 1,175.07Price range: $ 961.17 through $ 1,175.07
The SIRIUS modular system with its components for the switching, starting, protection and monitoring of motors and industrial systems stands for the fast, flexible and space-saving construction of control cabinets.
| Article Number | 3RT1054-6AP36
3RT1054-1AP36 |
| product brand name | SIRIUS |
| product designation | Power contactor |
| product type designation | 3RT1 |
| General technical data | |
| size of contactor | S6 |
| product extension | |
| ● function module for communication | No |
| ● auxiliary switch | Yes |
| power loss [W] for rated value of the current | |
| ● at AC in hot operating state | 21 W |
| ● at AC in hot operating state per pole | 7 W |
| ● without load current share typical | 5.2 W |
| insulation voltage | |
| ● of main circuit with degree of pollution 3 rated value | 1 000 V |
| ● of auxiliary circuit with degree of pollution 3 rated value | 500 V |
| surge voltage resistance | |
| ● of main circuit rated value | 8 kV |
| ● of auxiliary circuit rated value | 6 kV |
| maximum permissible voltage for safe isolation between | 690 V |
| coil and main contacts according to EN 60947-1 | |
| shock resistance at rectangular impulse | |
| ● at AC | 8,5g / 5 ms, 4,2g / 10 ms |
| ● at DC | 8,5g / 5 ms, 4,2g / 10 ms |
| shock resistance with sine pulse | |
| ● at AC 13,4g / 5 ms, 6,5g / 10 ms | 13,4g / 5 ms, 6,5g / 10 ms |
| ● at DC 13,4g / 5 ms, 6,5g / 10 ms | 13,4g / 5 ms, 6,5g / 10 ms |
| mechanical service life (switching cycles) | |
| ● of contactor typical | 10 000 000 |
| ● of the contactor with added electronically optimized | 5 000 000 |
| auxiliary switch block typical | |
| ● of the contactor with added auxiliary switch block | 10 000 000 |
| typical | |
| reference code according to IEC 81346-2 | Q |
| Substance Prohibitance (Date) | 5/1/2012 |
| Ambient conditions | |
| installation altitude at height above sea level maximum | 2 000 m |
| ambient temperature | |
| ● during operation | -25 … +60 °C |
| ● during storage | -55 … +80 °C |
| relative humidity minimum | 10% |
| relative humidity at 55 °C according to IEC 60068-2-30 maximum | 95% |
| Article Number | 3RT1055-6AP36 |
| product brand name | SIRIUS |
| product designation | Power contactor |
| product type designation | 3RT1 |
| General technical data | |
| size of contactor | S6 |
| product extension | |
| ● function module for communication | No |
| ● auxiliary switch | Yes |
| power loss [W] for rated value of the current | |
| ● at AC in hot operating state | 21 W |
| ● at AC in hot operating state per pole | 7 W |
| ● without load current share typical | 5.2 W |
| insulation voltage | |
| ● of main circuit with degree of pollution 3 rated value | 1 000 V |
| ● of auxiliary circuit with degree of pollution 3 rated value | 500 V |
| surge voltage resistance | |
| ● of main circuit rated value | 8 kV |
| ● of auxiliary circuit rated value | 6 kV |
| maximum permissible voltage for safe isolation between | 690 V |
| coil and main contacts according to EN 60947-1 | |
| shock resistance at rectangular impulse | |
| ● at AC | 8,5g / 5 ms, 4,2g / 10 ms |
| ● at DC | 8,5g / 5 ms, 4,2g / 10 ms |
| shock resistance with sine pulse | |
| ● at AC 13,4g / 5 ms, 6,5g / 10 ms | 13,4g / 5 ms, 6,5g / 10 ms |
| ● at DC 13,4g / 5 ms, 6,5g / 10 ms | 13,4g / 5 ms, 6,5g / 10 ms |
| mechanical service life (switching cycles) | |
| ● of contactor typical | 10 000 000 |
| ● of the contactor with added electronically optimized | 5 000 000 |
| auxiliary switch block typical | 10 000 000 |
| ● of the contactor with added auxiliary switch block | Q |
| typical | |
| reference code according to IEC 81346-2 | |
| Substance Prohibitance (Date) | 5/1/2012 |
| Ambient conditions | |
| installation altitude at height above sea level maximum | 2 000 m |
| ambient temperature | |
| ● during operation | -25 … +60 °C |
| ● during storage | -55 … +80 °C |
| relative humidity minimum | 10% |
| relative humidity at 55 °C according to IEC 60068-2-30 maximum | 95% |