Power rating |
Input voltage | Output voltage (VDC) |
Output current |
Built- in fan |
Model with terminal block facing upward |
---|---|---|---|---|---|
200 W | 100 to 120 VAC, 200 to 240 VAC (allowable range: 90 to 132 VAC, 180 to 264 VAC, or 254 to 373 VDC (Select with the switch.) *2) |
5 V | 40 A | None | S8FS-C20005 |
12 V | 17 A | S8FS-C20012 | |||
24 V | 8.8 A | S8FS-C20024 | |||
36 V | 5.9 A | S8FS-C20036 | |||
48 V | 4.43 A | S8FS-C20048 |
Note: You can use brackets that are sold separately to mount the Power Supplies to DIN Rail. Refer to Mounting Brackets
(Order Separately) on Data Sheet.
*1. The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC.
*2. The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 120 VAC, 200 to 240 VAC.
Power rating | 200 W | ||||||
---|---|---|---|---|---|---|---|
Output voltage (VDC) | 5 V | 12 V | 24 V | 36 V | 48 V | ||
Efficiency * | 115 VAC input | 81% typ. | 85% typ. | 88% typ. | 89% typ. | 88% typ. | |
230 VAC input | 81% typ. | 87% typ. | 88% typ. | 90% typ. | 90% typ. | ||
Input | Voltage range * | Single phase 90 to 132 VAC , Single phase 180 to 264 VAC , 254 to 373 VDC Select with the switch. (The L terminal for the DC input is the positive side and safety standards do not apply.) (Derating is required according to the input voltage. Refer to Derating Curves on Data Sheet.) |
|||||
Frequency * | 50 /60 Hz (47 to 450 Hz) | ||||||
Current * | 115 VAC input | 4 A typ. | |||||
230 VAC input | 2.3 A typ. | ||||||
Power factor | — | ||||||
Leakage current |
115 VAC input | 0.35 mA | 0.25 mA | 0.40 mA | 0.20 mA | 0.40 mA | |
230 VAC input | 0.60 mA | 0.50 mA | 0.75 mA | 0.45 mA | 0.80 mA | ||
Inrush current * (for a cold start at 25°) |
115 VAC input | 16 A typ. | |||||
230 VAC input | 32 A typ. | ||||||
Output | Rated Output Current | 40 A | 17 A | 8.8 A | 5.9 A | 4.43 A | |
Voltage adjustment range * | -10% to 10% (with V. ADJ) | ||||||
Ripple & Noise voltage * |
100 to 120 VAC/200 to 240 VAC input |
60 mVp-p max. |
60 mVp-p max. |
110 mVp-p max. |
130 mVp-p max. |
120 mVp-p max. |
|
Input variation influence * | 0.5% max. | ||||||
Load variation influence * | 1.0% max. | ||||||
Temperature variation influence |
100 to 120 VAC/200 to 240 VAC input |
0.03%/°C max. | |||||
Startup time * |
115 VAC input | 620 ms typ. | 630 ms typ. | 580 ms typ. | 630 ms typ. | 620 ms typ. | |
230 VAC input | 600 ms typ. | 610 ms typ. | 550 ms typ. | 600 ms typ. | 600 ms typ. | ||
Hold time * | 115 VAC input | 32 ms typ. | 30 ms typ. | 38 ms typ. | 30 ms typ. | 31 ms typ. | |
230 VAC input | 37 ms typ. | 35 ms typ. | 45 ms typ. | 37 ms typ. | 37 ms typ. | ||
Addi- tional func- tions |
Overload protection | Yes, automatic reset | |||||
Overvoltage protection * | Yes, 115% or higher of rated output voltage, power shut off (shut off the input voltage and turn on the input again) |
||||||
Overheat protection | No | ||||||
Series operation | Yes (For up to 2 Power Supplies, external diodes are required.) | ||||||
Parallel operation | No (However, backup operation is possible, external diodes are required.) | ||||||
Remote sensing | No | ||||||
Remote control | No | ||||||
Output indicator | Yes (LED: Green) | ||||||
Insula- tion |
Withstand voltage | 3 kVAC for 1 min. (between all input terminals and output terminals) current cutoff 20 mA |
|||||
2 kVAC for 1 min. (between all input terminals and PE terminals) current cutoff 20 mA |
|||||||
1 kVAC for 1 min. (between all output terminals and PE terminals) current cutoff 20 mA |
|||||||
Insulation resistance | 100 MΩ min. (between all output terminals and all input terminals/PE terminals) at 500 VDC |
||||||
Envi- ron- ment |
Ambient operating temperature | -20 to 50°C (Derating is required according to the temperature. Refer to Derating Curves on Data Sheet.) (with no condensation or icing) |
|||||
Storage temperature | -40 to 85°C (with no condensation or icing) | ||||||
Ambient operating humidity | 20% to 90% (Storage humidity: 10% to 95%) | ||||||
Vibration resistance | 10 to 55 Hz, 0.375-mm half amplitude for 2 h each in X, Y, and Z directions 10 to 500 Hz, 0.26-mm half amplitude for 1 h each in X, Y, and Z directions |
||||||
Shock resistance | 150 m/s2, 3 times each in ±X, ±Y, ±Z directions | ||||||
Relia- bility |
MTBF | 135,000 hrs min. | |||||
Life expectancy * | 10 years min. | ||||||
Con- struc- tion |
Dimensions (W × H × D) | Refer to Dimensions. | |||||
Weight | 700 g max. | ||||||
Cooling fan | No | ||||||
Degree of protection | — | ||||||
Stan- dards |
Harmonic current emissions | — | |||||
EMI | Conducted Emissions |
Conforms to EN 61204-3 Class A, EN 55011 Class A | |||||
Radiated Emissions |
Conforms to EN 61204-3 Class A, EN 55011 Class A | ||||||
EMS | Conforms to EN 61204-3 high severity levels | ||||||
Safety Standards | Approved Standards UL: cURus UL 62368-1 (Recognition) OVC II Pol2 CSA: cURus C22.2 No62368-1 Conformed Standards EN: EN 62368-1 OVC II Pol2 RCM (EN61000-6-4) |
||||||
Marine Standards | No | ||||||
SEMI | No |