$ 262.90
General information | |
Article Number | 6ES7288-1CR60-0AA0 |
Product type designation | CPU CR60 AC/DC/relay |
Engineering with | |
● Programming package | STEP 7 Micro/WIN SMART |
Installation type/mounting | |
Rail mounting | Yes; Standard – DIN rail |
Supply voltage | |
Rated value (AC) | |
● 120 V AC | Yes |
● 230 V AC | Yes |
permissible range, lower limit (AC) | 85 V |
permissible range, upper limit (AC) | 264 V |
Line frequency | |
● permissible range, lower limit | 47 Hz |
● permissible range, upper limit | 63 Hz |
Input current | |
Current consumption (rated value) | 160 mA; at 240 V AC |
Current consumption, max. | 280 mA; At 120 V AC |
Inrush current, max. | 7.3 A; at 264 V |
Output current | |
Current output, max | 300 mA; 24 V DC Sensor Power |
Power loss | |
Power loss, max. | 20 W |
Memory | |
Type of memory | DDR |
Flash | Yes |
RAM | Yes |
Memory available for user data | 8 kbyte |
Memory size | 12 kbyte; Program memory |
Micro Memory Card | Yes; microSDHC Card (optional) |
CPU processing times | |
for bit operations, typ. | 150 ns; / instruction |
for word operations, typ. | 1.2 µs; / instruction |
for floating point arithmetic, typ. | 3.6 µs; / instruction |
Address area | |
I/O address area | |
● Inputs | 32 byte; Digital inputs |
● Outputs | 32 byte; Digital outputs |
Time of day | |
Clock | |
● Type | Hardware clock, no battery backup |
● Hardware clock (real-time) | Yes |
● Backup time | 7 d |
● Deviation per day, max. | 4 s; within 120s/month at 25 °C |
Digital inputs | |
Number of digital inputs | 36 |
Input voltage | |
● Type of input voltage | DC |
● Rated value (DC) | 24 V |
● for signal “0” | < 5 V DC |
● for signal “1” | +15 to +30 V |
Input current | |
● for signal “1”, typ. | 4 mA |
Cable length | |
● shielded, max. | 500 m; 50m shielded for HSC inputs |
● unshielded, max. | 300 m |
Digital outputs | |
Number of digital outputs | 24; Relays |
Switching capacity of the outputs | |
● with resistive load, max. | 2 A |
● on lamp load, max. | 30 W; 30 W with DC, 200 W with AC |
Relay outputs | |
● Number of relay outputs | 24 |
Cable length | |
● shielded, max. | 500 m |
● unshielded, max. | 150 m |
Interfaces | |
Number of industrial Ethernet interfaces | 1 |
Number of RS 485 interfaces | 1 |
1. Interface | |
Interface type | Ethernet |
Isolated | Yes; Transformer isolated, 1,500V AC |
automatic detection of transmission rate | Yes; 10/100 Mbit/s |
Autonegotiation | Yes |
Autocrossing | Yes |
Interface types | |
● RJ 45 (Ethernet) | Yes |
Interface | |
interface type | RS 485 (max. 187.5 kbps) |
Protocols | |
Supports protocol for PROFINET IO | Yes |
PROFIBUS | No |
Protocols (Ethernet) | |
● TCP/IP | Yes |
communication functions / header | |
S7 communication | |
● supported | Yes |
● as server | Yes |
● as client | Yes |
Test commissioning functions | |
Forcing | |
● Forcing | Yes |
Integrated Functions | |
PID controller | Yes; PID closed-loop control function: Continuous controller outputs, binary controller outputs, automatic/manual mode, max. 8 loops |
EMC | |
Interference immunity against discharge of static electricity | |
● Interference immunity against discharge of static electricity acc. to IEC 61000-4-2 | Yes |
— Test voltage at air discharge | 8 kV |
— Test voltage at contact discharge | 4 kV |
Interference immunity against high-frequency electromagnetic fields | |
● Interference immunity against high-frequency radiation acc. to IEC 61000-4-3 | Yes; 10 V/m, 80 to 1 000 MHz (to IEC 61000-4-3); 10 V/m, 900 MHz,1.89 GHz, 50% ED (to IEC 61000-4-3) |
Interference immunity to cable-borne interference | |
● Interference immunity on supply lines acc. to IEC 61000-4-4 | Yes; 2 kV acc. to IEC 61000-4-4, burst |
● Interference immunity on signal cables acc. to IEC 61000-4-4 | Yes; ±2 kV acc. to IEC 61000-4-4, Burst |
Interference immunity against conducted variable disturbance induced by high-frequency fields | |
● Interference immunity against high frequency current feed acc. to IEC 61000-4-6 | Yes; 10 V, 150 kHz to 80 MHz (to IEC 61000-4-6) |
Emission of radio interference acc. to EN 55 011 | |
● Limit class A, for use in industrial areas | Yes; EN 61000-6-4, interference emission: Intended for use in industrial areas. |
Emission of conducted and non-conducted interference | |
● Interference emission via line/AC current cables | EN 61000-6-4, interference emission: Intended for use in industrial areas. |
Degree and class of protection | |
IP degree of protection | IP20 |
Ambient conditions | |
Free fall | |
● Fall height, max. | 0.3 m; five times, in product package |
Ambient temperature during operation | |
● min. | 0 °C |
● max. | 55 °C |
● horizontal installation, min. | 0 °C |
● horizontal installation, max. | 55 °C |
● vertical installation, min. | 0 °C |
● vertical installation, max. | 45 °C |
Ambient temperature during storage/transportation | |
● min. | -40 °C |
● max. | 70 °C |
Air pressure acc. to IEC 60068-2-13 | |
● Storage/transport, min. | 660 hPa |
● Storage/transport, max. | 1 080 hPa |
Altitude during operation relating to sea level | |
● Installation altitude, min. | -1 000 m |
● Installation altitude, max. | 2 000 m |
Relative humidity | |
● Operation at 25 ℃ without condensation, max. | 95% |
configuration / header | |
configuration / programming / header | |
Programming language | |
— LAD | Yes |
— FBD | Yes |
— STL | Yes |
Dimensions | |
Width | 175 mm |
Height | 81 mm |
Depth | 81 mm |
Weights | |
Weight, approx. | 620 g |
Weight | 0.62 kg |
---|---|
Dimensions | 17.5 × 8.1 × 8.1 cm |