SIMATIC S7-300 – FM 355-2 Temperature Controller Modules – Siemens Function Modules
$ 687.87 – $ 869.23
SKU: N/A
The FM 355-2 closed-loop control module is the intelligent 4-channel temperature control module.
Article number | 6ES7355-2CH00-0AE0 | 6ES7355-2SH00-0AE0 |
TEMP.-Control unit FM355-2C, 4 chan. | TEMP.-Control unit FM355-2S, 4 chan. | |
Supply voltage | ||
Load voltage L+ | ||
● Rated value (DC) | 24 V | 24 V |
● permissible range, lower limit (DC) | 20.4 V | 20.4 V |
● permissible range, upper limit (DC) | 28.8 V | 28.8 V |
Input current | ||
from load voltage L+ (without load), max. | 310 mA; Typ. 260 mA | 270 mA; typ. 220 mA |
from backplane bus 5 V DC, max. | 75 mA; typ. 50 mA | 75 mA; typ. 50 mA |
Power loss | ||
Power loss, typ. | 6.5 W | 5.5 W |
Power loss, max. | 7.8 W | 6.9 W |
Digital inputs | ||
Number of digital inputs | 8 | 8 |
Input characteristic curve in accordance with IEC 61131, type 2 | Yes | Yes |
Input voltage | ||
● Rated value (DC) | 24 V | 24 V |
● for signal “0” | -3 to +5V | -3 to +5V |
● for signal “1” | 13 to 30V | 13 to 30V |
Input current | ||
● for signal “1”, typ. | 7 mA | 7 mA |
Cable length | ||
● shielded, max. | 1 000 m | 1 000 m |
● unshielded, max. | 600 m | 600 m |
Digital outputs | ||
Number of digital outputs | 8 | |
Short-circuit protection | Yes; Electronic | |
Limitation of inductive shutdown voltage to | L+ (-1.5 V) | |
Controlling a digital input | Yes | |
Switching capacity of the outputs | ||
● on lamp load, max. | 5 W | |
Load resistance range | ||
● lower limit | 240 Ω | |
● upper limit | 4 kΩ | |
Output voltage | ||
● for signal “1”, min. | L+ (-2.5 V) | |
Output current | ||
● for signal “1” rated value | 0.1 A | |
● for signal “1” permissible range for 0 to 60 °C, min. | 5 mA | |
● for signal “1” permissible range for 0 to 60 °C, max. | 150 mA | |
● for signal “0” residual current, max. | 0.5 mA | |
Parallel switching of two outputs | ||
● for logic links | Yes | |
Switching frequency | ||
● with resistive load, max. | 100 Hz | |
● with inductive load, max. | 0.5 Hz | |
● on lamp load, max. | 100 Hz | |
Total current of the outputs (per group) | ||
all mounting positions | ||
— up to 60 °C, max. | 400 mA | |
Cable length | ||
● shielded, max. | 1 000 m | |
● unshielded, max. | 600 m | |
Analog inputs | ||
Number of analog inputs | 4 | 4 |
permissible input voltage for voltage input (destruction limit), max. | 20 V | 20 V |
permissible input current for current input (destruction limit), max. | 40 mA | 40 mA |
Input ranges | ||
● Voltage | Yes | Yes |
● Current | Yes | Yes |
● Thermocouple | Yes | Yes |
● Resistance thermometer | Yes | Yes |
Input ranges (rated values), voltages | ||
● 0 to +10 V | Yes | Yes |
— Input resistance (0 to 10 V) | 100 kΩ | 100 kΩ |
● -1.75 V to +11.75 V | Yes | Yes |
— Input resistance (-1.75 V to +11.75 V) | 100 kΩ | 100 kΩ |
Input ranges (rated values), currents | ||
● 0 to 20 mA | Yes | Yes |
— Input resistance (0 to 20 mA) | 50 Ω | 50 Ω |
● 0 to 23.5 mA | Yes | Yes |
— Input resistance (0 to 23.5 mA) | 50 Ω | 50 Ω |
● -3.5 mA to +23.5 mA | Yes | Yes |
— Input resistance (-3.5 mA to +23.5 mA) | 50 Ω | 50 Ω |
● 4 mA to 20 mA | Yes | Yes |
— Input resistance (4 mA to 20 mA) | 50 Ω | 50 Ω |
Input ranges (rated values), thermocouples | ||
● Type B | Yes | Yes |
— Input resistance (Type B) | 10 MΩ | 10 MΩ |
● Type E | Yes | Yes |
— Input resistance (Type E) | 10 MΩ | 10 MΩ |
● Type J | Yes | Yes |
— Input resistance (type J) | 10 MΩ | 10 MΩ |
● Type K | Yes | Yes |
— Input resistance (Type K) | 10 MΩ | 10 MΩ |
● Type R | Yes | Yes |
— Input resistance (Type R) | 10 MΩ | 10 MΩ |
● Type S | Yes | Yes |
— Input resistance (Type S) | 10 MΩ | 10 MΩ |
Input ranges (rated values), resistance thermometer | ||
● Pt 100 | Yes | Yes |
— Input resistance (Pt 100) | 10 MΩ | 10 MΩ |
Thermocouple (TC) | ||
Temperature compensation | ||
— internal temperature compensation | Yes | Yes |
— external temperature compensation with Pt100 | Yes | Yes |
Characteristic linearization | ||
● parameterizable | Yes | Yes |
— for thermocouples | Type B, E, J, K, R, S | Type B, E, J, K, R, S |
— for resistance thermometer | Pt100 (standard) | Pt100 (standard) |
Cable length | ||
● shielded, max. | 200 m; 50 m at 80 mV and thermocouples | 200 m; 50 m at 80 mV and thermocouples |
Analog outputs | ||
Number of analog outputs | 4 | |
Voltage output, short-circuit protection | Yes | |
Voltage output, short-circuit current, max. | 25 mA | |
Current output, no-load voltage, max. | 18 V | |
Output ranges, voltage | ||
● 0 to 10 V | Yes | |
● -10 V to +10 V | Yes | |
Output ranges, current | ||
● 0 to 20 mA | Yes | |
● 4 mA to 20 mA | Yes | |
Connection of actuators | ||
● for voltage output two-wire connection | Yes | |
● for current output two-wire connection | Yes | |
Load impedance (in rated range of output) | ||
● with voltage outputs, min. | 1 kΩ | |
● with voltage outputs, capacitive load, max. | 1 µF | |
● with current outputs, max. | 500 Ω | |
● with current outputs, inductive load, max. | 1 mH | |
Cable length | ||
● shielded, max. | 200 m; 50 m at 80 mV and thermocouples | |
Analog value generation for the inputs | ||
Integration and conversion time/resolution per channel | ||
● Resolution with overrange (bit including sign), max. | 14 bit | 14 bit |
Analog value generation for the outputs | ||
Settling time | ||
● for resistive load | 0.1 ms | |
● for capacitive load | 3.3 ms | |
● for inductive load | 0.5 ms | |
Encoder | ||
Connection of signal encoders | ||
● for voltage measurement | Yes | Yes |
● for current measurement as 4-wire transducer | Yes | Yes |
Connectable encoders | ||
● 2-wire sensor | Yes | Yes |
— permissible quiescent current (2-wire sensor), max. | 1.5 mA | 1.5 mA |
Errors/accuracies | ||
Operational error limit in overall temperature range | ||
● Voltage, relative to input range, (+/-) | 0.6 %; ±0.6 to ±0.7 % | 0.06 %; ±0.06 to ±0.7% |
● Current, relative to input range, (+/-) | 0.6 %; ±0.6 to ±0.7 % | 0.06 %; ±0.06 to ±0.7% |
● Resistance thermometer, relative to input range, (+/-) | 0.6 %; ±0.6 to ±0.7 % | 0.06 %; ±0.06 to ±0.7% |
● Voltage, relative to output range, (+/-) | 0.5 % | |
● Current, relative to output range, (+/-) | 0.6 % | |
Basic error limit (operational limit at 25 °C) | ||
● Voltage, relative to input range, (+/-) | 0.04 %; ±0.04 to ±0.5 % | 0.04 %; ±0.04 to ±0.5 % |
● Current, relative to input range, (+/-) | 0.04 %; ±0.04 to ±0.5 % | 0.04 %; ±0.04 to ±0.5 % |
● Resistance thermometer, relative to input range, (+/-) | 0.04 %; ±0.04 to ±0.5 % | 0.04 %; ±0.04 to ±0.5 % |
● Voltage, relative to output range, (+/-) | 0.4 % | |
● Current, relative to output range, (+/-) | 0.5 % | |
Interrupts/diagnostics/status information | ||
Substitute values connectable | Yes; Parameterizable | Yes; Parameterizable |
Integrated Functions | ||
Counter | No | No |
Control technology | ||
● Number of closed-loop controllers | 4 | 4 |
Potential separation | ||
Potential separation controller | ||
● between the channels | No | No |
● between the channels and backplane bus | Yes; Optocoupler | Yes; Optocoupler |
Isolation | ||
Isolation tested with | 500 V DC | 500 V DC |
connection method / header | ||
required front connector | 2x 20-pin | 2x 20-pin |
Dimensions | ||
Width | 80 mm | 80 mm |
Height | 125 mm | 125 mm |
Depth | 120 mm | 120 mm |
Weights | ||
Weight, approx. | 470 g | 470 g |
Weight | N/A |
---|---|
Dimensions | N/A |
Related products
-
Select options This product has multiple variants. The options may be chosen on the product page Details
-
Select options This product has multiple variants. The options may be chosen on the product page Details
-
Select options This product has multiple variants. The options may be chosen on the product page Details
-
Select options This product has multiple variants. The options may be chosen on the product page Details
-
Select options This product has multiple variants. The options may be chosen on the product page Details