$ 279.84
The fail-safe modules of the SIMATIC S7-1200 Controller permit the implementation of safety-related application requirements integrated into the overall automation. The safety functions required for fail-safe operation are integrated in the modules. Communication with the fail-safe SIMATIC S7 CPUs is performed by means of PROFIsafe mechanisms. The modules can only be operated in central configurations.
| Article number | 6ES7226-6RA32-0XB0 | |
| Digital Output SM 1226, F-DQ 2x Relay | ||
| General information | ||
| Product type designation | SM 1226, F-DQ 2x relay/5 A | |
| Supply voltage | ||
| permissible range, lower limit (DC) | 20.4 V | |
| permissible range, upper limit (DC) | 28.8 V | |
| power supply according to NEC Class 2 required | No | |
| Input current | ||
| from backplane bus 5 V DC, max. | 120 mA | |
| Digital outputs | ||
| ● from load voltage L+, max. | 300 mA | |
| Power loss | ||
| Power loss, typ. | 10 W | |
| Digital outputs | ||
| Number of digital outputs | 2 | |
| Short-circuit protection | No | |
| Output voltage | ||
| ● Rated value (DC) | 5 V DC to 30 V DC | |
| ● Rated value (AC) | 5 V AC to 250 V AC | |
| Output current | ||
| ● for signal “1” permissible range, max. | 5 A maximum per circuit and 10 A maximum of all circuits per module | |
| Relay outputs | ||
| ● Number of relay outputs | 2; 2 circuits per output | |
| Switching capacity of contacts | ||
| — with inductive load, max. | 0.1 Hz, accordance with IEC 60947-5-1, DC-13; 2 Hz, accordance with IEC 60947-5-1, AC-15 | |
| — with resistive load, max. | 2 Hz | |
| Cable length | ||
| ● shielded, max. | 200 m | |
| ● unshielded, max. | 200 m | |
| Interrupts/diagnostics/status information | ||
| Diagnostics indication LED | ||
| ● for status of the outputs | Yes | |
| Degree and class of protection | ||
| IP degree of protection | IP20 | |
| Standards, approvals, certificates | ||
| CE mark | Yes | |
| cULus | Yes | |
| FM approval | Yes | |
| Highest safety class achievable in safety mode | ||
| ● Performance level according to ISO 13849-1 | Category 4, PL e | |
| ● SIL acc. to IEC 61508 | SIL 3 | |
| Probability of failure (for service life of 20 years and repair time of 100 hours) | ||
| — Low demand mode: PFDavg in accordance with SIL3 | < 1.00E-05 | |
| — High demand/continuous mode: PFH in accordance with SIL3 | < 4.00E-09 | |
| Ambient conditions | ||
| Free fall | ||
| ● Fall height, max. | 0.3 m; five times, in product package | |
| Ambient temperature during operation | ||
| ● min. | 0 °C | |
| ● max. | 55 °C | |
| ● permissible temperature change | 5°C to 55°C, 3°C / minute | |
| Ambient temperature during storage/transportation | ||
| ● min. | -40 °C | |
| ● max. | 70 °C | |
| Air pressure acc. to IEC 60068-2-13 | ||
| ● Storage/transport, min. | 660 hPa | |
| ● Storage/transport, max. | 1 080 hPa | |
| Relative humidity | ||
| ● Operation at 25 ℃ without condensation, max. | 95 % | |
| Mechanics/material | ||
| Enclosure material (front) | ||
| ● Plastic | Yes | |
| Dimensions | ||
| Width | 70 mm | |
| Height | 100 mm | |
| Depth | 75 mm | |
| Weights | ||
| Weight, approx. | 300 g | |