QUINT4-PS/1AC/24DC/20/+ – 2904617 – Phoenix Contact Power Supply
$ 601.04
SKU: Phoenix Contact 2904617
Inosaki is one of the largest Phoenix Contact Distributors to provide terminal block, interface module, power supply and relay. And our best offer for terminal block types are Feed-through, Fuse Modular, Spring Cage, Double Level, and Multi-level, hence the series model references to PT Series, ST Series, TB Series, UT Series, UK Series. In additional for power supply are QUINT Power, STEP Power, Trio Power, and UNO Power. Please email us for catalog: sales@inosaki.my
Dimensions
Article Number | 2904617 |
---|---|
Width | 70 mm |
Height | 130 mm |
Depth | 125 mm |
Width with alternative assembly | 122 mm |
Height with alternative assembly | 130 mm |
Depth with alternative assembly | 73 mm |
Installation distance right/left | 5 mm / 5 mm |
Installation distance top/bottom | 50 mm / 50 mm |
Ambient conditions
Degree of protection | IP20 |
---|---|
Inflammability class in acc. with UL 94 (housing / terminal blocks) | V0 |
Ambient temperature (operation) | -40 °C … 75 °C (> 60 °C Derating: 2,5 %/K) |
Ambient temperature (storage/transport) | -40 °C … 85 °C |
Max. permissible relative humidity (operation) | ≤ 100 % (at 25 °C, non-condensing) |
Climatic class | 3K3 (in acc. with EN 60721) |
Degree of pollution | 2 |
Installation height | ≤ 5000 m (> 2000 m, observe derating) |
Input data
Nominal input voltage range | 100 V AC … 240 V AC |
---|---|
110 V DC … 250 V DC | |
Input voltage range | 100 V AC … 240 V AC -15 % … +10 % |
110 V DC … 250 V DC -18 % … +40 % | |
Dielectric strength maximum | 300 V AC 60 s |
AC frequency range | 50 Hz … 60 Hz -10 % … +10 % |
Frequency range (fN) | 50 Hz … 60 Hz -10 % … +10 % |
16.7 Hz (acc. to EN 50163) | |
Discharge current to PE | < 3.5 mA |
Current consumption | 6.8 A (100 V AC) |
5.5 A (120 V AC) | |
2.8 A (230 V AC) | |
2.7 A (240 V AC) | |
Nominal power consumption | 520 VA |
Inrush current | typ. 10 A (at 25 °C) |
Mains buffering time | typ. 36 ms (120 V AC) |
typ. 36 ms (230 V AC) | |
Input fuse | 12 A (slow-blow, internal) |
Recommended breaker for input protection | 10 A … 16 A (Characteristic B, C, D, K or comparable) |
Type of protection | Transient surge protection |
Protective circuit/component | Varistor, gas-filled surge arrester |
Output data
Nominal output voltage | 24 V DC |
---|---|
Setting range of the output voltage (USet) | 24 V DC … 28 V DC (constant capacity) |
Nominal output current (IN) | 20 A |
Static Boost (IStat.Boost) | 25 A |
Dynamic Boost (IDyn.Boost) | 30 A (5 s) |
Selective Fuse Breaking (ISFB) | 120 A (15 ms) |
Derating | > 60 °C … 70 °C (2.5%/K) |
Connection in parallel | yes, for redundancy and increased capacity |
Connection in series | yes |
Feedback voltage resistance | ≤ 35 V DC |
Protection against overvoltage at the output (OVP) | < 30 V DC (double protection incl. shutdown) |
Control deviation | < 0.5 % (Static load change 10 % … 90 %) |
< 2 % (Dynamic load change 10 % … 90 %, (10 Hz)) | |
< 0.25 % (change in input voltage ±10 %) | |
Residual ripple | < 30 mVPP (with nominal values) |
Output power | 480 W |
Typical response time | 300 ms (from SLEEP MODE) |
Maximum power dissipation in no-load condition | < 5 W (120 V AC) |
< 5 W (230 V AC) | |
Power loss nominal load max. | < 38 W (120 V AC) |
< 30 W (230 V AC) |
General
Net weight | 1.3 kg |
---|---|
Efficiency | typ. 92.7 % (120 V AC) |
typ. 94.2 % (230 V AC) | |
MTBF (IEC 61709, SN 29500) | > 868000 h (25 °C) |
> 524000 h (40 °C) | |
> 239000 h (60 °C) | |
Insulation voltage input/output | 4 kV AC (type test) |
2 kV AC (routine test) | |
Degree of protection | IP20 |
Protection class | I |
Inflammability class in acc. with UL 94 (housing / terminal blocks) | V0 |
Mounting position | horizontal DIN rail NS 35, EN 60715 |
Assembly instructions | Alignable: horizontally 0 mm at Pout <50% PN, 5 mm at Pout ≥50% PN, next to active components 15 mm, vertically 50 mm |
Connection data, input
Connection method | Screw connection |
---|---|
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 6 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 4 mm² |
Conductor cross section AWG min. | 30 |
Conductor cross section AWG max. | 10 |
Stripping length | 8 mm |
Connection data, output
Connection method | Screw connection |
---|---|
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 6 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 4 mm² |
Conductor cross section AWG min. | 30 |
Conductor cross section AWG max. | 10 |
Stripping length | 8 mm |
Connection data for signaling
Connection method | Screw connection |
---|---|
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 6 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 4 mm² |
Conductor cross section AWG min. | 30 |
Conductor cross section AWG max. | 10 |
Stripping length | 8 mm |
Standards
EMC requirements for noise immunity | EN 61000-6-1 |
---|---|
EN 61000-6-2 | |
EMC requirements for noise emission | EN 61000-6-3 |
EN 61000-6-4 | |
EMC requirements, power plant | IEC 61850-3 |
EN 61000-6-5 | |
HART FSK Physical Layer Test Specification Compliance | Output voltage UOut compliant |
Standard – Safety of transformers | EN 61558-2-16 |
Standard – Electrical safety | IEC 61010-2-201 (SELV) |
Standard – safety for equipment for measurement, control, and laboratory use | IEC 61010-1 |
Standard – Safety extra-low voltage | IEC 61010-1 (SELV) |
IEC 61010-2-201 (PELV) | |
Standard – Safe isolation | IEC 61558-2-16 |
Standard – Limitation of mains harmonic currents | EN 61000-3-2 |
Explosive atmosphere | IEC 60079-0 |
Mains variation/undervoltage | SEMI F47-0706, EN 61000-4-11 |
Rail applications | EN 50121-3-2 |
EN 50121-4 | |
EN 50121-5 | |
EN 50163 | |
IEC 62236-3-2 | |
IEC 62236-4 | |
IEC 62236-5 | |
Overvoltage category EN 61010-1 | II (≤ 5000 m) |
Overvoltage category EN 62477-1 | III (≤ 2000 m) |
Conformance/approvals
UL approvals | UL Listed UL 508 |
---|---|
UL/C-UL Recognized UL 60950-1 | |
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location) | |
CSA | CAN/CSA-C22.2 No. 60950-1-07 |
CSA-C22.2 No. 107.1-01 | |
SIQ | BG (type approved) |
Shipbuilding approval | DNV GL applied for |
EMC data
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
---|---|
Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
Conducted noise emission | EN 55016 |
EN 61000-6-3 (Class B) | |
Noise emission | EN 55016 |
EN 61000-6-3 (Class B) | |
Harmonic currents | EN 61000-3-2 |
EN 61000-3-2 (Class A) | |
Flicker | EN 61000-3-3 |
EN 61000-3-3 | |
DNV GL conducted interference | Class A |
Additional text | Area power distribution |
DNV GL noise radiation | Class B |
Additional text | Bridge and deck area |
Electrostatic discharge | EN 61000-4-2 |
Contact discharge | 8 kV (Test Level 4) |
Discharge in air | 15 kV (Test Level 4) |
Electromagnetic HF field | EN 61000-4-3 |
Frequency range | 80 MHz … 1 GHz |
Test field strength | 20 V/m (Test Level 3) |
Frequency range | 1 GHz … 6 GHz |
Test field strength | 10 V/m (Test Level 3) |
Comments | Criterion A |
Fast transients (burst) | EN 61000-4-4 |
Input | 4 kV (Test Level 4 – asymmetrical) |
Output | 4 kV (Test Level 4 – asymmetrical) |
Signal | 4 kV (Test Level 4 – asymmetrical) |
Comments | Criterion A |
Surge voltage load (surge) | EN 61000-4-5 |
Input | typ. 3 kV (Test Level 4 – symmetrical) |
typ. 6 kV (Test Level 4 – asymmetrical) | |
Output | 1 kV (Test Level 3 – symmetrical) |
2 kV (Test Level 3 – asymmetrical) | |
Signal | 4 kV (Test Level 4 – asymmetrical) |
Comments | Criterion A |
Conducted interference | EN 61000-4-6 |
I/O/S | asymmetrical |
Frequency range | 0.15 MHz … 80 MHz |
Voltage | 10 V (Test Level 3) |
Comments | Criterion A |
Power frequency magnetic field | EN 61000-4-8 |
Frequency | 16.7 Hz |
50 Hz | |
60 Hz | |
Test field strength | 100 A/m |
Additional text | 60 s |
Comments | Criterion A |
Frequency | 50 Hz |
60 Hz | |
Frequency range | 50 Hz … 60 Hz |
Test field strength | 1 kA/m |
Additional text | 3 s |
Frequency | 0 Hz |
Test field strength | 300 A/m |
Additional text | DC, 60 s |
Voltage dips | EN 61000-4-11 |
Voltage | 230 V AC |
Frequency | 50 Hz |
Voltage dip | 70 % |
Number of periods | 0.5 / 1 / 25 / 30 periods |
Additional text | Test Level 2 |
Comments | Criterion A: 0.5 / 1 / 25 / 30 periods |
Voltage dip | 40 % |
Number of periods | 5 / 10 / 50 periods |
Additional text | Test Level 2 |
Comments | Criterion A |
Voltage dip | 0 % |
Number of periods | 0,5 / 1 / 5 / 50 / 250 periods |
Additional text | Test Level 2 |
Comments | Criterion A: 0.5 / 1 period Criterion B: 5 / 50 / 250 periods |
Pulse-shape magnetic field | EN 61000-4-9 |
Test field strength | 1000 A/m |
Comments | Criterion A |
Damped oscillating magnetic field | EN 61000-4-10 |
Test field strength | 110 A/m |
Test level 1 | 100 kHz |
Test field strength | 110 A/m |
Test level 2 | 1 MHz |
Comments | Criterion A |
Attenuated sinusoidal oscillations (ring wave) | EN 61000-4-12 |
Input | 2 kV (Test Level 4 – symmetrical) |
4 kV (Test Level 4 – asymmetrical) | |
Comments | Criterion A |
Asymmetrical conducted disturbance variables | EN 61000-4-16 |
Test level 1 | 15 Hz 150 Hz (Test Level 4) |
Voltage | 30 V 3 V |
Test level 2 | 150 Hz 1.5 kHz (Test Level 4) |
Voltage | 3 V |
Test level 3 | 1.5 kHz 15 kHz (Test Level 4) |
Voltage | 3 V 30 V |
Test level 4 | 15 kHz 150 kHz (Test Level 4) |
Voltage | 30 V |
Test level 5 | 16.7 Hz 50 Hz 60 Hz (Test Level 4) |
Voltage | 30 V (Permanent) |
Test level 6 | 150 Hz 180 Hz (Test Level 4) |
Voltage | 30 V (Permanent) |
Test level 7 | 16.7 Hz 50 Hz 60 Hz (Test Level 4) |
Voltage | 300 V (1 s) |
Comments | Criterion A |
Attenuated oscillating wave | EN 61000-4-18 |
Input, output (test level 1) | 100 kHz 1 MHz (Test Level 3 – symmetrical) |
Voltage | 1 kV |
Input, output (test level 2) | 10 MHz |
Voltage | 1 kV |
Input, output (test level 3) | 100 kHz 1 MHz (Test Level 3 – asymmetrical) |
Voltage | 2.5 kV |
Signals (test level 1) | 100 kHz 1 MHz (Test Level 3 – symmetrical) |
Voltage | 1 kV |
Signals (test level 2) | 100 kHz 1 MHz (Test Level 3 – asymmetrical) |
Voltage | 2.5 kV |
Comments | Criterion A |
Criterion A | Normal operating behavior within the specified limits. |
Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
Criterion C | Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements. |
Environmental Product Compliance
REACh SVHC | Lead 7439-92-1 |
---|