SIMATIC S7-1500 – PM 1507 – Siemens Power Supply
$ 198.29 – $ 275.16
SKU: N/A
The design and functionality of the SIMATIC PM 1507 single-phase load power supply (PM = power module) with automatic range selection of the input voltage makes it an optimal match to the SIMATIC S7-1500 PLC. It supplies the S7-1500 system components such as CPU, system power supply (PS), I/O circuits of the input and output modules and, if necessary, the sensors and actuators with 24 V DC.
Siemens Power Supplies PM 1507 Product Specifications:
Article number | 6EP1332-4BA00 | 6EP1333-4BA00 | |
Product | S7-1500 PM1507 | S7-1500 PM1507 | |
Power supply, type | 24 V/3 A | 24 V/8 A | |
Input | |||
type of the power supply network | 1-phase AC | 1-phase AC | |
supply voltage at AC | |||
● initial value | Automatic range selection | Automatic range selection | |
supply voltage | |||
● 1 at AC rated value | 120 V | 120 V | |
● 2 at AC rated value | 230 V | 230 V | |
input voltage | |||
● 1 at AC | 85 … 132 V | 85 … 132 V | |
● 2 at AC | 170 … 264 V | 170 … 264 V | |
design of input wide range input | No | No | |
overvoltage overload capability | 2.3 × Vin rated, 1.3 ms | 2.3 × Vin rated, 1.3 ms | |
operating condition of the mains buffering | at Vin = 93/187 V | at Vin = 93/187 V | |
buffering time for rated value of the output current in the event of power failure minimum | 20 ms | 20 ms | |
operating condition of the mains buffering | at Vin = 93/187 V | at Vin = 93/187 V | |
line frequency | |||
● 1 rated value | 50 Hz | 50 Hz | |
● 2 rated value | 60 Hz | 60 Hz | |
line frequency | 45 … 65 Hz | 45 … 65 Hz | |
input current | |||
● at rated input voltage 120 V | 1.4 A | 3.7 A | |
● at rated input voltage 230 V | 0.8 A | 1.7 A | |
current limitation of inrush current at 25 °C maximum | 23 A | 62 A | |
duration of inrush current limiting at 25 °C | |||
● maximum | 3 ms | 3 ms | |
I2t value maximum | 1.3 A²·s | 12 A²·s | |
fuse protection type | T 3,15 A/250 V (not accessible) | T 6.3 A/250 V (not accessible) | |
● in the feeder | Recommended miniature circuit breaker: 10 A characteristic B or 6 A characteristic C | Recommended miniature circuit breaker: 16 A characteristic B or 10 A characteristic C | |
Output | |||
voltage curve at output | Controlled, isolated DC voltage | Controlled, isolated DC voltage | |
output voltage at DC rated value | 24 V | 24 V | |
output voltage | |||
● at output 1 at DC rated value | 24 V | 24 V | |
relative overall tolerance of the voltage | 1 % | 1 % | |
relative control precision of the output voltage | |||
● on slow fluctuation of input voltage | 0.1 % | 0.1 % | |
● on slow fluctuation of ohm loading | 0.1 % | 0.1 % | |
residual ripple | |||
● maximum | 50 mV | 50 mV | |
voltage peak | |||
● maximum | 150 mV | 150 mV | |
product function output voltage adjustable | No | No | |
display version for normal operation | LED green for 24 V OK; LED red for error; LED yellow for stand-by | LED green for 24 V OK; LED red for error; LED yellow for stand-by | |
behavior of the output voltage when switching on | No overshoot of Vout (soft start) | No overshoot of Vout (soft start) | |
response delay maximum | 1.5 s | 1.5 s | |
voltage increase time of the output voltage | |||
● typical | 10 ms | 10 ms | |
output current | |||
● rated value | 3 A | 8 A | |
● rated range | 0 … 3 A | 0 … 8 A | |
supplied active power typical | 72 W | 192 W | |
short-term overload current | |||
● on short-circuiting during the start-up typical | 12 A | 35 A | |
● at short-circuit during operation typical | 12 A | 35 A | |
duration of overloading capability for excess current | |||
● on short-circuiting during the start-up | 70 ms | 70 ms | |
● at short-circuit during operation | 70 ms | 70 ms | |
product feature | |||
● bridging of equipment | Yes | Yes | |
number of parallel-switched equipment resources for increasing the power | 2 | 2 | |
Efficiency | |||
efficiency in percent | 87 % | 90 % | |
power loss [W] | |||
● at rated output voltage for rated value of the output current typical | 11 W | 21 W | |
Closed-loop control | |||
relative control precision of the output voltage with rapid fluctuation of the input voltage by +/- 15% typical | 0.1 % | 0.1 % | |
relative control precision of the output voltage load step of resistive load 50/100/50 % typical | 1 % | 2 % | |
relative control precision of the output voltage at load step of resistive load 10/90/10 % typical | 3 % | 3 % | |
setting time | |||
● load step 10 to 90% typical | 5 ms | 5 ms | |
● load step 90 to 10% typical | 5 ms | 5 ms | |
● maximum | 5 ms | 5 ms | |
Protection and monitoring | |||
design of the overvoltage protection | Additional control loop, limitation (closed loop control) at < 28.8 V | Additional control loop, limitation (closed loop control) at < 28.8 V | |
response value current limitation | 3.15 … 3.6 A | 8.4 … 9.6 A | |
response value current limitation typical | 3.4 A | 9 A | |
property of the output short-circuit proof | Yes | Yes | |
design of short-circuit protection | Electronic shutdown, automatic restart | Electronic shutdown, automatic restart | |
display version for overload and short circuit | – | – | |
Safety | |||
galvanic isolation between input and output | Yes | Yes | |
galvanic isolation | Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 and EN 61131-2 | Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 and EN 61131-2 | |
operating resource protection class | Class I | Class I | |
leakage current | |||
● maximum | 3.5 mA | 3.5 mA | |
● typical | 0.4 mA | 1.3 mA | |
protection class IP | IP20 | IP20 | |
Approvals | |||
certificate of suitability | |||
● CE marking | Yes | Yes | |
● UL approval | Yes; cULus-Listed (UL 508, CSA C22.2 No. 142), File E143289 | Yes; cULus-Listed (UL 508, CSA C22.2 No. 142), File E143289 | |
● CSA approval | Yes; cULus-Listed (UL 508, CSA C22.2 No. 142), File E143289 | Yes; cULus-Listed (UL 508, CSA C22.2 No. 142), File E143289 | |
● cCSAus, Class 1, Division 2 | No | No | |
● ATEX | Yes; ATEX (EX) II 3G Ex nA nC IIC T4 Gc | Yes; ATEX (EX) II 3G Ex nA nC IIC T3 Gc | |
certificate of suitability | |||
● relating to ATEX | IECEx Ex nA nC IIC T4 Gc; ATEX (EX) II 3G Ex nA nC IIC T4 Gc; cULus (ANSI/ISA 12.12.01, CSA C22.2 No.213) Class I, Div. 2, Group ABCD, T4, File E330455 | IECEx Ex nA nC IIC T3 Gc; ATEX (EX) II 3G Ex nA nC IIC T3 Gc; cULus (ANSI/ISA 12.12.01, CSA C22.2 No.213) Class I, Div. 2, Group ABCD, T3, File E330455 | |
● IECEx | Yes; IECEx Ex nA nC IIC T4 Gc | Yes; IECEx Ex nA nC IIC T3 Gc | |
● NEC Class 2 | No | No | |
● ULhazloc approval | Yes | Yes | |
● FM registration | Yes; Class I, Div. 2, Group ABCD, T4 | Yes; Class I, Div. 2, Group ABCD, T4 | |
type of certification CB-certificate | Yes | Yes | |
certificate of suitability | |||
● EAC approval | Yes | Yes | |
certificate of suitability shipbuilding approval | Yes | Yes | |
shipbuilding approval | ABS, BV, DNV GL | ABS, BV, DNV GL | |
Marine classification association | |||
● American Bureau of Shipping Europe Ltd. (ABS) | Yes | Yes | |
● French marine classification society (BV) | Yes | Yes | |
● DNV GL | Yes | Yes | |
● Lloyds Register of Shipping (LRS) | No | No | |
● Nippon Kaiji Kyokai (NK) | No | No | |
EMC | |||
standard | |||
● for emitted interference | EN 55022 Class B | EN 55022 Class B | |
● for mains harmonics limitation | EN 61000-3-2 | EN 61000-3-2 | |
● for interference immunity | EN 61000-6-2 | EN 61000-6-2 | |
environmental conditions | |||
ambient temperature | |||
● during operation | 0 … 60 °C; with natural convection | 0 … 60 °C; with natural convection | |
● during transport | -40 … +85 °C | -40 … +85 °C | |
● during storage | -40 … +85 °C | -40 … +85 °C | |
environmental category according to IEC 60721 | Climate class 3K3, 5 … 95% no condensation | Climate class 3K3, 5 … 95% no condensation | |
Mechanics | |||
type of electrical connection | Screw-/spring clamp connection | Screw-/spring clamp connection | |
● at input | L, N, PE: 1 screw terminal each for 0.5 … 2.5 mm² | L, N, PE: 1 screw terminal each for 0.5 … 2.5 mm² | |
● at output | L+, M: 2 spring-loaded terminals each for 0.5 to 2.5 mm² | L+, M: 2 spring-loaded terminals each for 0.5 to 2.5 mm² | |
product function | |||
● removable terminal at input | Yes | Yes | |
● removable terminal at output | Yes | Yes | |
width of the enclosure | 50 mm | 75 mm | |
height of the enclosure | 147 mm | 147 mm | |
depth of the enclosure | 129 mm | 129 mm | |
required spacing | |||
● top | 40 mm | 40 mm | |
● bottom | 40 mm | 40 mm | |
● left | 0 mm | 0 mm | |
● right | 0 mm | 0 mm | |
net weight | 0.45 kg | 0.74 kg | |
product feature of the enclosure housing can be lined up | Yes | Yes | |
fastening method | Can be mounted onto S7-1500 rail | Can be mounted onto S7-1500 rail | |
MTBF at 40 °C | 1 611 993 h | 1 362 918 h | |
other information | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) |
Weight | N/A |
---|---|
Dimensions | N/A |
Related products
-
Select options This product has multiple variants. The options may be chosen on the product page Details
-
Select options This product has multiple variants. The options may be chosen on the product page Details