SIMATIC S7-300 – CPU 317-2 PN/DP – Siemens PLC
$ 3,441.24
SKU: 6ES7317-2EK14-0AB0
The CPU 317-2 PN/DP is a CPU with a large program memory. It is used in installations which have distributed automation structures in addition to a centralized I/O. It can be used, for example, as a central controller in production lines or as a machine controller with stringent requirements on machining speed.
Siemens PLC S7-300 Product Specifications:
Article number | 6ES7317-2EK14-0AB0 | |
CPU317-2 PN/DP, 1 MB | ||
General information | ||
HW functional status | 1 | |
Firmware version | V3.2 | |
Product function | ||
● Isochronous mode | Yes; Via PROFIBUS DP or PROFINET interface | |
Engineering with | ||
● Programming package | STEP 7 V5.5 or higher | |
Supply voltage | ||
Rated value (DC) | 24 V | |
permissible range, lower limit (DC) | 20.4 V | |
permissible range, upper limit (DC) | 28.8 V | |
external protection for power supply lines (recommendation) | 2 A min. | |
Mains buffering | ||
● Mains/voltage failure stored energy time | 5 ms | |
● Repeat rate, min. | 1 s | |
Input current | ||
Current consumption (rated value) | 750 mA | |
Current consumption (in no-load operation), typ. | 150 mA | |
Inrush current, typ. | 4 A | |
I²t | 1 A²·s | |
Power loss | ||
Power loss, typ. | 4.65 W | |
Memory | ||
Work memory | ||
● integrated | 1 024 kbyte | |
● expandable | No | |
Load memory | ||
● Plug-in (MMC) | Yes | |
● Plug-in (MMC), max. | 8 Mbyte | |
● Data management on MMC (after last programming), min. | 10 y | |
Backup | ||
● present | Yes; Guaranteed by MMC (maintenance-free) | |
● without battery | Yes; Program and data | |
CPU processing times | ||
for bit operations, typ. | 0.025 µs | |
for word operations, typ. | 0.03 µs | |
for fixed point arithmetic, typ. | 0.04 µs | |
for floating point arithmetic, typ. | 0.16 µs | |
CPU-blocks | ||
Number of blocks (total) | 2 048; (DBs, FCs, FBs); the maximum number of loadable blocks can be reduced by the MMC used. | |
DB | ||
● Number, max. | 2 048; Number range: 1 to 16000 | |
● Size, max. | 64 kbyte | |
FB | ||
● Number, max. | 2 048; Number range: 0 to 7999 | |
● Size, max. | 64 kbyte | |
FC | ||
● Number, max. | 2 048; Number range: 0 to 7999 | |
● Size, max. | 64 kbyte | |
OB | ||
● Size, max. | 64 kbyte | |
● Number of free cycle OBs | 1; OB 1 | |
● Number of time alarm OBs | 1; OB 10 | |
● Number of delay alarm OBs | 2; OB 20, 21 | |
● Number of cyclic interrupt OBs | 4; OB 32, 33, 34, 35 | |
● Number of process alarm OBs | 1; OB 40 | |
● Number of DPV1 alarm OBs | 3; OB 55, 56, 57 | |
● Number of isochronous mode OBs | 1; OB 61 – isochronous mode is possible either on DP or PROFINET IO (not simultaneously) | |
● Number of startup OBs | 1; OB 100 | |
● Number of asynchronous error OBs | 6; OB 80, 82, 83, 85, 86, 87 (OB83 only for PROFINET IO) | |
● Number of synchronous error OBs | 2; OB 121, 122 | |
Nesting depth | ||
● per priority class | 16 | |
● additional within an error OB | 4 | |
Counters, timers and their retentivity | ||
S7 counter | ||
● Number | 512 | |
Retentivity | ||
— adjustable | Yes | |
— lower limit | 0 | |
— upper limit | 511 | |
— preset | Z 0 to Z 7 | |
Counting range | ||
— adjustable | Yes | |
— lower limit | 0 | |
— upper limit | 999 | |
IEC counter | ||
● present | Yes | |
● Type | SFB | |
● Number | Unlimited (limited only by RAM capacity) | |
S7 times | ||
● Number | 512 | |
Retentivity | ||
— adjustable | Yes | |
— lower limit | 0 | |
— upper limit | 511 | |
— preset | No retentivity | |
Time range | ||
— lower limit | 10 ms | |
— upper limit | 9 990 s | |
IEC timer | ||
● present | Yes | |
● Type | SFB | |
● Number | Unlimited (limited only by RAM capacity) | |
Data areas and their retentivity | ||
Retentive data area (incl. timers, counters, flags), max. | 256 kbyte | |
Flag | ||
● Size, max. | 4 096 byte | |
● Retentivity available | Yes; From MB 0 to MB 4 095 | |
● Retentivity preset | MB 0 to MB 15 | |
● Number of clock memories | 8; 1 memory byte | |
Data blocks | ||
● Retentivity adjustable | Yes; via non-retain property on DB | |
● Retentivity preset | Yes | |
Local data | ||
● per priority class, max. | 32 768 byte; Max. 2048 bytes per block | |
Address area | ||
I/O address area | ||
● Inputs | 8 192 byte | |
● Outputs | 8 192 byte | |
of which distributed | ||
— Inputs | 8 192 byte | |
— Outputs | 8 192 byte | |
Process image | ||
● Inputs | 8 192 byte | |
● Outputs | 8 192 byte | |
● Inputs, adjustable | 8 192 byte | |
● Outputs, adjustable | 8 192 byte | |
● Inputs, default | 256 byte | |
● Outputs, default | 256 byte | |
Subprocess images | ||
● Number of subprocess images, max. | 1; With PROFINET IO, the length of the user data is limited to 1600 bytes | |
Digital channels | ||
● Inputs | 65 536 | |
— of which central | 1 024 | |
● Outputs | 65 536 | |
— of which central | 1 024 | |
Analog channels | ||
● Inputs | 4 096 | |
— of which central | 256 | |
● Outputs | 4 096 | |
— of which central | 256 | |
Hardware configuration | ||
Number of expansion units, max. | 3 | |
Number of DP masters | ||
● integrated | 1 | |
● via CP | 4 | |
Number of operable FMs and CPs (recommended) | ||
● FM | 8 | |
● CP, PtP | 8 | |
● CP, LAN | 10 | |
Rack | ||
● Racks, max. | 4 | |
● Modules per rack, max. | 8 | |
Time of day | ||
Clock | ||
● Hardware clock (real-time) | Yes | |
● retentive and synchronizable | Yes | |
● Backup time | 6 wk; At 40 °C ambient temperature | |
● Deviation per day, max. | 10 s; Typ.: 2 s | |
● Behavior of the clock following POWER-ON | Clock continues running after POWER OFF | |
● Behavior of the clock following expiry of backup period | the clock continues at the time of day it had when power was switched off | |
Operating hours counter | ||
● Number | 4 | |
● Number/Number range | 0 to 3 | |
● Range of values | 0 to 2^31 hours (when using SFC 101) | |
● Granularity | 1 h | |
● retentive | Yes; Must be restarted at each restart | |
Clock synchronization | ||
● supported | Yes | |
● to MPI, master | Yes | |
● to MPI, slave | Yes | |
● to DP, master | Yes; With DP slave only slave clock | |
● to DP, slave | Yes | |
● in AS, master | Yes | |
● in AS, slave | Yes | |
● on Ethernet via NTP | Yes; As client | |
Digital inputs | ||
Number of digital inputs | 0 | |
Digital outputs | ||
Number of digital outputs | 0 | |
Analog inputs | ||
Number of analog inputs | 0 | |
Analog outputs | ||
Number of analog outputs | 0 | |
Interfaces | ||
Number of industrial Ethernet interfaces | 1; 2 ports (switch) RJ45 | |
Number of PROFINET interfaces | 1; 2 ports (switch) RJ45 | |
Number of RS 485 interfaces | 1; Combined MPI / PROFIBUS DP | |
Number of RS 422 interfaces | 0 | |
1. Interface | ||
Interface type | Integrated RS 485 interface | |
Isolated | Yes | |
Interface types | ||
● RS 485 | Yes | |
● Output current of the interface, max. | 200 mA | |
Protocols | ||
● MPI | Yes | |
● PROFIBUS DP master | Yes | |
● PROFIBUS DP slave | Yes | |
● Point-to-point connection | No | |
MPI | ||
● Transmission rate, max. | 12 Mbit/s | |
Services | ||
— PG/OP communication | Yes | |
— Routing | Yes | |
— Global data communication | Yes | |
— S7 basic communication | Yes | |
— S7 communication | Yes | |
— S7 communication, as client | No; but via CP and loadable FB | |
— S7 communication, as server | Yes | |
PROFIBUS DP master | ||
● Transmission rate, max. | 12 Mbit/s | |
● Number of DP slaves, max. | 124 | |
Services | ||
— PG/OP communication | Yes | |
— Routing | Yes | |
— Global data communication | No | |
— S7 basic communication | Yes; I blocks only | |
— S7 communication | Yes | |
— S7 communication, as client | No | |
— S7 communication, as server | Yes | |
— Equidistance | Yes | |
— Isochronous mode | Yes; OB 61; isochronous mode can only be used alternatively on PROFIBUS DP or PROFINET IO | |
— SYNC/FREEZE | Yes | |
— Activation/deactivation of DP slaves | Yes | |
— Number of DP slaves that can be simultaneously activated/deactivated, max. | 8 | |
— Direct data exchange (slave-to-slave communication) | Yes; as subscriber | |
— DPV1 | Yes | |
Address area | ||
— Inputs, max. | 8 kbyte | |
— Outputs, max. | 8 kbyte | |
User data per DP slave | ||
— Inputs, max. | 244 byte | |
— Outputs, max. | 244 byte | |
PROFIBUS DP slave | ||
● Transmission rate, max. | 12 Mbit/s | |
● automatic baud rate search | Yes; only with passive interface | |
● Address area, max. | 32 | |
● User data per address area, max. | 32 byte | |
Services | ||
— PG/OP communication | Yes | |
— Routing | Yes; Only with active interface | |
— Global data communication | No | |
— S7 basic communication | No | |
— S7 communication | Yes | |
— S7 communication, as client | No | |
— S7 communication, as server | Yes; Connection configured on one side only | |
— Direct data exchange (slave-to-slave communication) | Yes | |
— DPV1 | No | |
Transfer memory | ||
— Inputs | 244 byte | |
— Outputs | 244 byte | |
2. Interface | ||
Interface type | PROFINET | |
Isolated | Yes | |
automatic detection of transmission rate | Yes; 10/100 Mbit/s | |
Autonegotiation | Yes | |
Autocrossing | Yes | |
Change of IP address at runtime, supported | Yes | |
Interface types | ||
● RJ 45 (Ethernet) | Yes | |
● Number of ports | 2 | |
● integrated switch | Yes | |
Protocols | ||
● MPI | No | |
● PROFINET IO Controller | Yes; Also simultaneously with IO-Device functionality | |
● PROFINET IO Device | Yes; Also simultaneously with IO Controller functionality | |
● PROFINET CBA | Yes | |
● PROFIBUS DP master | No | |
● PROFIBUS DP slave | No | |
● Open IE communication | Yes; Via TCP/IP, ISO on TCP, and UDP | |
● Web server | Yes | |
● Media redundancy | Yes | |
PROFINET IO Controller | ||
● Transmission rate, max. | 100 Mbit/s | |
Services | ||
— PG/OP communication | Yes | |
— Routing | Yes | |
— S7 communication | Yes; with loadable FBs, max. configurable connections: 16, max. number of instances: 32 | |
— Isochronous mode | Yes; OB 61; isochronous mode can only be used alternatively on PROFIBUS DP or PROFINET IO | |
— IRT | Yes | |
— Shared device | Yes | |
— Prioritized startup | Yes | |
— Number of IO devices with prioritized startup, max. | 32 | |
— Number of connectable IO Devices, max. | 128 | |
— Of which IO devices with IRT, max. | 64 | |
— of which in line, max. | 64 | |
— Number of IO Devices with IRT and the option “high flexibility” | 128 | |
— of which in line, max. | 61 | |
— Number of connectable IO Devices for RT, max. | 128 | |
— of which in line, max. | 128 | |
— Activation/deactivation of IO Devices | Yes | |
— Number of IO Devices that can be simultaneously activated/deactivated, max. | 8 | |
— IO Devices changing during operation (partner ports), supported | Yes | |
— Number of IO Devices per tool, max. | 8 | |
— Device replacement without swap medium | Yes | |
— Send cycles | 250 μs, 500 μs,1 ms; 2 ms, 4 ms (not in the case of IRT with “high flexibility” option) | |
— Updating time | 250 µs to 512 ms (depending on the operating mode, see Manual “S7-300 CPU 31xC and CPU 31x, technical Data” for more details) | |
Address area | ||
— Inputs, max. | 8 kbyte | |
— Outputs, max. | 8 kbyte | |
— User data consistency, max. | 1 024 byte | |
PROFINET IO Device | ||
Services | ||
— PG/OP communication | Yes | |
— Routing | Yes | |
— S7 communication | Yes; with loadable FBs, max. configurable connections: 16, max. number of instances: 32 | |
— Isochronous mode | No | |
— IRT | Yes | |
— PROFIenergy | Yes; With SFB 73 / 74 prepared for loadable PROFIenergy standard FB for I-Device | |
— Shared device | Yes | |
— Number of IO Controllers with shared device, max. | 2 | |
Transfer memory | ||
— Inputs, max. | 1 440 byte; Per IO Controller with shared device | |
— Outputs, max. | 1 440 byte; Per IO Controller with shared device | |
Submodules | ||
— Number, max. | 64 | |
— User data per submodule, max. | 1 024 byte | |
PROFINET CBA | ||
● acyclic transmission | Yes | |
● cyclic transmission | Yes | |
Open IE communication | ||
● Number of connections, max. | 16 | |
● Local port numbers used at the system end | 0, 20, 21, 23, 25, 80, 102, 135, 161, 443, 8080, 34962, 34963, 34964, 65532, 65533, 65534, 65535 | |
● Keep-alive function, supported | Yes | |
Protocols | ||
PROFIsafe | No | |
Redundancy mode | ||
Media redundancy | ||
— Switchover time on line break, typ. | 200 ms; PROFINET MRP | |
— Number of stations in the ring, max. | 50 | |
Open IE communication | ||
● TCP/IP | Yes; via integrated PROFINET interface and loadable FBs | |
— Number of connections, max. | 16 | |
— Data length for connection type 01H, max. | 1 460 byte | |
— Data length for connection type 11H, max. | 32 768 byte | |
— several passive connections per port, supported | Yes | |
● ISO-on-TCP (RFC1006) | Yes; via integrated PROFINET interface and loadable FBs | |
— Number of connections, max. | 16 | |
— Data length, max. | 32 768 byte | |
● UDP | Yes; via integrated PROFINET interface and loadable FBs | |
— Number of connections, max. | 16 | |
— Data length, max. | 1 472 byte | |
Web server | ||
● supported | Yes | |
● User-defined websites | Yes | |
● Number of HTTP clients | 5 | |
communication functions / header | ||
PG/OP communication | Yes | |
Data record routing | Yes | |
Global data communication | ||
● supported | Yes | |
● Number of GD loops, max. | 8 | |
● Number of GD packets, max. | 8 | |
● Number of GD packets, transmitter, max. | 8 | |
● Number of GD packets, receiver, max. | 8 | |
● Size of GD packets, max. | 22 byte | |
● Size of GD packet (of which consistent), max. | 22 byte | |
S7 basic communication | ||
● supported | Yes | |
● User data per job, max. | 76 byte | |
● User data per job (of which consistent), max. | 76 byte; 76 bytes (with X_SEND or X_RCV); 64 bytes (with X_PUT or X_GET as server) | |
S7 communication | ||
● supported | Yes | |
● as server | Yes | |
● as client | Yes; via integrated PROFINET interface and loadable FB or via CP and loadable FB | |
● User data per job, max. | See online help of STEP 7 (shared parameters of the SFBs/FBs and of the SFCs/FCs of S7 Communication) | |
S5 compatible communication | ||
● supported | Yes; via CP and loadable FC | |
communication functions / PROFINET CBA (with set target communication load) / header | ||
● Setpoint for the CPU communication load | 50 % | |
● number of remote connection partners / with PROFINET CBA | 32 | |
● number of technological functions / with PROFINET CBA / for master or slave | 30 | |
● number of connections / with PROFINET CBA / for master or slave / total | 1 000 | |
● data volume / of the input variables / with PROFINET CBA / for master or slave | 4 000 byte | |
● data volume / of the output variables / with PROFINET CBA / for master or slave | 4 000 byte | |
● number of internal and PROFIBUS interconnections / with PROFINET CBA / maximum | 500 | |
● data volume / of internal and PROFIBUS interconnections / with PROFINET CBA / for master or slave | 4 000 byte | |
● data volume / with PROFINET CBA / per connection / maximum | 1 400 byte | |
performance data / PROFINET CBA / remote interconnection / with acyclic transfer / header | ||
— update time / of the remote interconnections / in the case of acyclic transmission / with PROFINET CBA | 500 ms | |
— number of remote connections to input variables / in the case of acyclic transmission / with PROFINET CBA / maximum | 100 | |
— number of remote connections to output variables / in the case of acyclic transmission / with PROFINET CBA / maximum | 100 | |
— data volume / as user data for remote interconnections with input variables / in the case of acyclic transmission / with PROFINET CBA | 2 000 byte | |
— data volume / as user data for remote interconnections with output variables / in the case of acyclic transmission / with PROFINET CBA | 2 000 byte | |
— data volume / as user data for remote interconnections / in the case of acyclic transmission / with PROFINET CBA / per connection / maximum | 1 400 byte | |
performance data / PROFINET CBA / remote interconnection / with cyclic transfer / header | ||
— update time / of the remote interconnections / with cyclical transfer / with PROFINET CBA | 10 ms | |
— number of remote connections to input variables / with PROFINET CBA / with cyclic transfer / maximum | 200 | |
— number of remote connections to output variables / with cyclical transfer / with PROFINET CBA / maximum | 200 | |
— data volume / as user data for remote interconnections with input variables / with cyclical transfer / with PROFINET CBA / maximum | 2 000 byte | |
— data volume / as user data for remote interconnections with output variables / with cyclical transfer / with PROFINET CBA / maximum | 2 000 byte | |
— data volume / as user data for remote interconnections / with cyclical transfer / with PROFINET CBA / per connection / maximum | 450 byte | |
performance data / PROFINET CBA / HMI variables via PROFINET / acyclic / header | ||
— number of connectable HMI stations / for HMI variables / in the case of acyclic transmission / with PROFINET CBA | 3; 2x PN OPC/1x iMap | |
— update time / of the HMI variables / in the case of acyclic transmission / with PROFINET CBA | 500 ms | |
— number of HMI variables / in the case of acyclic transmission / with PROFINET CBA / maximum | 200 | |
— data volume / as user data for HMI variables / in the case of acyclic transmission / with PROFINET CBA / maximum | 2 000 byte | |
performance data / PROFINET CBA / PROFIBUS proxy functionality / header | ||
— product function / with PROFINET CBA / PROFIBUS proxy functionality | Yes | |
— number of coupled PROFIBUS devices / with PROFIBUS functionality | 16 | |
— data volume / with PROFIBUS proxy functionality / with PROFINET CBA / per connection / maximum | 240 byte; Slave-dependent | |
Number of connections | ||
● overall | 32 | |
● usable for PG communication | 31 | |
— reserved for PG communication | 1 | |
— adjustable for PG communication, min. | 1 | |
— adjustable for PG communication, max. | 31 | |
● usable for OP communication | 31 | |
— reserved for OP communication | 1 | |
— adjustable for OP communication, min. | 1 | |
— adjustable for OP communication, max. | 31 | |
● usable for S7 basic communication | 30 | |
— reserved for S7 basic communication | 0 | |
— adjustable for S7 basic communication, min. | 0 | |
— adjustable for S7 basic communication, max. | 30 | |
● usable for S7 communication | 16 | |
— reserved for S7 communication | 0 | |
— adjustable for S7 communication, min. | 0 | |
— adjustable for S7 communication, max. | 16 | |
● total number of instances, max. | 32 | |
● usable for routing | X1 as MPI: max. 10; X1 as DP master: max. 24; X1 as DP slave (active): max. 14; X2 as PROFINET: 24 max. | |
S7 message functions | ||
Number of login stations for message functions, max. | 32; Depending on the configured connections for PG/OP and S7 basic communication | |
Process diagnostic messages | Yes | |
simultaneously active Alarm-S blocks, max. | 300 | |
Test commissioning functions | ||
Status block | Yes; Up to 2 simultaneously | |
Single step | Yes | |
Number of breakpoints | 4 | |
Status/control | ||
● Status/control variable | Yes | |
● Variables | Inputs, outputs, memory bits, DB, times, counters | |
● Number of variables, max. | 30 | |
— of which status variables, max. | 30 | |
— of which control variables, max. | 14 | |
Forcing | ||
● Forcing | Yes | |
● Forcing, variables | Inputs, outputs | |
● Number of variables, max. | 10 | |
Diagnostic buffer | ||
● present | Yes | |
● Number of entries, max. | 500 | |
— adjustable | No | |
— of which powerfail-proof | 100; Only the last 100 entries are retained | |
● Number of entries readable in RUN, max. | 499 | |
— adjustable | Yes; From 10 to 499 | |
— preset | 10 | |
Service data | ||
● can be read out | Yes | |
Ambient conditions | ||
Ambient temperature during operation | ||
● min. | 0 °C | |
● max. | 60 °C | |
configuration / header | ||
Configuration software | ||
● STEP 7 | Yes; V5.5 or higher | |
configuration / programming / header | ||
● Command set | see instruction list | |
● Nesting levels | 8 | |
● System functions (SFC) | see instruction list | |
● System function blocks (SFB) | see instruction list | |
Programming language | ||
— LAD | Yes | |
— FBD | Yes | |
— STL | Yes | |
— SCL | Yes | |
— CFC | Yes | |
— GRAPH | Yes | |
— HiGraph® | Yes | |
Know-how protection | ||
● User program protection/password protection | Yes | |
● Block encryption | Yes; With S7 block Privacy | |
Dimensions | ||
Width | 40 mm | |
Height | 125 mm | |
Depth | 130 mm | |
Weights | ||
Weight, approx. | 340 g |
Weight | 0.38 kg |
---|---|
Dimensions | 12.8 × 15.2 × 5.2 cm |
Related products
-
Select options This product has multiple variants. The options may be chosen on the product page Details
-
Select options This product has multiple variants. The options may be chosen on the product page Details