Power rating | 30 W | |||||
---|---|---|---|---|---|---|
Output voltage (VDC) | 5 V | 12 V | 15 V | 24 V | ||
Efficiency *1 | 100 VAC input | 81% typ. | 84% typ. | 86% typ. | 86% typ. | |
200 VAC input | 81% typ. | 86% typ. | 88% typ. | 88% typ. | ||
230 VAC input | 81% typ. | 86% typ. | 88% typ. | 89% typ. | ||
Input | Voltage range *1 | Single phase, 85 to 264 VAC, 80 to 370 VDC | ||||
Frequency *1 | 50/60 Hz (47 to 450 Hz) | |||||
Current *1 | 100 VAC input | 0.72 A typ. | ||||
200 VAC input | 0.43 A typ. | |||||
Power factor *1 | — | |||||
Leakage current *1 |
100 VAC input | 0.5 mA max. | ||||
200 VAC input | 1 mA max. | |||||
Inrush current *1 (for a cold start at 25°C) |
100 VAC input | 14 A typ. | ||||
200 VAC input | 28 A typ. | |||||
Output | Rated Output Current | 6 A | 3 A | 2.4 A | 1.5 A | |
Voltage adjustment range *1 | -10% to 15% (with V.ADJ) | |||||
Ripple & Noise voltage *1 |
100 to 240 VAC input |
50 mVp-p max. | 60 mVp-p max. | 50 mVp-p max. | 60 mVp-p max. | |
Input variation influence *1 | 0.5% max. | |||||
Load variation influence *1 | 1.0% max. | |||||
Temperature variation influence |
100 to 240 VAC input |
0.05%/°C max. | ||||
Startup time *1 | 100 VAC input | 1,000 ms max. | ||||
200 VAC input | 1,000 ms max. | |||||
Hold time *1 | 100 VAC input | 11 ms typ. | 10 ms typ. | 11 ms typ. | 10 ms typ. | |
200 VAC input | 60 ms typ. | 50 ms typ. | 50 ms typ. | 55 ms typ. | ||
Additional functions |
Overload protection | Yes, automatic reset | ||||
Overvoltage protection *1 | Yes, 120% or higher of rated output voltage, power shut off (shut off the input voltage and turn on the input again) |
|||||
Overheat protection | No | |||||
Series operation | Yes (For up to two Power Supplies, external diodes are required.) | |||||
Parallel operation | No (However, backup operation is possible, external diodes are required.) | |||||
Remote sensing | No | |||||
Remote control | No | |||||
Output indicator | Yes (LED: Green) | |||||
Insulation | Withstand voltage | 3 kVAC for 1 min. (between all input terminals and output terminals) current cutoff 20 mA |
||||
2 kVAC for 1 min. (between all input terminals and PE terminals) current cutoff 20 mA |
||||||
1 kVAC for 1 min. (between all output terminals and PE terminals) current cutoff 20 mA |
||||||
Insulation resistance | 100 MΩ min. (between all output terminals and all input terminals/PE terminals) at 500 VDC |
|||||
Environ- ment |
Ambient operating temperature |
-20 to 70°C (Derating is required according to the temperature.) (with no condensation or icing) |
||||
Storage temperature | -25 to 75°C (with no condensation or icing) | |||||
Ambient operating humidity | 90% max. (Storage humidity: 90% max.) | |||||
Vibration resistance | 10 to 55 Hz, 4.5 G max., 0.375-mm half amplitude for 2 h each in X, Y, and Z directions |
|||||
Shock resistance | 150 m/s2, 3 times each in ±X, ±Y, ±Z directions | |||||
Reliability | MTBF | 135,000 hrs min. | ||||
Life expectancy *1 | 10 years min. | |||||
Con- struction |
Dimensions (W×H×D) | Refer to Dimensions. | ||||
Weight | 250 g | |||||
Cooling fan | No | |||||
Degree of protection | — | |||||
Standards | Harmonic current emissions | Conforms to EN 61000-3-2 | ||||
EMI *1 | Conducted Emissions |
Conforms to EN 61204-3 Class B, EN 55011 Class B | ||||
Radiated Emissions |
Conforms to EN 61204-3 Class B, EN 55011 Class B | |||||
EMS | Conforms to EN 61204-3 high severity levels | |||||
Safety Standards *2 | UL 508 (Listing, excluding models with connector option) UL 62368-1 (Recognition, OVCII [≤ 3,000 m], Pol2) CSA C22.2 No.107.1 (excluding models with connector option) CSA C22.2 No.62368-1 (excluding models with connector option) EN 62477-1 (OVCIII [≤ 2,000 m], OVCII [> 2,000 m and ≤ 3,000 m], Pol2) EN/IEC 62368-1 (OVCII [≤ 3,000 m], Pol2) Conforms to EN/IEC 61558-2-16 Conforms to PELV (EN/IEC 60204-1) RCM (EN61000-6-4) |
|||||
Marine Standards | No | |||||
SEMI | Conforms to F47-0706 (200 VAC input) |
Power rating | 50 W | |||||
---|---|---|---|---|---|---|
Output voltage (VDC) | 5 V | 12 V | 15 V | 24 V | ||
Efficiency *1 | 100 VAC input | 81% typ. | 84% typ. | 86% typ. | 86% typ. | |
200 VAC input | 82% typ. | 86% typ. | 88% typ. | 89% typ. | ||
230 VAC input | 82% typ. | 86% typ. | 88% typ. | 89% typ. | ||
Input | Voltage range *1 | Single phase, 85 to 264 VAC, 80 to 370 VDC | ||||
Frequency *1 | 50/60 Hz (47 to 450 Hz) | |||||
Current *1 | 100 VAC input | 1.1 A typ. | ||||
200 VAC input | 0.62 A typ. | |||||
Power factor *1 | — | |||||
Leakage current *1 |
100 VAC input | 0.5 mA max. | ||||
200 VAC input | 1 mA max. | |||||
Inrush current *1 (for a cold start at 25°C) |
100 VAC input | 14 A typ. | ||||
200 VAC input | 28 A typ. | |||||
Output | Rated Output Current | 8 A | 4.3 A | 3.5 A | 2.2A | |
Voltage adjustment range *1 | -10% to 15% (with V.ADJ) | |||||
Ripple & Noise voltage *1 |
100 to 240 VAC input |
40 mVp-p max. | 40 mVp-p max. | 40 mVp-p max. | 60 mVp-p max. | |
Input variation influence *1 | 0.5% max. | |||||
Load variation influence *1 | 1.0% max. | |||||
Temperature variation influence |
100 to 240 VAC input |
0.05%/°C max. | ||||
Startup time *1 | 100 VAC input | 1,000 ms max. | ||||
200 VAC input | 1,000 ms max. | |||||
Hold time *1 | 100 VAC input | 14 ms typ. | 11 ms typ. | 10 ms typ. | 10 ms typ. | |
200 VAC input | 75 ms typ. | 60 ms typ. | 60 ms typ. | 55 ms typ. | ||
Additional functions |
Overload protection | Yes, automatic reset | ||||
Overvoltage protection *1 | Yes, 120% or higher of rated output voltage, power shut off (shut off the input voltage and turn on the input again) |
|||||
Overheat protection | No | |||||
Series operation | Yes (For up to two Power Supplies, external diodes are required.) | |||||
Parallel operation | No (However, backup operation is possible, external diodes are required.) | |||||
Remote sensing | No | |||||
Remote control | No | |||||
Output indicator | Yes (LED: Green) | |||||
Insulation | Withstand voltage | 3 kVAC for 1 min. (between all input terminals and output terminals) current cutoff 20 mA |
||||
2 kVAC for 1 min. (between all input terminals and PE terminals) current cutoff 20 mA |
||||||
1 kVAC for 1 min. (between all output terminals and PE terminals) current cutoff 20 mA |
||||||
500 VAC for 1 min. (between all output terminals and RC terminals) current cutoff 20 mA |
||||||
Insulation resistance | 100 MΩ min. (between all output terminals and all input terminals/PE terminals) at 500 VDC |
|||||
Environ- ment |
Ambient operating temperature |
-20 to 70°C (Derating is required according to the temperature.) (with no condensation or icing) |
||||
Storage temperature | -25 to 75°C (with no condensation or icing) | |||||
Ambient operating humidity | 90% max. (Storage humidity: 90% max.) | |||||
Vibration resistance | 10 to 55 Hz, 4.5 G max., 0.375-mm half amplitude for 2 h each in X, Y, and Z directions |
|||||
Shock resistance | 150 m/s2, 3 times each in ±X, ±Y, ±Z directions | |||||
Reliability | MTBF | 135,000 hrs min. | ||||
Life expectancy *1 | 10 years min. | |||||
Con- struction |
Dimensions (W×H×D) | Refer to Dimensions. | ||||
Weight | 300 g | |||||
Cooling fan | No | |||||
Degree of protection | — | |||||
Standards | Harmonic current emissions | Conforms to EN 61000-3-2 | ||||
EMI *1 | Conducted Emissions |
Conforms to EN 61204-3 Class B, EN 55011 Class B | ||||
Radiated Emissions |
Conforms to EN 61204-3 Class B, EN 55011 Class B | |||||
EMS | Conforms to EN 61204-3 high severity levels | |||||
Safety Standards *2 | UL 508 (Listing, excluding models with connector option) UL 62368-1 (Recognition, OVCII [≤ 3,000 m], Pol2) CSA C22.2 No.107.1 (excluding models with connector option) CSA C22.2 No.62368-1 (excluding models with connector option) EN 62477-1 (OVCIII [≤ 2,000 m], OVCII [> 2,000 m and ≤ 3,000 m], Pol2) EN/IEC 62368-1 (OVCII [≤ 3,000 m], Pol2) Conforms to EN/IEC 61558-2-16 Conforms to PELV (EN/IEC 60204-1) RCM (EN61000-6-4) |
|||||
Marine Standards | No | |||||
SEMI | Conforms to F47-0706 (200 VAC input) |
Power rating | 100 W | |||||
---|---|---|---|---|---|---|
Output voltage (VDC) | 5 V | 12 V | 15 V | 24 V | ||
Efficiency *1 | 100 VAC input | 79% typ. | 84% typ. | 85% typ. | 87% typ. | |
200 VAC input | 81% typ. | 86% typ. | 87% typ. | 89% typ. | ||
230 VAC input | 81% typ. | 86% typ. | 87% typ. | 89% typ. | ||
Input | Voltage range *1 | Single phase, 85 to 264 VAC, 80 to 370 VDC | ||||
Frequency *1 | 50/60 Hz (47 to 450 Hz) | |||||
Current *1 | 100 VAC input | 2.1 A typ. | ||||
200 VAC input | 1.2 A typ. | |||||
Power factor *1 | — | |||||
Leakage current *1 |
100 VAC input | 0.5 mA max. | ||||
200 VAC input | 1 mA max. | |||||
Inrush current *1 (for a cold start at 25°C) |
100 VAC input | 14 A typ. | ||||
200 VAC input | 28 A typ. | |||||
Output | Rated Output Current | 16 A | 8.5 A | 7 A | 4.5 A | |
Voltage adjustment range *1 | -10% to 15% (with V.ADJ) | |||||
Ripple & Noise voltage *1 |
100 to 240 VAC input |
70 mVp-p max. | 90 mVp-p max. | 100 mVp-p max. | 80 mVp-p max. | |
Input variation influence *1 | 0.5% max. | |||||
Load variation influence *1 | 1.0% max. | |||||
Temperature variation influence |
100 to 240 VAC input |
0.05%/°C max. | ||||
Startup time *1 | 100 VAC input | 1,000 ms max. | ||||
200 VAC input | 1,000 ms max. | |||||
Hold time *1 | 100 VAC input | 12 ms typ. | 11 ms typ. | 11 ms typ. | 10 ms typ. | |
200 VAC input | 70 ms typ. | 55 ms typ. | 55 ms typ. | 55 ms typ. | ||
Additional functions |
Overload protection | Yes, automatic reset | ||||
Overvoltage protection *1 | Yes, 120% or higher of rated output voltage, power shut off (shut off the input voltage and turn on the input again) |
|||||
Overheat protection | No | |||||
Series operation | Yes (For up to two Power Supplies, external diodes are required.) | |||||
Parallel operation | No (However, backup operation is possible, external diodes are required.) | |||||
Remote sensing | No | |||||
Remote control | Yes (Only for models with remote control option) | |||||
Output indicator | Yes (LED: Green) | |||||
Insulation | Withstand voltage | 3 kVAC for 1 min. (between all input terminals and output terminals) current cutoff 20 mA |
||||
2 kVAC for 1 min. (between all input terminals and PE terminals) current cutoff 20 mA |
||||||
1 kVAC for 1 min. (between all output terminals and PE terminals) current cutoff 20 mA |
||||||
Only Remote control 500 VAC for 1 min. (between all output terminals and RC terminals) current cutoff 20 mA |
||||||
Insulation resistance | 100 MΩ min. (between all output terminals and all input terminals/PE terminals) at 500 VDC |
|||||
Environ- ment |
Ambient operating temperature |
-20 to 70°C (Derating is required according to the temperature. Refer to Engineering Data) (with no condensation or icing) |
||||
Storage temperature | -25 to 75°C (with no condensation or icing) | |||||
Ambient operating humidity | 90% max. (Storage humidity: 90% max.) | |||||
Vibration resistance | 10 to 55 Hz, 4.5 G max., 0.375-mm half amplitude for 2 h each in X, Y, and Z directions |
|||||
Shock resistance | 150 m/s2, 3 times each in ±X, ±Y, ±Z directions | |||||
Reliability | MTBF | 135,000 hrs min. | ||||
Life expectancy *1 | 10 years min. | |||||
Con- struction |
Dimensions (W×H×D) | Refer to Dimensions. | ||||
Weight | 400 g | |||||
Cooling fan | No | |||||
Degree of protection | — | |||||
Standards | Harmonic current emissions | Conforms to EN 61000-3-2 | ||||
EMI *1 | Conducted Emissions |
Conforms to EN 61204-3 Class B, EN 55011 Class B | ||||
Radiated Emissions |
Conforms to EN 61204-3 Class B, EN 55011 Class B | |||||
EMS | Conforms to EN 61204-3 high severity levels | |||||
Safety Standards *2 | UL 508 (Listing, excluding models with connector option or remote control option) UL 508 (Recognition, models with remote control option) UL 62368-1 (Recognition, OVCII [≤ 3,000 m], Pol2) CSA C22.2 No.107.1 (excluding models with connector option or remote control option) CSA C22.2 No.62368-1 (excluding models with connector option or remote control option) EN 62477-1 (OVCIII [≤ 2,000 m], OVCII [> 2,000 m and ≤ 3,000 m], Pol2) EN/IEC 62368-1 (OVCII [≤ 3,000 m], Pol2) Conforms to EN/IEC 61558-2-16 Conforms to PELV (EN/IEC 60204-1) RCM (EN61000-6-4) |
|||||
Marine Standards | No | |||||
SEMI | SEMI Conforms to F47-0706 (200 VAC input) |
Power rating | 150 W | ||||||
---|---|---|---|---|---|---|---|
Output voltage (VDC) | 5 V | 12 V | 15 V | 24 V | 48 V | ||
Efficiency *1 | 100 VAC input | 78% typ. | 84% typ. | 85% typ. | 87% typ. | 85% typ. | |
200 VAC input | 81% typ. | 87% typ. | 88% typ. | 89% typ. | 88% typ. | ||
230 VAC input | 81% typ. | 87% typ. | 88% typ. | 90% typ. | 88% typ. | ||
Input | Voltage range *1 | Single phase, 85 to 264 VAC, 80 to 370 VDC | |||||
Frequency *1 | 50 /60 Hz (47 to 450 Hz) | ||||||
Current *1 | 100 VAC input | 3 A typ. | |||||
200 VAC input | 1.8 A typ. | ||||||
Power factor *1 | — | ||||||
Leakage current *1 |
100 VAC input | 0.5 mA max. | |||||
200 VAC input | 1 mA max. | ||||||
Inrush current *1 (for a cold start at 25°C) |
100 VAC input | 14 A typ. | |||||
200 VAC input | 28 A typ. | ||||||
Output | Rated Output Current | 21 A | 13 A | 10 A | 6.5 A | 3.3 A | |
Voltage adjustment range *1 | -10% to 15% (with V.ADJ) | ||||||
Ripple & Noise voltage *1 |
100 to 240 VAC input |
100 mVp-p max. |
110 mVp-p max. |
80 mVp-p max. |
110 mVp-p max. |
120 mVp-p max. |
|
Input variation influence *1 | 0.5% max. | ||||||
Load variation influence *1 | 1.0% max. | ||||||
Temperature variation influence |
100 to 240 VAC input |
0.05%/°C max. | |||||
Startup time *1 | 100 VAC input | 1,000 ms max. | |||||
200 VAC input | 1,000 ms max. | ||||||
Hold time *1 | 100 VAC input | 14 ms typ. | 10 ms typ. | 10 ms typ. | 10 ms typ. | 11 ms typ. | |
200 VAC input | 80 ms typ. | 55 ms typ. | 55 ms typ. | 55 ms typ. | 55 ms typ. | ||
Additional functions |
Overload protection | Yes, automatic reset | |||||
Overvoltage protection *1 | Yes, 120% or higher of rated output voltage, power shut off (shut off the input voltage and turn on the input again) |
||||||
Overheat protection | No | ||||||
Series operation | Yes (For up to two Power Supplies, external diodes are required.) | ||||||
Parallel operation | No (However, backup operation is possible, external diodes are required.) | ||||||
Remote sensing | No | ||||||
Remote control | Yes (Only for models with remote control option) | ||||||
Output indicator | Yes (LED: Green) | ||||||
Insulation | Withstand voltage | 3 kVAC for 1 min.(between all input terminals and output terminals) current cutoff 20 mA |
|||||
2 kVAC for 1 min.(between all input terminals and PE terminals) current cutoff 20 mA |
|||||||
1 kVAC for 1 min.(between all output terminals and PE terminals) current cutoff 20 mA |
|||||||
Only Remote control 500 VAC for 1 min.(between all output terminals and RC terminals) current cutoff 20 mA |
|||||||
Insulation resistance | 100 MΩ min.(between all output terminals and all input terminals/PE terminals) at 500 VDC |
||||||
Environ- ment |
Ambient operating temperature |
-20 to 70°C (Derating is required according to the temperature. Refer to Engineering Data) (with no condensation or icing) |
|||||
Storage temperature | -25 to 75°C (with no condensation or icing) | ||||||
Ambient operating humidity | 90% max. (Storage humidity: 90% max.) | ||||||
Vibration resistance | 10 to 55 Hz, 4.5 G max., 0.375-mm half amplitude for 2 h each in X, Y, and Z directions |
||||||
Shock resistance | 150 m/s2, 3 times each in ±X, ±Y, ±Z directions | ||||||
Reliability | MTBF | 135,000 hrs min. | |||||
Life expectancy *1 | 10 years min. | ||||||
Con- struction |
Dimensions (W×H×D) | Refer to Dimensions on page 22. | |||||
Weight | 500 g | ||||||
Cooling fan | No | ||||||
Degree of protection | — | ||||||
Standards | Harmonic current emissions | Conforms to EN 61000-3-2 (Applicable at 80% or less of the rated load.) | |||||
EMI *1 | Conducted Emissions |
Conforms to EN 61204-3 Class B, EN 55011 Class B | |||||
Radiated Emissions |
Conforms to EN 61204-3 Class B, EN 55011 Class B | ||||||
EMS | Conforms to EN 61204-3 high severity levels | ||||||
Safety Standards *2 | UL 508 (Listing, excluding models with connector option or remote control option) UL 508 (Recognition, models with remote control option) UL 62368-1 (Recognition, OVCII [≤ 3,000 m], Pol2) CSA C22.2 No.107.1 (excluding models with connector option or remote control option) CSA C22.2 No.62368-1 (excluding models with connector option or remote control option) EN 62477-1 (OVCIII [≤ 2,000 m], OVCII [> 2,000 m and ≤ 3,000 m], Pol2) EN/IEC 62368-1 (OVCII [≤ 3,000 m], Pol2) Conforms to EN/IEC 61558-2-16 Conforms to PELV (EN/IEC 60204-1) RCM (EN61000-6-4) BIS (IS 13252 (Part 1)/IEC 60950-1) (Output voltage 24 V type only. However, excluding S8FSG15024C-500 and S8FS-G15024CD-500.) |
||||||
Marine Standards | No | ||||||
SEMI | Conforms to F47-0706 (200 VAC input) |
Power rating | 300 W | |||||
---|---|---|---|---|---|---|
Output voltage (VDC) | 12 V | 15 V | 24 V | 48 V | ||
Efficiency *1 | 100 VAC input | 81% typ. | 81% typ. | 82% typ. | 82% typ. | |
200 VAC input | 85% typ. | 85% typ. | 87% typ. | 87% typ. | ||
230 VAC input | 85% typ. | 86% typ. | 87% typ. | 87% typ. | ||
Input | Voltage range *1 | Single phase, 85 to 264 VAC, 120 to 370 VDC | ||||
Frequency *1 | 50/60 Hz (47 to 63 Hz) | |||||
Current *1 | 100 VAC input | 4.2 A typ. | ||||
200 VAC input | 2.1 A typ. | |||||
Power factor *1 | 0.9 min. | |||||
Leakage current *1 |
100 VAC input | 0.5 mA max. | ||||
200 VAC input | 1 mA max. | |||||
Inrush current *1 (for a cold start at 25°C) |
100 VAC input | 14 A typ. | ||||
200 VAC input | 28 A typ. | |||||
Output | Rated Output Current | 25 A | 20 A | 14 A | 7 A | |
Voltage adjustment range *1 | -10% to 15% (with V.ADJ) | |||||
Ripple & Noise voltage *1 |
100 to 240 VAC input |
140 mVp-p max. | 270 mVp-p max. | 150 mVp-p max. | 330 mVp-p max. | |
Input variation influence *1 | 0.5% max. | |||||
Load variation influence *1 | 1.0% max. | |||||
Temperature variation influence |
100 to 240 VAC input |
0.05%/°C max. | ||||
Startup time *1 | 100 VAC input | 1,000 ms max. | ||||
200 VAC input | 1,000 ms max. | |||||
Hold time *1 | 100 VAC input | 30 ms typ. | 30 ms typ. | 30 ms typ. 40 ms typ. (Extended hold time type) |
30 ms typ. | |
200 VAC input | 30 ms typ. | 25 ms typ. | 30 ms typ. 40 ms typ. (Extended hold time type) |
30 ms typ. | ||
Additional functions |
Overload protection | Yes, automatic reset | ||||
Overvoltage protection *1 | Yes, 120% or higher of rated output voltage, power shut off (shut off the input voltage and turn on the input again) |
|||||
Overheat protection | Yes, power shut off (shut off the input voltage and turn on the input again) |
|||||
Series operation | Yes (For up to two Power Supplies, external diodes are required.) | |||||
Parallel operation | No (However, backup operation is possible, external diodes are required.) | |||||
Remote sensing | No | |||||
Remote control | Yes (Only for models with remote control option) | |||||
Output indicator | Yes (LED: Green) | |||||
Insulation | Withstand voltage | 3 kVAC for 1 min. (between all input terminals and output terminals) current cutoff 20 mA |
||||
2 kVAC for 1 min. (between all input terminals and PE terminals) current cutoff 20 mA |
||||||
1 kVAC for 1 min. (between all output terminals and PE terminals) current cutoff 20 mA |
||||||
Only Remote control 500 VAC for 1 min. (between all output terminals and RC terminals) current cutoff 20 mA |
||||||
Insulation resistance | 100 MΩ min. (between all output terminals and all input terminals/PE terminals) at 500 VDC |
|||||
Environ- ment |
Ambient operating temperature |
-20 to 70°C (Derating is required according to the temperature.) (with no condensation or icing) |
||||
Storage temperature | -25 to 75°C (with no condensation or icing) | |||||
Ambient operating humidity | 90% max. (Storage humidity: 90% max.) | |||||
Vibration resistance | 10 to 55 Hz, 4.5 G max., 0.375-mm half amplitude for 2 h each in X, Y, and Z directions |
|||||
Shock resistance | 150 m/s2, 3 times each in ±X, ±Y, ±Z directions | |||||
Reliability | MTBF | 135,000 hrs min. | ||||
Life expectancy *1 | 10 years min. | |||||
Con- struction |
Dimensions (W×H×D) | Refer to Dimensions. | ||||
Weight | 700 g | |||||
Cooling fan | Yes | |||||
Degree of protection | — | |||||
Standards | Harmonic current emissions | Conforms to EN 61000-3-2 | ||||
EMI *1 | Conducted Emissions |
Conforms to EN 61204-3 Class B, EN 55011 Class B | ||||
Radiated Emissions |
Conforms to EN 61204-3 Class B, EN 55011 Class B | |||||
EMS | Conforms to EN 61204-3 high severity levels | |||||
Safety Standards *2 | UL 508 (Listing, excluding models with remote control option) UL 508 (Recognition, models with remote control option) UL 62368-1 (Recognition, OVCII [≤ 3,000 m], Pol2) CSA C22.2 No.107.1 (excluding models with remote control option) CSA C22.2 No.62368-1 (excluding models with remote control option) EN 62477-1 (OVCIII [≤ 2,000 m], OVCII [> 2,000 m and ≤ 3,000 m], Pol2) EN/IEC 62368-1 (OVCII [≤ 3,000 m], Pol2) Conforms to EN/IEC 61558-2-16 Conforms to PELV (EN/IEC 60204-1) RCM (EN61000-6-4) BIS (IS 13252 (Part 1)/IEC 60950-1) (Output voltage 24 V type only. However, excluding S8FSG30024C-500 and S8FS-G30024CD-500.) |
|||||
Marine Standards | No | |||||
SEMI | Conforms to F47-0706 (200 VAC input) |
Power rating | 600 W | |||||
---|---|---|---|---|---|---|
Output voltage (VDC) | 12 V | 15 V | 24 V | 48 V | ||
Efficiency *1 | 100 VAC input | 84% typ. | 84% typ. | 85% typ. | 88% typ. | |
200 VAC input | 88% typ. | 88% typ. | 89% typ. | 92% typ. | ||
230 VAC input | 88% typ. | 88% typ. | 90% typ. | 92% typ. | ||
Input | Voltage range *1 | Single phase, 85 to 264 VAC, 120 to 350 VDC | ||||
Frequency *1 | 50/60 Hz (47 to 63 Hz) | |||||
Current *1 | 100 VAC input | 7.7 A typ. | ||||
200 VAC input | 3.8 A typ. | |||||
Power factor *1 | 0.9 min. | |||||
Leakage current *1 |
100 VAC input | 0.5 mA max. | ||||
200 VAC input | 1 mA max. | |||||
Inrush current *1 (for a cold start at 25°C) |
100 VAC input | 14 A typ. | ||||
200 VAC input | 28 A typ. | |||||
Output | Rated Output Current | 50 A | 40 A | 27 A | 13 A | |
Voltage adjustment range *1 | -10% to 15% (with V.ADJ) | |||||
Ripple & Noise voltage *1 |
100 to 240 VAC input |
170 mVp-p max. | 170 mVp-p max. | 280 mVp-p max. | 340 mVp-p max. | |
Input variation influence *1 | 0.5% max. | |||||
Load variation influence *1 | 1.0% max. | |||||
Temperature variation influence |
100 to 240 VAC input |
0.05%/°C max. | ||||
Startup time *1 | 100 VAC input | 1,000 ms max. | ||||
200 VAC input | 1,000 ms max. | |||||
Hold time *1 | 100 VAC input | 30 ms typ. | 25 ms typ. | 30 ms typ. 40 ms typ. (Extended hold time type) |
30 ms typ. | |
200 VAC input | 30 ms typ. | 25 ms typ. | 30 ms typ. 40 ms typ. (Extended hold time type) |
30 ms typ. | ||
Additional functions |
Overload protection | Yes, automatic reset | ||||
Overvoltage protection *1 | Yes, 120% or higher of rated output voltage, power shut off (shut off the input voltage and turn on the input again) |
|||||
Overheat protection | Yes, power shut off (shut off the input voltage and turn on the input again) | |||||
Series operation | Yes (For up to two Power Supplies, external diodes are required.) | |||||
Parallel operation | Yes (up to five Power Supplies, S8FS-G60024 (models with parallel operation option) only). |
|||||
Remote sensing | No | |||||
Remote control | Yes (Only Remote control) | |||||
Output indicator | Yes (LED: Green) | |||||
Insulation | Withstand voltage | 3 kVAC for 1 min. (between all input terminals and output terminals) current cutoff 20 mA |
||||
2 kVAC for 1 min. (between all input terminals and PE terminals) current cutoff 20 mA |
||||||
1 kVAC for 1 min. (between all output terminals and PE terminals) current cutoff 20 mA |
||||||
Only Remote control 500 VAC for 1 min. (between all output terminals and RC terminals) current cutoff 20 mA |
||||||
Insulation resistance | 100 MΩ min. (between all output terminals and all input terminals/PE terminals) at 500 VDC |
|||||
Environ- ment |
Ambient operating temperature |
-20 to 70°C (Derating is required according to the temperature.) (with no condensation or icing) |
||||
Storage temperature | -25 to 75°C (with no condensation or icing) | |||||
Ambient operating humidity | 90% max. (Storage humidity: 90% max.) | |||||
Vibration resistance | 10 to 55 Hz, 4.5 G max., 0.375-mm half amplitude for 2 h each in X, Y, and Z directions |
|||||
Shock resistance | 150 m/s2, 3 times each in ±X, ±Y, ±Z directions | |||||
Reliability | MTBF | 135,000 hrs min. | ||||
Life expectancy *1 | 10 years min. | |||||
Con- struction |
Dimensions (W×H×D) | Refer to Dimensions. | ||||
Weight | 1,050 g | |||||
Cooling fan | Yes | |||||
Degree of protection | — | |||||
Standards | Harmonic current emissions | Conforms to EN 61000-3-2 | ||||
EMI *1 | Conducted Emissions |
Conforms to EN 61204-3 Class B, EN 55011 Class B | ||||
Radiated Emissions |
Conforms to EN 61204-3 Class B, EN 55011 Class B | |||||
EMS | Conforms to EN 61204-3 high severity levels | |||||
Safety Standards *2 | UL 508 (Listing, excluding models with remote control option) UL 508 (Recognition, models with remote control option) UL 62368-1 (Recognition, OVCII [≤ 3,000 m], Pol2) CSA C22.2 No.107.1 (excluding models with remote control option) CSA C22.2 No.62368-1 (excluding models with remote control option) EN 62477-1 (OVCIII [≤ 2,000 m], OVCII [> 2,000 m and ≤ 3,000 m], Pol2) EN/IEC 62368-1 (OVCII [≤ 3,000 m], Pol2) Conforms to EN/IEC 61558-2-16 Conforms to PELV (EN/IEC 60204-1) RCM (EN61000-6-4) BIS (IS 13252 (Part 1)/IEC 60950-1) (Output voltage 24 V type only. However, excluding S8FSG60024C-500 and S8FS-G60024CD-500.) |
|||||
Marine Standards | No | |||||
SEMI | Conforms to F47-0706 (200 VAC input) |
*1. Refer to Ratings, Characteristics, and Functions below.
*2. Refer to Standard Compliance below.
Ratings, Characteristics, and Functions
Efficiency | The value is when both rated output voltage and rated output current are satisfied. |
||
---|---|---|---|
Input | Voltage range | Do not use an inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal temperature of the Power Supply may result in ignition or burning. |
|
Frequency | |||
Current | The value is when both rated output voltage and rated output current are satisfied. |
||
Power factor | The value is when both rated output voltage and rated output current are satisfied. |
||
Leakage current | The values are determined according to the Act on Power Supply Safety of Electrical Appliances and Materials. |
||
Inrush current (for a cold start at 25°C) |
For a cold start at 25°C. Refer to the following figure. | ||
Output | Voltage adjustment range | If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than +15% of the voltage adjustment range. When adjusting the output voltage, confirm the actual output voltage from the Power Supply and be sure that the load is not damaged. |
|
Ripple & Noise voltage | The value is when both rated output voltage and rated output current are satisfied. A characteristic when the ambient operating temperature is 25°C. |
||
Input variation influence | This is the maximum variation in the output voltage when the input voltage is gradually changed within the allowable input voltage range at the rated output voltage and rated output current. |
||
Load variation influence | This is the value when the output current is changed from 0 A to the rated output current while the input voltage is within the allowable input voltage. |
||
Startup time | The value is when both rated output voltage and rated output current are satisfied. For a cold start at 25°C. Refer to the following figure. |
||
Hold time | The value is when both rated output voltage and rated output current are satisfied. At 25°C. Refer to the following figure. |
||
Additional functions |
Overvoltage protection | Refer to Overvoltage Protection on Data Sheet for the time when input voltage shuts off and input turns on again. |
|
Reliability | Life expectancy | Refer to Recommended Replacement Periods and Periodic Replacement for Preventive Maintenance on Data Sheet for details. |
|
Standards | EMI | Conducted Emissions | The 150-W and higher models conform to Class B when an aluminum plate is set under the Power Supply. |
Standard Compliance
• The input voltage range for compliance with EC Directives and other safety standards (UL, EN, etc.) is 90 to 264 VAC.
• EN/IEC 61558-2-16
To comply with EN/IEC 60204-1 (Machine Safety), a transformer is required in the control circuit. If, however, a Power Supply that has a built-in transformer that complies with EN/IEC 6155-8-2-16 is used, an external transformer is not required.
• Safety standard targets during a DC input *
During a DC input, UL 62368-1, cUR (CSA C22.2 No. 62368-1), EN/IEC 62368-1, EN 62477-1, EN/IEC 61558-2-16, and EN/IEC 60204-1 are safety standard targets. (However, the input voltage range is 120 to 320 VDC. The safety standards during DC input are not acquired for the S8FS-G60048[].)
It is possible to comply with the safety standards by connecting a UL-authenticated fuse. Select a UL-authenticated fuse that satisfies the following conditions:
S8FS-G015[][]/030[][] (320 VDC or above, 3 A)
S8FS-G050[][] (320 VDC or above, 4 A)
S8FS-G100[][] (320 VDC or above, 8 A)
S8FS-G150[][] (320 VDC or above, 10 A)
S8FS-G300[][] (320 VDC or above, 12 A)
S8FS-G600[][] (320 VDC or above, 20 A)
• To comply with the PELV output of the EN/IEC 60204-1, ground the output negative side (-V) to PE. *
* Applicable to products produced from May 2018
• EN/IEC 61558-2-16
To comply with EN/IEC 60204-1 (Machine Safety), a transformer is required in the control circuit. If, however, a Power Supply that has a built-in transformer that complies with EN/IEC 6155-8-2-16 is used, an external transformer is not required.
• Safety standard targets during a DC input *
During a DC input, UL 62368-1, cUR (CSA C22.2 No. 62368-1), EN/IEC 62368-1, EN 62477-1, EN/IEC 61558-2-16, and EN/IEC 60204-1 are safety standard targets. (However, the input voltage range is 120 to 320 VDC. The safety standards during DC input are not acquired for the S8FS-G60048[].)
It is possible to comply with the safety standards by connecting a UL-authenticated fuse. Select a UL-authenticated fuse that satisfies the following conditions:
S8FS-G015[][]/030[][] (320 VDC or above, 3 A)
S8FS-G050[][] (320 VDC or above, 4 A)
S8FS-G100[][] (320 VDC or above, 8 A)
S8FS-G150[][] (320 VDC or above, 10 A)
S8FS-G300[][] (320 VDC or above, 12 A)
S8FS-G600[][] (320 VDC or above, 20 A)
• To comply with the PELV output of the EN/IEC 60204-1, ground the output negative side (-V) to PE. *
* Applicable to products produced from May 2018
Inrush Current, Startup Time, Output Hold Time
Note:
The total inrush current of all of the Power Supplies will flow for parallel operation or backup operation.
Sufficiently check the fusing characteristics of fuses and the operating characteristics of breakers and select fuses and breakers so that external fuses will not burn out or breakers will not operate due to inrush current.
Ripple Noise Voltage
The specified standard for the ripple voltage noise was measured with a measurement circuit that is based on JEITA standard RC-9131A.
Model | S8FS-G03024CD, S8FS-G05024C, S8FS-G05024CD, S8FS-G10024C, S8FS-G10024CD, S8FS-G15024C, S8FS-G30024C, S8FS-G30024CD, S8FS-G60024C, S8FS-G60024CD |
---|
Weight | N/A |
---|---|
Model | S8FS-G03024CD, S8FS-G05024C, S8FS-G05024CD, S8FS-G10024C, S8FS-G10024CD, S8FS-G15024C, S8FS-G30024C, S8FS-G30024CD, S8FS-G60024C, S8FS-G60024CD |
Related products
-
Select options This product has multiple variants. The options may be chosen on the product page Details
-
Select options This product has multiple variants. The options may be chosen on the product page Details
-
Select options This product has multiple variants. The options may be chosen on the product page Details
-
Select options This product has multiple variants. The options may be chosen on the product page Details
-
Select options This product has multiple variants. The options may be chosen on the product page Details
-
Select options This product has multiple variants. The options may be chosen on the product page Details