			$ 299.92
The IM 157-1 PN interface module enables the connection of ET 200AL to PROFINET and handles the communication between the I/O modules and the higher-level PROFINET I/O controller in the PLC autonomously.
| Article number | 6ES7157-1AB00-0AB0 | |
| ET 200AL, IM 157-1 PN | ||
| General information | ||
| Product type designation | IM 157-1 PN | |
| HW functional status | FS02 | |
| Firmware version | V1.0.x | |
| Vendor identification (VendorID) | 002AH | |
| Product function | ||
| ● I&M data | Yes; I&M0 to I&M4 | |
| Engineering with | ||
| ● STEP 7 TIA Portal configurable/integrated from version | STEP 7 V13 SP1 or higher | |
| ● STEP 7 configurable/integrated from version | From V5.5 SP4 Hotfix 3 | |
| ● PROFINET from GSD version/GSD revision | GSDML V2.3.1 | |
| Configuration control | ||
| via dataset | Yes | |
| Supply voltage | ||
| power supply according to NEC Class 2 required | No | |
| Load voltage 1L+ | ||
| ● Rated value (DC) | 24 V | |
| ● permissible range, lower limit (DC) | 20.4 V | |
| ● permissible range, upper limit (DC) | 28.8 V | |
| ● Reverse polarity protection | Yes; against destruction | |
| Input current | ||
| Current consumption (rated value) | 100 mA | |
| from load voltage 1L+ (unswitched voltage) | 4 A; Maximum value | |
| from load voltage 2L+, max. | 4 A; Maximum value | |
| Power loss | ||
| Power loss, typ. | 2.9 W | |
| Address area | ||
| Address space per station | ||
| ● Address space per station, max. | 1 430 byte | |
| Interfaces | ||
| Number of PROFINET interfaces | 1 | |
| 1. Interface | ||
| Interface type | PROFINET | |
| Interface types | ||
| ● M12 port | Yes; 2x M12 D-coded | |
| ● integrated switch | Yes | |
| Protocols | ||
| ● PROFINET IO Device | Yes | |
| ● Open IE communication | Yes | |
| Interface types | ||
| M12 port | ||
| ● Transmission procedure | PROFINET with 100 Mbit/s full duplex (100BASE-TX) | |
| ● 10 Mbps | Yes; for Ethernet services | |
| ● 100 Mbps | Yes; PROFINET with 100 Mbit/s full duplex (100BASE-TX) | |
| ● Autonegotiation | Yes | |
| ● Autocrossing | Yes | |
| Protocols | ||
| PROFINET IO Device | ||
| Services | ||
| — IRT | Yes; 250 µs, 500 µs, 1 ms, 2 ms, 4 ms, 8 ms, 16 ms, 32 ms, 64 ms, 128 ms | |
| — PROFIenergy | Yes | |
| — Shared device | Yes | |
| — Number of IO Controllers with shared device, max. | 4 | |
| Redundancy mode | ||
| Media redundancy | ||
| — MRP | Yes | |
| — MRPD | Yes | |
| Open IE communication | ||
| ● TCP/IP | Yes | |
| ● SNMP | Yes | |
| ● LLDP | Yes | |
| Interrupts/diagnostics/status information | ||
| Diagnostics function | Yes | |
| Alarms | ||
| ● Diagnostic alarm | Yes | |
| Diagnostics indication LED | ||
| ● RUN LED | Yes; green LED | |
| ● ERROR LED | Yes; red LED | |
| ● MAINT LED | Yes; Yellow LED | |
| ● Connection display LINK TX/RX | Yes; 2x green LED | |
| Potential separation | ||
| between the load voltages | Yes | |
| between PROFINET and all other circuits | Yes | |
| Isolation | ||
| Isolation tested with | 707 V DC (type test) | |
| Degree and class of protection | ||
| IP degree of protection | IP65/67 | |
| Standards, approvals, certificates | ||
| Suitable for safety-related tripping of standard modules | Yes; From FS01 | |
| Highest safety class achievable for safety-related tripping of standard modules | ||
| ● Performance level according to ISO 13849-1 | PL d | |
| ● Category according to ISO 13849-1 | Cat. 3 | |
| ● SIL acc. to IEC 62061 | SIL 2 | |
| Ambient conditions | ||
| Ambient temperature during operation | ||
| ● min. | -25 °C | |
| ● max. | 55 °C | |
| connection method / header | ||
| Design of electrical connection for supply voltage | M8, 4-pole | |
| ET-Connection | ||
| ● ET-Connection | M8, 4-pin, shielded | |
| Dimensions | ||
| Width | 45 mm | |
| Height | 159 mm | |
| Depth | 40 mm | |
| Weights | ||
| Weight, approx. | 263 g | |