SIMATIC ET 200SP – IM 155-6PN Basic / Standard PROFINET Interface Modules – Siemens
$ 320.10 – $ 1,286.78
SKU: N/A
SIMATIC IM155-6PN Basic with PROFINET access
- Max. 12 I/O modules, no PROFIsafe modules, with complete diagnostic support
- Max. 32 bytes in each case for input and output data per module and per station
- Data update time: typ.1 ms
- PROFINET connection via 2 integrated RJ45 sockets (integrated 2-port switch)
- Package includes server module
SIMATIC IM 155-6PN Standard with a PROFINET interface for SIMATIC BusAdapters
- Two types of delivery:
- As package with IM155-6PN ST, with pre-assembled BA 2xRJ45 BusAdapter, including server module
- As package with IM155-6PN ST, without BusAdapter, including server module
- Max. 32 I/O modules, also PROFIsafe modules, with complete diagnostic support
- Expansion option with max. 16 modules from the ET 200AL series using the BU-Send BaseUnit and the BA-Send BusAdapter
- Max. 256 bytes in each case for input and output data per module and max. 512 bytes per station (depending on configuration)
- Data update time: typ.1 ms
- Selection of the type of connection of the PROFINET by means of SIMATIC BusAdapter (BusAdapter for copper cables only)
Siemens Interface Modules ET 200SP Product Specifications:
Article number | 6ES7155-6AR00-0AN0 | 6ES7155-6AA01-0BN0 | 6ES7155-6AU01-0BN0 |
ET 200SP, IM155-6PN Basic | ET 200SP, IM155-6PN ST incl. BA 2xRJ45 | ET 200SP, IM155-6PN ST | |
General information | |||
Product type designation | IM 155-6 PN BA | IM 155-6 PN ST | IM 155-6 PN ST |
HW functional status | from FS04 | FS01 | From FS03 |
Firmware version | |||
● FW update possible | Yes | Yes | Yes |
Product function | |||
● I&M data | Yes; I&M0 to I&M3 | Yes; I&M0 to I&M3 | Yes; I&M0 to I&M3 |
● Module swapping during operation (hot swapping) | Yes; Single hot swapping | Yes; Single hot swapping | Yes; Single hot swapping |
● Isochronous mode | No | No | No |
Engineering with | |||
● STEP 7 TIA Portal configurable/integrated from version | V13 SP1 | V14 | V14 |
● STEP 7 configurable/integrated from version | V5.5 SP4 and higher | V5.5 SP4 and higher | V5.5 SP4 and higher |
● PROFINET from GSD version/GSD revision | V2.3 / – | V2.3 / – | V2.3 / – |
Configuration control | |||
via dataset | Yes | Yes | Yes |
Supply voltage | |||
Rated value (DC) | 24 V | 24 V | 24 V |
permissible range, lower limit (DC) | 19.2 V | 19.2 V | 19.2 V |
permissible range, upper limit (DC) | 28.8 V | 28.8 V | 28.8 V |
Reverse polarity protection | Yes | Yes | Yes |
Short-circuit protection | Yes | Yes | |
Mains buffering | |||
● Mains/voltage failure stored energy time | 5 ms | 10 ms | 10 ms |
Input current | |||
Current consumption (rated value) | 450 mA | 450 mA | |
Current consumption, max. | 300 mA | 550 mA | 550 mA |
Inrush current, max. | 3.7 A | 3.7 A | |
I²t | 0.09 A²·s | 0.09 A²·s | 0.09 A²·s |
Power | |||
Infeed power to the backplane bus | 4.5 W | 4.5 W | |
Power loss | |||
Power loss, typ. | 1.8 W | 1.9 W | 1.9 W |
Address area | |||
Address space per module | |||
● Address space per module, max. | 32 byte; per input / output | 256 byte; per input / output | 256 byte; per input / output |
Address space per station | |||
● Address space per station, max. | 32 byte; per input / output | 512 byte; Dependent on configuration | 512 byte; Dependent on configuration |
Hardware configuration | |||
Rack | |||
● Quantity of operable ET 200SP modules, max. | 12 | 32 | 32 |
● Quantity of operable ET 200AL modules, max. | 0 | 16 | 16 |
Submodules | |||
● Number of submodules per station, max. | 256 | 256 | |
Interfaces | |||
Number of PROFINET interfaces | 1; 2 ports (switch) | 1; 2 ports (switch) | 1; 2 ports (switch) |
1. Interface | |||
Interface types | |||
● RJ 45 (Ethernet) | Yes; 2 integrated RJ45 ports | Yes; Pre-assembled BusAdapter BA 2x RJ45 | |
● Number of ports | 2 | 2 | 2 |
● integrated switch | Yes | Yes | Yes |
● BusAdapter (PROFINET) | No | Yes; compatible BusAdapters: BA 2x RJ45, BA 2x FC, BA 2x M12 | Yes; compatible BusAdapters: BA 2x RJ45, BA 2x FC, BA 2x M12 |
Protocols | |||
● PROFINET IO Device | Yes | Yes | Yes |
● Open IE communication | Yes | Yes | Yes |
● Media redundancy | Yes; PROFINET MRP | Yes; PROFINET MRP | Yes; PROFINET MRP |
Interface types | |||
RJ 45 (Ethernet) | |||
● Transmission procedure | PROFINET with 100 Mbit/s full duplex (100BASE-TX) | PROFINET with 100 Mbit/s full duplex (100BASE-TX) | PROFINET with 100 Mbit/s full duplex (100BASE-TX) |
● 10 Mbps | No | ||
● 100 Mbps | Yes; PROFINET with 100 Mbit/s full duplex (100BASE-TX) | Yes; PROFINET with 100 Mbit/s full duplex (100BASE-TX) | Yes; PROFINET with 100 Mbit/s full duplex (100BASE-TX) |
● Autonegotiation | Yes | Yes | Yes |
● Autocrossing | Yes | Yes | Yes |
Protocols | |||
PROFINET IO Device | |||
Services | |||
— IRT | No | Yes; with send cycles of between 250 µs and 4 ms in increments of 125 µs | Yes; with send cycles of between 250 µs and 4 ms in increments of 125 µs |
— PROFIenergy | No | Yes | Yes |
— Prioritized startup | No | Yes | Yes |
— Shared device | No | Yes | Yes |
— Number of IO Controllers with shared device, max. | 2 | 2 | |
Redundancy mode | |||
● PROFINET system redundancy (S2) | No | No | No |
Media redundancy | |||
— MRP | Yes | Yes | Yes |
— MRPD | No | No | No |
Open IE communication | |||
● TCP/IP | Yes | Yes | Yes |
● SNMP | Yes | Yes | Yes |
● LLDP | Yes | Yes | Yes |
Isochronous mode | |||
Equidistance | No | ||
Interrupts/diagnostics/status information | |||
Status indicator | Yes | Yes | Yes |
Alarms | Yes | Yes | Yes |
Diagnostics function | Yes | Yes | Yes |
Diagnostics indication LED | |||
● RUN LED | Yes; green LED | Yes; green LED | Yes; green LED |
● ERROR LED | Yes; red LED | Yes; red LED | Yes; red LED |
● MAINT LED | Yes; Yellow LED | Yes; Yellow LED | Yes; Yellow LED |
● Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED | Yes; green PWR LED | Yes; green PWR LED |
● Connection display LINK TX/RX | Yes; 2x green link LEDs on BusAdapter | Yes; 2x green link LEDs on BusAdapter | Yes; 2x green link LEDs on BusAdapter |
Potential separation | |||
between backplane bus and electronics | No | No | No |
between PROFINET and all other circuits | Yes | Yes; 1 500 V AC | Yes; 1500 V AC (type test) |
between supply and all other circuits | No | No | No |
Permissible potential difference | |||
between different circuits | Safety extra low voltage SELV | Safety extra low voltage SELV | |
Isolation | |||
Isolation tested with | 707 V DC (type test) | 707 V DC (type test) | |
Standards, approvals, certificates | |||
Network loading class | 2 | 2 | 2 |
Security level | According to Security Level 1 Test Cases V1.1.1 | According to Security Level 1 Test Cases V1.1.1 | |
Ambient conditions | |||
Ambient temperature during operation | |||
● horizontal installation, min. | -30 °C | 0 °C | 0 °C |
● horizontal installation, max. | 60 °C | 60 °C | 60 °C |
● vertical installation, min. | -30 °C | 0 °C | 0 °C |
● vertical installation, max. | 50 °C | 50 °C | 50 °C |
Altitude during operation relating to sea level | |||
● Installation altitude above sea level, max. | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual | 5 000 m |
connection method / header | |||
ET-Connection | |||
● via BU/BA Send | No | Yes; + 16 ET 200AL modules | Yes; + 16 ET 200AL modules |
Dimensions | |||
Width | 35 mm | 50 mm | 50 mm |
Height | 117 mm | 117 mm | 117 mm |
Depth | 74 mm | 74 mm | 74 mm |
Weights | |||
Weight, approx. | 125 g | 190 g; IM 155-6 PN BA with 2x RJ45 ports and server module | 147 g; without BusAdapter |
Weight | N/A |
---|---|
Dimensions | N/A |
Related products
-
Select options This product has multiple variants. The options may be chosen on the product page Details
-
Select options This product has multiple variants. The options may be chosen on the product page Details
-
Select options This product has multiple variants. The options may be chosen on the product page Details
-
Select options This product has multiple variants. The options may be chosen on the product page Details
-
Select options This product has multiple variants. The options may be chosen on the product page Details
-
Select options This product has multiple variants. The options may be chosen on the product page Details