The fail-safe ET 200SP modules can be used to implement the safety-related application requirements as an integrated part of the overall automation. The safety functions required for fail-safe operation are integrated in the modules. Communication with the fail-safe SIMATIC S7 CPUs is performed by means of PROFIsafe. The modules can be operated both in centralized and distributed configurations.
| Article number | 6ES7136-6DB00-0CA0 | 6ES7136-6DC00-0CA0 |
| ET 200SP, El-Mod., F-DQ 4xDC 24V/2A | ET 200SP, F-DQ 8x 24VDC/0.5A PP | |
| General information | ||
| Product type designation | F-DQ 4×24 V DC/2A HF | F-DQ 8×24 V DC/0.5 A PP HF |
| Firmware version | ||
| ● FW update possible | Yes | |
| usable BaseUnits | BU type A0 | BU type A0 |
| Color code for module-specific color identification plate | CC02 | |
| Product function | ||
| ● I&M data | Yes; I&M0 to I&M3 | Yes; I&M0 to I&M3 |
| Engineering with | ||
| ● STEP 7 TIA Portal configurable/integrated from version | V12 | V14 SP1 with HSP 202 |
| ● STEP 7 configurable/integrated from version | V5.5 SP3 / – | V5.5 SP4 HF5 |
| ● PROFINET from GSD version/GSD revision | V2.31 | V2.31 |
| Supply voltage | ||
| Rated value (DC) | 24 V | 24 V |
| permissible range, lower limit (DC) | 20.4 V | 19.2 V |
| permissible range, upper limit (DC) | 28.8 V | 28.8 V |
| Reverse polarity protection | Yes | Yes |
| power supply according to NEC Class 2 required | No | No |
| Input current | ||
| Current consumption (rated value) | 75 mA; without load | 75 mA; without load |
| Current consumption, max. | 21 mA; From the backplane bus | 21 mA; From the backplane bus |
| output voltage / header | ||
| Rated value (DC) | 24 V | 24 V |
| Power | ||
| Power available from the backplane bus | 70 mW | 70 mW |
| Power loss | ||
| Power loss, typ. | 4 W | 3 W |
| Address area | ||
| Address space per module | ||
| ● Inputs | 5 byte | 6 byte; 5 bytes non-RIOforFA; 6 bytes RIOforFA |
| ● Outputs | 5 byte | 6 byte; 5 bytes non-RIOforFA; 6 bytes RIOforFA |
| Hardware configuration | ||
| Automatic encoding | Yes | Yes |
| ● Electronic coding element type F | Yes | Yes |
| Digital outputs | ||
| Type of digital output | Transistor | Transistor |
| Number of digital outputs | 4 | 8 |
| Digital outputs, parameterizable | Yes | Yes |
| Short-circuit protection | Yes | Yes |
| ● Response threshold, typ. | > 3.3 A | Min. 0.7 A |
| Open-circuit detection | Yes | No |
| ● Response threshold, typ. | 8 mA | |
| Overload protection | Yes | |
| ● Response threshold, typ. | 2.9 A | |
| Limitation of inductive shutdown voltage to | Typ. -2x 47 V | Typ. -39 V |
| Controlling a digital input | Yes | |
| Switching capacity of the outputs | ||
| ● with resistive load, max. | 2 A | 0.5 A |
| ● on lamp load, max. | 10 W | 2 W |
| Load resistance range | ||
| ● lower limit | 12 Ω | 48 Ω |
| ● upper limit | 2 000 Ω | 12 000 Ω |
| Output voltage | ||
| ● for signal “1”, min. | 24 V; L+ (-0.5 V) | 24 V; L+ (-0.5 V) |
| Output current | ||
| ● for signal “1” rated value | 2 A | 0.5 A |
| ● for signal “0” residual current, max. | 0.5 mA | 0.5 mA |
| Switching frequency | ||
| ● with resistive load, max. | 30 Hz; Symmetrical | 30 Hz; Symmetrical |
| ● with inductive load, max. | 0.1 Hz; according to IEC 60947-5-1, DC-13, symmetrical | 0.1 Hz; according to IEC 60947-5-1, DC-13, symmetrical |
| ● with capacitive load, max. | 2 Hz; Symmetrical | |
| ● on lamp load, max. | 10 Hz; Symmetrical | 10 Hz; Symmetrical |
| Total current of the outputs | ||
| ● Current per channel, max. | 2 A; note derating data in the manual | 0.5 A; note derating data in the manual |
| ● Current per module, max. | 6 A; note derating data in the manual | 3 A; note derating data in the manual |
| Total current of the outputs (per module) | ||
| horizontal installation | ||
| — up to 40 °C, max. | 3 A | |
| — up to 50 °C, max. | 2.5 A | |
| — up to 60 °C, max. | 2 A | |
| vertical installation | ||
| — up to 50 °C, max. | 2 A | |
| Cable length | ||
| ● shielded, max. | 1 000 m | 100 m |
| ● unshielded, max. | 500 m | 100 m |
| Interrupts/diagnostics/status information | ||
| Diagnostics function | Yes | Yes |
| Substitute values connectable | No | No |
| Alarms | ||
| ● Diagnostic alarm | Yes | Yes |
| Diagnostics indication LED | ||
| ● RUN LED | Yes; green LED | Yes; green LED |
| ● ERROR LED | Yes; red LED | Yes; red LED |
| ● Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED | Yes; green PWR LED |
| ● Channel status display | Yes; green LED | Yes; green LED |
| ● for channel diagnostics | Yes; red LED | Yes; red LED |
| ● for module diagnostics | Yes; green/red DIAG LED | Yes; green/red DIAG LED |
| Potential separation | ||
| Potential separation channels | ||
| ● between the channels | No | No |
| ● between the channels and backplane bus | Yes | Yes |
| ● between the channels and the power supply of the electronics | No | No |
| Isolation | ||
| Isolation tested with | 707 V DC (type test) | 707 V DC (type test) |
| Standards, approvals, certificates | ||
| Suitable for safety functions | Yes | Yes |
| Highest safety class achievable in safety mode | ||
| ● Performance level according to ISO 13849-1 | PLe | PLe |
| ● Category according to ISO 13849-1 | Cat. 4 | |
| ● SIL acc. to IEC 61508 | SIL 3 | SIL 3 |
| Probability of failure (for service life of 20 years and repair time of 100 hours) | ||
| — Low demand mode: PFDavg in accordance with SIL2 | < 2.00E-04 | |
| — Low demand mode: PFDavg in accordance with SIL3 | < 2.00E-05 | < 6.00E-05 |
| — High demand/continuous mode: PFH in accordance with SIL2 | < 1.00E-08 1/h | |
| — High demand/continuous mode: PFH in accordance with SIL3 | < 1.00E-09 1/h | < 2.00E-09 1/h |
| Ambient conditions | ||
| Ambient temperature during operation | ||
| ● horizontal installation, min. | 0 °C | 0 °C |
| ● horizontal installation, max. | 60 °C | 60 °C |
| ● vertical installation, min. | 0 °C | 0 °C |
| ● vertical installation, max. | 50 °C | 50 °C |
| Altitude during operation relating to sea level | ||
| ● Installation altitude above sea level, max. | 4 000 m; Restrictions for installation altitudes > 2 000 m, see manual | 4 000 m; with derating |
| Dimensions | ||
| Width | 15 mm | 15 mm |
| Height | 73 mm | 73 mm |
| Depth | 58 mm | 58 mm |
| Weights | ||
| Weight, approx. | 57 g | 48 g |