$ 1,479.06
Part Number | 6ES7326-2BF01-0AB0 |
Supply voltage | |
Rated value (DC) | 24 V; 1L+ |
Reverse polarity protection | Yes |
Load voltage L+ | |
● Rated value (DC) | 24 V; 2L+, 3L+ |
● Reverse polarity protection | No |
Input current | |
from supply voltage 1L+, max. | 70 mA |
from load voltage 2L+ (without load), max. | 100 mA |
from load voltage 3L+ (without load), max. | 100 mA |
from backplane bus 5 V DC, max. | 100 mA |
Power loss | |
Power loss, typ. | 12 W |
Digital outputs | |
Number of digital outputs | 10 |
Short-circuit protection | Yes |
Limitation of inductive shutdown voltage to | L+ (-53 V) without series diode, L+ (-33 V) with series diode |
Switching capacity of the outputs | |
● on lamp load, max. | 5 W |
Output voltage | |
● for signal “1”, min. | L+ (-1 V) without series diode, L+ (-1.8 V) with series diode |
Output current | |
● for signal “1” rated value | 2 A 7 mA |
● for signal “1” permissible range for 0 to 40 °C, min. | |
● for signal “1” permissible range for 0 to 40 °C, max. | 2 A; 2 A for horizontal installation, 1 A for vertical installation |
● for signal “1” permissible range for 40 to 60 °C, min. | 7 mA |
● for signal “1” permissible range for 40 to 60 °C, max. | 1 A; for horizontal installation |
● for signal “0” residual current, max. | 0.5 mA |
Switching frequency | |
● with resistive load, max. | 10 Hz |
● with inductive load, max. | 2 Hz |
● on lamp load, max. | 10 Hz |
Total current of the outputs (per group) | |
horizontal installation | |
— up to 40 °C, max. | 7.5 A; without series diode, 5 A with series diode |
— up to 60 °C, max. | 5 A; without series diode, 4 A with series diode |
vertical installation | |
— up to 40 °C, max. | 5 A; without series diode, 4 A with series diode |
Cable length | |
● shielded, max. | 1 000 m; 200 m for SIL 3, AK 6, Cat 4 |
● unshielded, max. | 600 m |
Interrupts/diagnostics/status information | |
Alarms | |
● Diagnostic alarm | Yes |
Diagnoses | |
● Diagnostic information readable | Yes |
Diagnostics indication LED | |
● Fail-safe operation | Yes |
● Group error SF (red) | Yes |
Potential separation | |
Potential separation digital outputs | |
● between the channels | Yes |
● between the channels, in groups of | 5 |
● between the channels and backplane bus | Yes |
● between the channels and the power supply of the electronics | Yes |
Isolation | |
Isolation tested with | 500 V DC/350 V AC |
Standards, approvals, certificates | |
Highest safety class achievable in safety mode | |
● acc. to DIN VDE 0801 | AK 5 and 6 |
● acc. to EN 954 | Cat. 4 |
● Performance level according to ISO 13849-1 | e |
● SIL acc. to IEC 61508 | SIL 3 |
connection method / header | |
required front connector | 40-pin |
Dimensions | |
Width | 80 mm |
Height | 125 mm |
Depth | 120 mm |
Weights | |
Weight, approx. | 465 g |
Weight | 0.532 kg |
---|---|
Dimensions | 13.2 × 15.5 × 8.9 cm |
INOSAKI Limited
RM B 5/F Gaylord Comm,
Bldg 114-118 Lockhart Rd.
Hong Kong
INOSAKI Sdn. Bhd.
2-1-9, Ground Floor, One Square, Tingkat Mahsuri 1,
11900 Bayan Lepas, Penan
INOSAKI Pte. Ltd.
101 Upper Cross Street,
No. 06-17, People’s Park Centre,
Singapore (058357)