R-SP-E12 – Segment Protector – PEPPERL+FUCHS FieldConnex Ethernet-APL and Fieldbus Infrastructure

$ 862.40

SKU: R-SP-E12

PEPPERL+FUCHS FieldConnex is connectivity from the market leader and always the right choice. With FOUNDATION fieldbus H1 and PROFIBUS PA, field devices can be easily and reliably integrated into any process plant. Fieldbus ensures smooth digital data communication between the plant and the control system and also provides power supply for all field devices.

General specifications
Design / Mounting Cabinet installation
Fieldbus connection
Power dissipation 250 mW
Main cable (Trunk)
Rated voltage 9 … 32 V DC
Outputs
Number of outputs 12
Rated voltage max. 32 V
Rated current max. 40 mA
Short-circuit current max. 52 mA
Self current consumption max. 9 mA
Voltage drop main cable/outputs max. 1.3 V
Terminating resistor selectable 100 Ω integrated
Surge protection trunk, spurs overvoltage protected if voltage exceeds typ. 39 V, max. 41 V
Indicators/operating means
LED PWR green: Fieldbus voltage > 10 V
LED CHANNEL ERROR red flashing: short-circuit
LED COM yellow: bus activity
LED TERM ON yellow: termination activated
Directive conformity
Electromagnetic compatibility
Directive 2004/108/EC EN 61326-1:2006
Standard conformity
Electromagnetic compatibility NE 21:2006
Degree of protection IEC 60529
Fieldbus standard IEC 61158-2
Shock resistance EN 60068-2-27
Vibration resistance EN 60068-2-6
Ambient conditions
Ambient temperature -40 … 70 °C (-40 … 158 °F)
Storage temperature -40 … 85 °C (-40 … 185 °F)
Relative humidity 95 % non-condensing
Shock resistance 15 g , 11 ms
Vibration resistance 5 g , 10 … 150 Hz
Mechanical specifications
Connection type screw fixing
Core cross section max. 2.5 mm2 / AWG 12-24
Housing material Polycarbonate
Housing width 216 mm
Housing height 100 mm
Housing depth 50 mm
Degree of protection IP20
Mass 800 g
Mounting DIN rail mounting
Coating resin filled
Data for application in connection with hazardous areas
EU-type examination certificate PTB 04 ATEX 2100 X
Marking Ex-Hexagon II 2 G Ex e mb IIC T4 Gb
Maximum values
Rated voltage ≤ 35 V
Prospective short-circuit current 100 A
Directive conformity
Directive 94/9/EC EN 60079-0:2012 , EN 60079-7:2007 , EN 60079-18:2009
International approvals
IECEx approval IECEx PTB 05.0010X
Approved for Ex me II T4
Certificates and approvals
Marine approval DNV A-14038
General information
Supplementary information EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.
Weight 0.8 kg
Dimensions 5.0 × 21.6 × 10.0 cm

Related products