$ 983.21
Using fail-safe ET 200MP/S7-1500 modules makes it possible to implement safety-related application requirements as an integral part of the overall automation. The safety functions required for fail-safe operation are integrated in the modules. Communication with the fail-safe SIMATIC S7 CPUs is performed by means of PROFIsafe.
The modules can be operated both in centralized and distributed configurations.
Article number | 6ES7526-1BH00-0AB0 | |
ET 200MP, F-DI 16X24VDC | ||
General information | ||
Product type designation | F-DI 16x24VDC | |
Firmware version | ||
● FW update possible | Yes | |
Product function | ||
● I&M data | Yes; I&M0 to I&M3 | |
Engineering with | ||
● STEP 7 TIA Portal configurable/integrated from version | V13 SP1 with HSP 0086 | |
Operating mode | ||
● DI | Yes | |
Supply voltage | ||
Rated value (DC) | 24 V | |
permissible range, lower limit (DC) | 19.2 V | |
permissible range, upper limit (DC) | 28.8 V | |
Reverse polarity protection | Yes | |
power supply according to NEC Class 2 required | No | |
Input current | ||
Current consumption (rated value) | 50 mA; without load | |
Current consumption, max. | 60 mA; without load | |
Encoder supply | ||
Number of outputs | 4 | |
Short-circuit protection | Yes; Electronic (response threshold 0.7 A to 1.8 A) | |
24 V encoder supply | ||
● 24 V | Yes; min. L+ (-1.5 V) | |
● Short-circuit protection | Yes | |
● Output current, max. | 300 mA; Max. 100 mA when mounted vertically | |
Power | ||
Power available from the backplane bus | 0.9 W | |
Power loss | ||
Power loss, typ. | 4.6 W | |
Address area | ||
Address space per module | ||
● Inputs | 9 byte; S7-300/400F CPU, 8 byte | |
● Outputs | 5 byte; S7-300/400F CPU, 4 byte | |
Hardware configuration | ||
Automatic encoding | Yes | |
● Electronic coding element type F | Yes | |
Digital inputs | ||
Number of digital inputs | 16 | |
Source/sink input | Yes; P-reading | |
Input characteristic curve in accordance with IEC 61131, type 1 | Yes | |
Input voltage | ||
● Rated value (DC) | 24 V | |
● for signal “0” | -30 to +5 V | |
● for signal “1” | +15 to +30 V | |
Input current | ||
● for signal “1”, typ. | 3.7 mA | |
Input delay (for rated value of input voltage) | ||
for standard inputs | ||
— parameterizable | Yes | |
— at “0” to “1”, min. | 0.4 ms | |
— at “0” to “1”, max. | 20 ms | |
— at “1” to “0”, min. | 0.4 ms | |
— at “1” to “0”, max. | 20 ms | |
Cable length | ||
● shielded, max. | 1 000 m | |
● unshielded, max. | 500 m | |
Interrupts/diagnostics/status information | ||
Diagnostics function | Yes | |
Alarms | ||
● Diagnostic alarm | Yes | |
● Hardware interrupt | No | |
Diagnoses | ||
● Monitoring the supply voltage | Yes | |
● Wire-break | No | |
● Short-circuit | Yes | |
● Group error | Yes | |
Diagnostics indication LED | ||
● RUN LED | Yes; green LED | |
● ERROR LED | Yes; red LED | |
● Channel status display | Yes; green LED | |
● for channel diagnostics | Yes; red LED | |
● for module diagnostics | Yes; red LED | |
Potential separation | ||
Potential separation channels | ||
● between the channels and backplane bus | Yes | |
Isolation | ||
Isolation tested with | 707 V DC (type test) | |
Standards, approvals, certificates | ||
Suitable for safety functions | Yes | |
Highest safety class achievable in safety mode | ||
● Performance level according to ISO 13849-1 | PLe | |
● SIL acc. to IEC 61508 | SIL 3 | |
Probability of failure (for service life of 20 years and repair time of 100 hours) | ||
— Low demand mode: PFDavg in accordance with SIL3 | < 5.00E-05 | |
— High demand/continuous mode: PFH in accordance with SIL3 | < 1.00E-09 1/h | |
Ambient conditions | ||
Ambient temperature during operation | ||
● horizontal installation, min. | 0 °C | |
● horizontal installation, max. | 60 °C | |
● vertical installation, min. | 0 °C | |
● vertical installation, max. | 40 °C | |
Dimensions | ||
Width | 35 mm | |
Height | 147 mm | |
Depth | 129 mm | |
Weights | ||
Weight, approx. | 280 g |
Weight | 0.340 kg |
---|---|
Dimensions | 15.1 × 15.1 × 4.7 cm |
INOSAKI Limited
RM B 5/F Gaylord Comm,
Bldg 114-118 Lockhart Rd.
Hong Kong
INOSAKI Sdn. Bhd.
2-1-9, Ground Floor, One Square, Tingkat Mahsuri 1,
11900 Bayan Lepas, Penan
INOSAKI Pte. Ltd.
101 Upper Cross Street,
No. 06-17, People’s Park Centre,
Singapore (058357)