Inosaki is one of the largest Phoenix Contact Distributors to provide terminal block, interface module, power supply and relay. And our best offer for terminal block types are Feed-through, Fuse Modular, Spring Cage, Double Level, and Multi-level, hence the series model references to PT Series, ST Series, TB Series, UT Series, UK Series. In additional for power supply are QUINT Power, STEP Power, Trio Power, and UNO Power. Please email us for catalog: sales@inosaki.my
Product Description
The fourth generation of the high-performance QUINT POWER power supplies ensures superior system availability by means of new functions. Signaling thresholds and characteristic curves can be individually adjusted via the NFC interface.
The unique SFB technology and preventive function monitoring of the QUINT POWER power supply increase the availability of your application.
Dimensions
Width |
120 mm |
Height |
130 mm |
Depth |
125 mm |
Installation dimensions |
Installation distance right/left |
5 mm / 5 mm |
Installation distance top/bottom |
50 mm / 50 mm |
Ambient Conditions
Degree of protection |
IP20 |
Ambient temperature (operation) |
-25 °C … 70 °C (> 60 °C Derating: 2,5 %/K) |
Ambient temperature (storage/transport) |
-40 °C … 85 °C |
Ambient temperature (start-up type tested) |
-40 °C |
Maximum altitude |
≤ 5000 m (> 2000 m, observe derating) |
Climatic class |
3K3 (in acc. with EN 60721) |
Max. permissible relative humidity (operation) |
≤ 95 % (at 25 °C, non-condensing) |
Shock |
11 ms, 15 g, in each space direction (according to IEC 60068-2-27) |
Vibration (operation) |
5 Hz … 100 Hz resonance search 0.7g, 90 min., resonance frequency 0.7g, 90 min. (in accordance with DNV GL Class A)
5 Hz … 100 Hz resonance search 2.3g, 90 min., resonance frequency 2.3g, 90 min. (according to DNV GL Class C) mounted with UWA 130 – 2901664 |
Input Data
AC operation
Network type |
Star network |
Nominal input voltage range |
3x 400 V AC … 500 V AC |
2x 400 V AC … 500 V AC |
Input voltage range |
3x 400 V AC … 500 V AC -20 % … +10 % |
2x 400 V AC … 500 V AC -10 % … +10 % |
Typical national grid voltage |
400 V AC |
480 V AC |
Voltage type of supply voltage |
AC/DC |
Inrush current |
typ. 1.5 A (at 25 °C) |
Inrush current integral (I2t) |
< 0.06 A2s |
Inrush current limitation |
2 A (after 1 ms) |
AC frequency range |
50 Hz … 60 Hz -10 % … +10 % |
Frequency range (fN) |
50 Hz … 60 Hz -10 % … +10 % |
Mains buffering time |
typ. 26 ms (3x 400 V AC) |
typ. 26 ms (3x 480 V AC) |
Current consumption |
3x 1.8 A (400 V AC) |
3x 1.5 A (480 V AC) |
2x 3 A (400 V AC) |
2x 2.5 A (480 V AC) |
3x 1.5 A (500 V AC) |
2x 2.4 A (500 V AC) |
Nominal power consumption |
1217 VA |
Protective circuit |
Transient surge protection; Varistor, gas-filled surge arrester |
Power factor (cos phi) |
0.95 |
Switch-on time |
< 1 s |
Typical response time |
300 ms (from SLEEP MODE) |
Recommended breaker for input protection |
3x 4 A … 20 A (Characteristic B, C, D, K or comparable) |
Recommended fuse for input protection |
≥ 300 V AC |
Discharge current to PE |
< 3.5 mA |
1 mA (550 V AC, 60 Hz) |
DC operation
Nominal input voltage range |
± 260 V DC … 300 V DC |
Input voltage range |
± 260 V DC … 300 V DC -13 % … +30 % |
Current consumption |
2.2 A (±260 V DC) |
1.9 A (±300 V DC) |
Nominal power consumption |
1217 VA |
Recommended breaker for input protection |
1x 6 A (10 x 38 mm, 30 kA L/R = 2 ms) |
Recommended fuse for input protection |
≥ 1000 V DC |
Output Data
Efficiency |
typ. 95.9 % (400 V AC) |
typ. 96.2 % (480 V AC) |
Nominal output voltage |
48 V DC |
Setting range of the output voltage (USet) |
48 V DC … 56 V DC (constant capacity) |
Nominal output current (IN) |
20 A |
Static Boost (IStat.Boost) |
22.5 A |
Dynamic Boost (IDyn.Boost) |
30 A (5 s) |
Selective Fuse Breaking (ISFB) |
105 A (15 ms) |
Magnetic circuit breaker tripping |
A1…A20 / B2…B10 / C1…C6 / Z1…Z16 |
Derating |
> 60 °C … 70 °C (2.5%/K) |
Feedback voltage resistance |
≤ 60 V DC |
Protection against overvoltage at the output (OVP) |
≤ 60 V DC |
Control deviation |
< 0.5 % (Static load change 10 % … 90 %) |
< 2 % (Dynamic load change 10 % … 90 %, (10 Hz)) |
< 0.25 % (change in input voltage ±10 %) |
Residual ripple |
< 50 mVPP (with nominal values) |
Short-circuit-proof |
yes |
No-load proof |
yes |
Output power |
960 W |
1080 W |
1440 W |
Maximum no-load power dissipation |
< 6 W (400 V AC) |
< 6 W (480 V AC) |
Power loss nominal load max. |
< 41 W (400 V AC) |
< 41 W (480 V AC) |
Power dissipation SLEEP MODE |
< 1 W (400 V AC) |
< 1 W (480 V AC) |
Crest factor |
typ. 1.67 (400 V AC) |
typ. 1,63 (480 V AC) |
Rise time |
< 1 s (UOut = 10 % … 90 %) |
Connection in parallel |
yes, for redundancy and increased capacity |
Connection in series |
yes |
Commercial Data
Item number |
2904627 |
Packing unit |
1 pc |
Minimum order quantity |
1 pc |
Product Key |
CMPI34 |
GTIN |
4063151023171 |
Weight per Piece (including packing) |
2,811.6 g |
Weight per Piece (excluding packing) |
2,811.6 g |
Customs tariff number |
85044083 |
Country of origin |
TH |
Standards and Regulations
Rail applications |
EN 50121-3-2 |
EN 50121-5 |
IEC 62236-3-2 |
IEC 62236-5 |
Standard – Limitation of mains harmonic currents |
EN 61000-3-2 |
Standard – Electrical safety |
IEC 61010-2-201 (SELV) |
Standard – Safety extra-low voltage |
IEC 61010-1 (SELV) |
IEC 61010-2-201 (PELV) |
Standard – Safe isolation |
IEC 61558-2-16 |
IEC 61010-2-201 |
Standard – safety for equipment for measurement, control, and laboratory use |
IEC 61010-1 |
Standard – Safety of transformers |
EN 61558-2-16 |
Battery charging |
DIN 41773-1 |
Approval – requirement of the semiconductor industry with regard to mains voltage dips |
SEMI F47-0706, EN 61000-4-1 |
Approval data
CSA |
CAN/CSA-C22.2 No. 61010-1-12 |
CAN/CSA-C22.2 No. 61010-2-201 |
SIQ |
CB-Scheme (IEC 61010-1, IEC 61010-2-201) |
UL approvals |
UL Listed UL 61010-1 |
UL Listed UL 61010-2-201 |
UL 121201 & CSA C22.2 No. 213-17 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location) |
EMC Data
Low Voltage Directive |
Conformance with Low Voltage Directive 2014/35/EC |
Electromagnetic compatibility |
Conformance with EMC Directive 2014/30/EU |
EMC requirements for noise emission |
EN 61000-6-3 |
EN 61000-6-4 |
EMC requirements for noise immunity |
EN 61000-6-1 |
EN 61000-6-2 |
EMC requirements, power plant |
IEC 61850-3 |
EN 61000-6-5 |
Conducted noise emission |
EN 55016 |
EN 61000-6-3 (Class B) |
Interference emission |
Interference emission in accordance with EN 61000-6-3 (residential and commercial) and EN 61000-6-4 (industrial) |
Noise emission |
Additional basic standard EN 61000-6-5 (immunity in power station), IEC/EN 61850-3 (energy supply) |
Noise emission |
EN 55016 |
EN 61000-6-3 (Class B) |
Noise immunity |
Immunity in accordance with EN 61000-6-1 (residential), EN 61000-6-2 (industrial), and EN 61000-6-5 (power station equipment zone), IEC/EN 61850-3 (power supply) |
DNV GL conducted interference |
Class A |
Additional text |
Area power distribution |
DNV GL noise radiation |
Class B |
Additional text |
Bridge and deck area |