$ 34.76 – $ 48.62
With the BaseUnits (BUs), the ET 200SP offers a rugged and service-friendly design with permanent wiring:
An ET 200SP station can be expanded via one ‘BU-Send’ BaseUnit with a “BA-Send” BusAdapter plugged onto it with up to 16 modules from the ET 200AL series of I/O devices with IP67 protection.
Article number | 6ES7193-6BP00-0DU0 | 6ES7193-6B0-0BU0P0 |
BaseUnit Type U0, BU20-P16+A0+2D, PU 1 | BaseUnit Type U0, BU20-P16+A0+2B, PU 1 | |
General information | ||
Product type designation | BU type U0 | BU type U0 |
HW functional status | FS10 and higher | FS10 and higher |
Supply voltage | ||
Rated value (DC) | See manual | See manual |
● For P1 and P2 bus | 120 V | 120 V |
● For AUX bus | 120 V; Equal potential group to P1/P2 bus or PE | 120 V; Equal potential group to P1/P2 bus or PE |
● for process terminals | 120 V | 120 V |
Rated value (AC) | See manual | See manual |
● For P1 and P2 bus | 277 V | 277 V |
● For AUX bus | 277 V; Equal potential group to P1/P2 bus or PE | 277 V; Equal potential group to P1/P2 bus or PE |
● for process terminals | 277 V | 277 V |
external protection for power supply lines | Yes | |
Mains filter | ||
● integrated | No | No |
Current carrying capacity | ||
up to 60 °C, max. | 10 A | 10 A |
For P1 and P2 bus, max. | 10 A | 10 A |
For AUX bus, max. | 10 A | 10 A |
For process terminals, max. | 10 A; Point of contact, derating depends on the module | 10 A; Point of contact, derating depends on the module |
Hardware configuration | ||
Automatic encoding | Yes | Yes |
Formation of potential groups | ||
● New potential group | Yes | No |
● Potential group continued from the left | No | Yes |
Slots | ||
● Number of slots | 1 | 1 |
Potential separation | ||
between backplane bus and supply voltage | Yes | Yes |
between process terminals and supply voltage | Yes; Not applicable for process terminals 15 and 16 | Yes; Not applicable for process terminals 15 and 16 |
between power bus and supply voltage | No | No |
Isolation | ||
Isolation tested with | 3 100 V DC | 3 100 V DC |
Ambient conditions | ||
Ambient temperature during operation | ||
● horizontal installation, min. | -30 °C | -30 °C |
● horizontal installation, max. | 60 °C | 60 °C |
● vertical installation, min. | -30 °C | -30 °C |
● vertical installation, max. | 50 °C | 50 °C |
Altitude during operation relating to sea level | ||
● Installation altitude above sea level, max. | 3 000 m | 3 000 m |
connection method / header | ||
Terminals | ||
● Terminal type | Push-in terminal | Push-in terminal |
● Conductor cross-section, min. | 0.14 mm²; 0.2 mm² without wire end ferrule | 0.14 mm²; 0.2 mm² without wire end ferrule |
● Conductor cross-section, max. | 2.5 mm²; 1.5 mm² with wire end ferrule | 2.5 mm²; 1.5 mm² with wire end ferrule |
● Number of process terminals to I/O module | 16 | 16 |
● Number of terminals to AUX bus | 0 | 0 |
● Number of add-on terminals | 0 | 0 |
● Number of terminals with connection to P1 and P2 bus | 2 | 2 |
Dimensions | ||
Width | 20 mm | 20 mm |
Height | 117 mm | 117 mm |
Depth | 35 mm | 35 mm |
Weights | ||
Weight, approx. | 50 g | 50 g |